HomeMy WebLinkAboutA14-0011 Calcs NAC Extender.pdfJobsite Information:Eye Pieces of Vail--Vail Village The calculations below show the power load on what will be a newly installed NAC extender used to power the notification appliances in the newly renovated office space. Entries only to be made in the Yellow cell locations Regulated Load in Standby Number of Current Total Current Device Type Devices (Amps)(Amps) Main PC Board 1 X 0.065 =0.065 Power Supervision Relays X 0.025 =0 Auxiliary Current Draw X =0 from TB4 Terminals 9 & 10 STANDBY LOAD =0.065 Regulated Load in ALARM Number of Current Total Current Device Type Devices (Amps)(Amps) Main PC Board without AC 1 X 0.145 =0.145 Power Supervision Relays X 0.025 =0 Auxiliary Current Draw X =0 from TB4 Terminals 9 & 10 NAC / Output # 1 X =0 SYS-SR 15 2 X 0.0071 =0.0142 SYS-SR 30 0 X 0.0076 =0 SYS-P4R 30 2 X 0.0112 =0.0224 SYS-P4R 75 0 X 0.0168 =0 NAC / Output # 2 X =0 NAC / Output # 3 X =0 NAC / Output # 4 X =0 ALARM LOAD =0.182 Battery Amp Hour Calculation Standby Load Required Standby Time Current (Amps)(Typically 24 or 60 Hours ) 0.065 X 24 =1.56 AH Alarm Load Required Alarm Time Current (Amps)(Typically 5 or 10 Minutes ) 0.1816 X 10 =0.03 AH Sub Total Standby / Alarm Amp Hours 1.59 AH Multiply by the Derating Factor X 1.2 * Total Ampere Hours Required =2 AH * Derating Factor required to compensate for the non-linear discharge characteristic of a battery. FCPS-24FS6 / 8 Battery Calculation