HomeMy WebLinkAboutA17-0041_Lodge Twr-Unit 787 Submittal - 4009-9201_1503673920.pdf Features Provides additional notification appliance circuit (NAC) capacity with flexible operation modes and power-limited design Four, Class B NACs are standard:  Rated 2 A each for conventional reverse polarity 24 VDC notification appliances and providing multiple operation modes  Can be selected to provide synchronization for Simplex® visible notification strobe flashes  Capable of controlling TrueAlert non-addressable notification appliances operating with SmartSync two-wire control mode** Input control options:  IDNet addressable communications from a Simplex model 4010, 4010ES, 4100U, or 4100ES Fire Alarm Control Panel**  Or from one or two conventional 24 VDC NACs with multiple output control options IDNet communications control benefits:  Provides status monitoring and individual NAC control using a single address per 4009 IDNet NAC Extender  Supports IDNet “Device Level” earth fault location WALKTEST operation is available with either input choice Internal 8 A power supply/battery charger:  Charges internal batteries up to 12.7 Ah or up to 18 Ah batteries in external cabinet  Provides status monitoring of battery, input power, and earth faults  Rated 8 A for “Special Application” appliances; including Simplex 4901, 4903, 4904, and 4906 Series horns, strobes, horn/strobes, and speaker/strobes  Rated 6 A for “Regulated 24 DC” appliance power Optional 4009 IDNet NAC Extender modules:  IDNet Communications Repeater provides Class B or Class A output  IDNet Communications Fiber Optic Receiver/Repeater, available as Class B or Class X  Four additional Class B NACs, rated 1.5 A for Special Application appliances; 1 A for Regulated 24 DC appliance power  Class A, Two Circuit Adapter Module UL Listed to Standard 864 External Accessories IDNet communication fiber optic transmitters:  For applications requiring the data integrity available with fiber optic communications  Available as Class B or Class X  Mounts in standard six-gang electrical box External battery cabinet for 18 Ah batteries ALARM FIRE PULL DOWN PO W ER BEFO RE SERVI CI NG CAUTION DI SCO NNECT 4009 IDNet NAC EXTENDER T M Optional IDNet Channel Repeater SIMPLE XTIM EREC ORDERCO. 4090- 910 1 MONITO RZA M,CLA SSB INSTAL . INST R.574 - 183 DATEC ODE : 1 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 + 24V 0V +IDNET - IDNET ZONE PWR + ZONE PWR -IDC + IDC - Up to 8 NACs 4010 (shown) or 4010ES/4100ES/4100U Fire Alarm Control Panel Fire Alarm Control Panel with Conventional NACs Fiber Optic IDNet Communications NAC Control 2-Wire IDNet Communications FI RE ALARM CO NTRO L D I S C O N N E C T P O W E R B E F O R E S ER V I C I N G CAUTI O N * * SYSTEM I S NO RM AL * * 12: 02: 15pm M on 9- Feb- 98 S U P V A C K S Y S T E M S U P E R V I SOR Y A L A R M A C K F I R E A L A R M T R O U B L EA C K S Y S T E M TR OU B LE AL A R M S I L E N C E A L A R M SI L E N C ED S Y S T E M R E S E T A C PO W E R or or 4009 IDNet NAC Extender IDNet Fiber Optic Transmitter 4009 IDNet NAC Extender Connection Reference Drawing Introduction ADA Compliance. Complying with the notification requirements of ADA (Americans with Disabilities Act) may require more notification appliance power than is available within the fire alarm control panel. When additional power is required, a Simplex 4009 IDNet NAC Extender can provide up to 8 A of NAC power with up to eight, supervised reverse polarity NACs. Location Flexibility. The 4009 IDNet NAC Extender can be mounted close to a compatible dedicated host panel or can be located remotely for convenient power distribution. Multiple operation modes and multiple connection options further increase location flexibility. Additional Information. For additional operation detail and application information, refer to Installation Instructions 574-181 and field wiring diagram 842-068. * ULC listed model is 4009-9202CA. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:214 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of SimplexGrinnell LP, Westminster. ** 4100U requires revision 11 software or higher for compatibility. 