HomeMy WebLinkAboutA14-0011 Scope of Work Letter.pdf e L. •sc Superior Alarm � & Electronics Security, Fire, CCTV, Access Control, Custom AudioNideo, and Automation April 4th, 2014 Vail Fire and Emergency Services Mike Vaughan 42 W. Meadow Dr. Vail, CO 81657 Re: Scope of Work Letter—Eye Pieces of Vail 122 E. Meadow Dr. Suite D-1 Vail, Colorado 80657 Dear Mike: We have been contracted to reconfigure the fire alarm devices at 122 E.Meadow Drive due to a renovation of office space for Eye Pieces of Vail. The building is not sprinklered and currently has an addressable alarm panel in place(Silent Knight 5820XL). We will be adding a NAC extender to the existing system to support the notification appliances to be installed. There are 4 existing smoke detectors in the space which will be repositioned to meet the configuration of the new space. As no additional power draw will be placed on the FACP,battery calculations attached are limited to the NAC extender. Device listing for added devices are as follows: 1 SD-505AHS 135 degree fixed heat 1 Firelite 24FS6 NAC extender 1 SD500-ANM Addressable Notification Module 3 SD500-MIM Mini Input Module—Pull Station 2 SYS-SR Strobes 2 SYS-P4R Horn Strobes These changes will be performed in compliance with current fire codes and all NFPA fire codes. Brad Wo[niak President ' '---6 Z_______— . -. Superior Alarm Electronics George Sharer, N10ET III—Fire Alarm Systems Cert.#98481 Fire Engineering Services ` ..,.. : /4\\I +err\ . Poet Office Dox 4910 7 Edwards,Golurado 01532 * Phone(070)ea6-67813 * Fax(070)826-&790 www.superioralarmco.com s admin@superioralamico.com