4010 requires revision 2 software or higher for compatibility. LifeAlarm Fire Alarm Controls UL, ULC, CSFM Listed; FM Approved;4009 IDNet NAC Extender for Control from 4010, 4010ES, MEA (NYC) Acceptance* 4100ES/4100U IDNet Communications, or Conventional NACs S4009-0002-11 1/2013 Vail Fire & Emergency Services 08/25/17 Application and Operation Information IDNet Addressable Communications Compatible. Up to ten (10), 4009 IDNet NAC Extenders can be controlled per 4010ES/4100ES/4100U IDNet communications channel; up to five (5) can be controlled on the 4010 IDNet communications channel. Each output NAC can be individually controlled for general alarm or selective area notification requiring only one point address per Extender. Individual Extender NACs can also be manually controlled from the host panel. IDNet controlled extenders will inform the host panel of troubles via IDNet communications. 4010ES/4100ES/4100U control panels control using multi-point rules, refer to data sheet S4090-0011 for details. Optional IDNet Repeaters. IDNet communications can be repeated with the optional IDNet Repeater Module or with the optional Fiber Optic Receiver Module. Up to 100 of the IDNet channel points can be repeated once (refer to pages 3 and 5 for details). Repeated IDNet communications also support the “device level” earth fault location utility of the host panel. Hardwire Control Applications. For applications where an existing (or new) conventional NAC needs additional power, the 4009 IDNet NAC Extender can be controlled directly from the NAC. Either one or two NACs, from either the same, or from different host fire alarm control panels, can be connected to control the 4009 IDNet NAC Extender output NACs. Multiple control selections provide flexible operation. (Refer to page 4 for more detail.) Alarms from the host panel will activate the four, 4009 IDNet NAC Extender NACs (or optionally, eight NACs) to extend the alarm. The 4009 IDNet Extender monitors itself and each of its output NACs for trouble conditions, including earth faults. Extenders wired to conventional NACs will indicate a trouble by opening the path to the NAC’s end-of-line resistor, but retaining the ability to respond to alarms. Individual troubles are also annunciated by LEDs located on the 4009 IDNet NAC Extender main circuit board. (Refer to page 7 for more diagnostic information.) Standard Models Model Description 4009-9201 120 VAC input 4009 IDNet NAC Extender with 4, Class B NACs and 8 A power supply 4009-9202CA* 4009-9301 240 VAC input * ULC listed model Optional Modules (for on-site installation) Model Description Comments 4009-9807 Additional four point NAC module, rated 1.5 A Special Application appliances; 1 A for Regulated 24 DC appliance power, Class B One maximum 4009-9808 Dual Class A adapter (for two NAC outputs) Select as required (4 maximum) 4009-9809 IDNet Repeater, output is Class A or Class B Select either an IDNet Repeater or a Fiber Optic Receiver as required; one transmitter can connect to one receiver 4009-9810 Fiber Optic Receiver Class B 4009-9811 Class A (IDNet), Class X (fiber) 4009-9805 Red Appliqué for door Select if required 2975-9801 Semi-Flush Trim Kit Beige trim 1-7/16” wide (78 mm), use if required for semi-flush installations 2975-9802 Red trim Battery Selection (select battery size per system requirements) Model Description Comments 2081-9272 6.2 Ah Battery, 12 VDC Two batteries are required, 24 VDC operation 2081-9274 10 Ah Battery, 12 VDC 2081-9288 12.7 Ah Battery, 12 VDC 2081-9275 18 Ah Battery, 12 VDC Requires external battery cabinet, two batteries are required, 24 VDC operation External Accessories (select per system requirements) Model Description Comments 4090-9105 IDNet Fiber Optic Transmitter Class B operation Mounts in six-gang electrical box, refer to page 4 for mounting details 4090-9107 Class X operation 4009-9801 External battery cabinet for up to 18 Ah batteries, beige 16-1/4” W x 13-1/2” H x 5-3/4” D (413 mm x 343 mm x 146 mm) 4081 Series End-of-Line Resistor Harnesses; see data sheet S4081-0003 for details 2 S4009-0002-11 1/2013 Product Selection Vail Fire & Emergency Services 08/25/17 IDNet devices and additional 4009 IDNet NAC Extender(s) ALARM FIRE PULL DOWN SIMPLEXTIMERE CORDERCO. 4090-9101 MONITORZAM,CL ASSB IN S TA L. IN ST R.57 4- 1 83 DATECODE: 1 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 + 24V 0 V +I DNET - IDNET ZO NE PWR + ZO NE PWR -IDC + IDC - ALARM FIRE PULL DOWN SIMPLEXTIMERECORDERCO. 4090- 9101 MONITORZAM,CLASSB IN STA L . INST R .57 4- 1 83 DATECODE: 1 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 + 24V 0V +I DNET - IDNET ZO NE PWR + ZO NE PWR -I DC + I DC - PO W ER BEFO RE SERVI CI NG CAUTI ON DI SCO NNECT 4009 IDNet NAC EXTENDER T M F I R E 4009 IDNet NAC Extender with optional internal IDNet Repeater Repeated IDNet Channel: up to 100 devices maximum on repeater output, 250 devices total on IDNet Channel Output NACs, four standard, eight with expansion option Typical IDNet compatible devices (Refer to individual devices for actual wiring requirements, some wiring is not shown.) 4100ES (shown) or 4010ES/4100U/4010 Fire Alarm Control Panel IDNet addressable communications channel, shown Class B (Style 4) PO W E R BE FO RE SERVI CI NG CAUTIO N DI SCO NNECT 4009 IDNet NAC EXTENDER T M Conventional NAC operation (horns) SmartSync operation (horns and strobes) Conventional NAC operation (strobes) F I R E Select conventional or SmartSync operation per NAC NOTE: Up to ten (10) 4009 IDNet NAC Extenders may be connected per 4010ES, 4100ES or 4100U IDNet channel, up to five (5) on the 4010 IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). FI RE ALARM CO NTRO L D I S CO NN E C T P O W E R B E F O RE S E RV I C I NG CAUTI O N * * SYSTEM I S NO RM AL * * 12: 02: 15pm M on 9- Feb- 98 S U P V A C K S Y S T E M S U P E R V I SOR Y A L A R M A C K F I R E A L A R M T R O U B L E A C K S Y S T E M TR OU B LE ALA R M S I L E N C E A L A R M S I L E N C ED S Y S T E M R E S E T A C PO W E R 4010, 4010ES, 4100ES, or 4100U Fire Alarm Control Panel 4090-9105, Class B (Style 4) Output Fiber Optic Transmitter Two fiber cables, 3000 ft (914 m) maximum distance Four fiber cables, 3000 ft (914 m) maximum distance 4090-9107, Class A (Style 7) Output Fiber Optic Transmitter 24 VDC power for fiber optic transmitters 4009 IDNet NAC Extenders with optional internal IDNet Fiber Receivers IDNet addressable communications channel Class B (Style 4) or Class A (Style 6), Class B shown Repeated IDNet Channel: up to 100 devices maximum on repeater output, 250 devices total on IDNet Channel ALARM FIRE PULL DOWN SIMPLE XTIMEREC ORD ERCO. 40 90- 9101 MONITORZAM,CLA SSB INS TAL . INSTR.574 -18 3 DA TECODE: 1 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 + 2 4V 0V +I DNE T - I DNET ZO NE PW R + ZO NE PW R -I DC + I DC - PO W ER BEFO RE SERVI CI NG CAUTION DI SCO NNECT 4009 IDNet NAC EXTENDER TM Output NACs ALARM FIRE PULL DOWN SIMPLE XTIMEREC ORD ERCO. 40 90- 9101 MONITORZAM,CLA SSB INS TAL . INSTR.574 -18 3 DA TECODE: 1 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 + 2 4V 0V +I DNE T - I DNET ZO NE PW R + ZO NE PW R -I DC + I DC - PO W ER BEFO RE SERVI CI NG CAUTION DI SCO NNECT 4009 IDNet NAC EXTENDER TM Output NACs NOTE: Up to ten (10) 4009 IDNet NAC Extenders may be connected per 4010ES, 4100ES or 4100U IDNet channel, up to five (5) on the 4010 IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). Fiber optic transmitters connect to only one receiver in a 4009 IDNet NAC Extender. 3 S4009-0002-11 1/2013 Typical IDNet Connection Example Typical Fiber Optic System Connections Vail Fire & Emergency Services 08/25/17 Hardwire Control Connection Information NAC Input Selections. The 4009 IDNet NAC Extender can be selected to:  Track input NAC operation or to provide a locally generated code, selectable per NAC input  If selected for local coding, NAC outputs can be either Temporal Coded or 60 Beats/min March Time Coded, one code selection per extender (input NACs must be on continuous with Alarm)  Additionally, NAC outputs can be selected to provide the Simplex strobe synchronization signal. This signal will synchronize the flashes of synchronized strobes but will be ignored by free-run strobes and audible devices. (Strobes are for operation by noncoded NACs.) NAC input to NAC output control can be selected for standard and optional NACs per the following table: Conventional NAC Output Operation Options Input A B C NAC 1 NACs 1 & 2, 5 & 6 NACs 1-4 NACs 1-8 NAC 2 NACs 3 & 4, 7 & 8 NACs 5-8 None SmartSync NAC Output Operation Input NAC Control Function NAC 1 Strobe Control All NAC outputs (1-8) NAC 2 Horn Control SmartSync Notification Appliance Control The TrueAlert Notification Appliance product line includes addressable and non-addressable operation. Non-addressable models are available with 2-wire SmartSync operation or conventional 4-wire operation. The following details apply to use with the 4009 IDNet NAC Extender:  TrueAlert non-addressable models with SmartSync operation allow audible notification to be separately controlled over the same wire pair that controls visible notification  4009 IDNet NAC Extenders can be selected to provide SmartSync operation whether controlled by IDNet communications or conventional NACs  IDNet control allows output NACs to be individually selected for conventional or SmartSync operation  With NAC input control, all output NACs are selected for either conventional or SmartSync operation  Refer to data sheet S4009-0003 for TrueAlert Addressable operation details, contact your local Simplex product supplier for further information on specific TrueAlert notification appliances P O W E R B E F O R E S E R VI C I N G CAUTI O N DI SC O N NE C T 4009 IDNet NAC EXTENDER TM Up to eight (8) output NACs total; hardwire control can be selected to map NAC inputs to different combinations of NAC outputs depending on system requirements Fire Alarm Control Panel with Conventional NACs 4009 IDNet NAC Extender NAC 1 input (see Note 1) NAC 2 input (optional, see Note 1) Conventional NACs Output NACs SmartSync operation Notes: 1. For separate audible and visible output NAC control, or SmartSync NAC output operation, two (2) input NACs are required. NAC 1 is "on-until-reset" and NAC 2 is "on-until-silenced." 2. To synchronize strobe flash outputs for up to four (4) 4009 IDNet NAC Extenders, use the synchronized strobe output from a Synchronized Flash Module (4905-9914 for Class B operation, 4905-9922 for Class A operation) or, if available, from a NAC selected to provide synchronized strobe flash output. NOTE: DO NOT USE a NAC selected for SmartSync operation for this function. With hardwire control, NAC outputs are all conventional or all SmartSync operation To additional 4009 IDNet NAC Extenders (up to four (4), 4009 IDNet NAC Extenders per NAC); see Note 2 Refer to Installation Instructions 574-181 for additional information and application guidance Class A operation, either mode, requires 4009-9808 Dual Class A Adapter 4 S4009-0002-11 1/2013 Hardwire Control NAC Connection One-Line Reference Diagram Vail Fire & Emergency Services 08/25/17 Input Ratings 120 VAC Input (4009-9201) 3A @ 102-132 VAC, 60 Hz 240 VAC Input (4009-9301) 1.5A @ 204-264 VAC, 50/60 Hz Hardwire Control from External NACs, Input Requirements Conventional reverse polarity operation 5 mA maximum; 16 to 33 VDC Output Ratings Total Rating 8 A, Special Application appliances 6 A, Regulated 24 DC appliance power Standard NACs 2 A each, Special Application or Regulated 24 DC appliance power Optional NACs (requires 4009-9807) 1.5 A each, Special Application appliances 1 A each, Regulated 24 DC appliance power Special Application Appliances Simplex 4901, 4903, 4904, and 4906 Series non-addressable horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative for compatible appliances) Regulated 24 DC Appliances Power for other UL listed appliances; use associated external synchronization modules where required Strobe Operation Up to 33 strobes per NAC can be synchronized; output NACs configured for Simplex synchronized strobe operation are synchronized to each other Auxiliary Output 500 mA @ 24 VDC nominal Optional Modules Ratings IDNet Repeater Module (4009-9809) Input Power 70 mA @ 24 VDC, system supplied IDNet Input, One Address Maximum distance from IDNet source is 2500 ft (762 m) IDNet Output Specifications Repeated IDNet output for up to 100 devices (total IDNet devices not to exceed 250 per channel) Maximum distance to farthest device is 2500 ft (762 m) Total distance including “T-taps” is 10,000 ft (3048 m) Class A loop maximum distance is 2500 ft (762 m), no “T” taps Fiber Optic Receiver Modules Input Current 4009-9810, Class B, 65 mA @ 24 VDC, system supplied 4009-9811, Class X, 80 mA @ 24 VDC, system supplied IDNet Output Specifications Same as those for Repeater Module (see above) Fiber Optic Transmission Distance 3000 ft (914 m) maximum General (LED status indicators are listed on page 7, dimensions and mounting details are on page 6) Operating Temperature 32° to 120° F (0° to 49° C) Operating Humidity Range 10% to 90% RH from 32° F to 104° F (0° C to 40° C) Wiring Connections* Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Input Voltage 18.9-32 VDC from compatible listed fire alarm supply Input Current 4090-9105, Class B, 30 mA @ 24 VDC 4090-9107, Class X, 35 mA @ 24 VDC Fiber Optic Connections and cable requirements Multimode, graded index, 50/125µm, 62.5/125 µm, 100/40 µm, or 200 µm Type ST connectors 4090-9105, Class B operation, two fiber cables required 4090-9107, Class X operation, four fiber cables required Module Size (with mounting bracket) 6-13/16” W x 3-3/4” H x 1-1/8” D (173 mm x 95 mm x 29 mm) On-board Status Indicators Green LED flashing = transmit Red LED flashing = receive Separate red LED on 4090-9107 = Class X receive Communications Simplex IDNet Fiber Optic Transmission Distance 3000 ft (914 m) maximum Wiring Connections* Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Operating Humidity 10% to 90% RH from 32° to 104° F (0° to 40° C) Operating Temperature 32° F to 120° F (0° to 49° C) * Metric wire equivalents: 18 AWG = 0.82 mm2; 12 AWG = 3.31 mm2 5 S4009-0002-11 1/2013 4009 IDNet NAC Extender Specifications Fiber Optic Transmitter Specifications Vail Fire & Emergency Services 08/25/17 Door, 5/8" (16 mm) thick Cabinet depth 4-1/4" (108 mm) 16-1/4" (413 mm) 13-1/2" (343 mm) Wall surface reference for semi-flush mount Non-power limited wiring area (AC input) 12" (305 mm) Battery location, no conduit entry or wiring in this area (12.7 Ah battery outline shown) IDNet repeater or Fiber optic receiver Optional Class A adapter modules 4009-9807 Additional Four point module (shown with Class A adapters) 10-29/32" (277 mm) Knockouts for screw or nail mounting holes System Module Semi-flush trim option 1-3/16" wide (30 mm), 3/8" (9.5 mm) thick Exposed cabinet dimension for semi-flush mount 1" (25.4 mm), 1-3/8" (35 mm) with semi-flush trim NOTE: Recommended conduit entrance varies with module selection. Refer to general installation instructions 574-181, specific module installation instructions, and to field wiring diagrams 842-068 before locating conduit entrance. POWER BEFORE SERVICING CAUTION DISCONNECT 4009 IDNet NAC EXTENDER TM Optional red appliqué (4009-9805 ) 6 S4009-0002-11 1/2013 4009 IDNet NAC Extender Mounting and Module Placement Information 4009 IDNet NAC Extender Cabinet with Door Detail Vail Fire & Emergency Services 08/25/17 Service Diagnostic Features Power-up Self-Diagnostics. Upon power-up, the 4009 IDNet NAC Extender tests each module and performs earth fault diagnostics. Trouble conditions are communicated to the host control panel and are also displayed on diagnostic status LEDs in the 4009 IDNet NAC Extender. When connected via IDNet communications, detailed status information is available at the host. When controlled with conventional NAC inputs, common troubles are signaled by providing a polarized open circuit that disconnects the NAC wiring from its end-of-line resistor but still allows a reversed polarity alarm to be received. Door Mounted Reference Label. The 4009 IDNet NAC Extender has a detailed programming and diagnostic label inside the front door that provides a quick reference for both installation and checkout. LED Status Indicators are provided for the following:  Each NAC (standard and optional) has a dedicated yellow LED that: – During supervision provides a slow flash to indicate a short circuit condition and a fast flash to indicate an open circuit – During an alarm, the LED follows the NAC output (on steady or flashing with coded output)  Four, general status yellow LEDs provide nine separate indications listed in priority of urgency. As a trouble is eliminated, any remaining trouble(s) will then be indicated until the 4009 IDNet NAC Extender is returned to normal operation.  AC power status is indicated by a green LED that is on when AC is normal. During low AC (brownout) conditions or with no AC, the LED is off. Additional power and battery status is indicated by the general status LEDs. 7 S4009-0002-11 1/2013 Surface mount box: Simplex model 2975-9217 (ordered separately) Flush mount masonry box: use 6-gang box, RACO # 960, 2-1/2" deep (64 mm), or RACO # 965, 3-1/2" (89 mm) deep, or equal (supplied by others) Six-gang blank cover plate Mulberry Metal Products 97156 or equal (by others) Flush mount ganged boxes: use 6-gang box, 1-1/2" (38 mm) minimum depth; six, RACO # 400 or equal, (supplied by others) IDNet fiber optic transmitter: 4090-9107, Shown, Class A (Style 7) output 4090-9105, Not shown, Class B (Style 4) output INSTALLATION NOTE: Fiber optic cable bend radius should be 2" (51 mm) minimum, or per Manufacturer's specification. 4090-9105/9107 IDNet Fiber Optic Transmitter Mounting Information Vail Fire & Emergency Services 08/25/17 Step 1. Calculate Basic Extender Battery Requirements (minus NAC loads) Panel, NAC Options, and Auxiliary Power (underlined model numbers are optional modules) Model Descript ion Supervisory Current Actual Supervisory Alarm Current Actual Alarm 4009-9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA 4009-9301 240 VAC input 4009-9807 Additional Four Point NAC 40 mA +_______ 40 mA +_______ 4009-9808 Dual Class A Adapter (no additional current) – – – – Auxiliary Power Output (500 mA maximum) +_______(500 mA maximum) + [A1] _______ Basic Panel Supervisory Current = [S1] _____ Basic Panel Alarm Current = [A2] ______ Step 2. Calculate IDNet Output Module and Device Current (if used) 4009-9809 IDNet Repeater Select one per Extender 70 mA +_______ 70 mA +_______4009-9810* Fiber Optic Receiver, Class B 65 mA 65 mA 4009-9811* Fiber Optic Receiver, Class X 80 mA 80 mA IDNet Devices (connected to Repeater or Receiver above), 0.7 mA each, maximum of 100 Total devices x 0.7 mA each +_______Total devices x 0.7 mA each +_______ * Note: IDNet Fiber Optic Transmitter current is supplied from the host fire alarm control panel IDNet Module Supervisory Current [S2] = ____ = [A3] ______IDNet Module Alarm Current Step 2. Calculate Available NAC Current Maximum Available Current = 8 A* Subtract Auxiliary Power Output - [A1] ______ Subtract IDNet Module Current - [A3] ______ * 8 A for Special Application Appliances; 6 A for Regulated 24 DC Appliances Available NAC Current = [A4] ______ Step 3. Calculate Actual NAC Loading (Limited to Available NAC Current per Step 2.) NAC Type NAC Circuit #NAC Alarm Current Standard Panel NACS, 2 A maximum per NAC Circuit 1 +_______ Circuit 2 +_______ Circuit 3 +_______ Circuit 4 +_______ Optional Four Point NAC Module, 1.5 A maximum Special Application rating, 1 A maximum Regulated 24 DC rating, per NAC Circuit 5 +_______ Circuit 6 +_______ Circuit 7 +_______ Circuit 8 +_______ Total Actual NAC Load Alarm Current = [A5] _______ Step 4. Calculate Total Supervisory Current Total Supervisory Current = Basic Panel Current [S1] + IDNet Module Current [S2] = ________ Step 5. Calculate Total Alarm Current Total Alarm Current = Basic Panel Current [A2] + IDNet Module Current [A3] + Actual NAC Current [A5] = ________ TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Tyco Fire Protection Products · Westminster, MA · 01441-0001 · USA S4009-0002-11 1/2013 www.simplexgrinnell.com © 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. 4009 IDNet NAC Extender Current Calculation Chart Vail Fire & Emergency Services 08/25/17