HomeMy WebLinkAboutFA.03.pdfIFC-320 FIRE ALARM CONTROL PANEL - FAP5 Calculation Column 1 Primary, Non-Fire Alarm Current (amps) Calculation Column 2 Primary, Fire Alarm Current (amps) DEVICE QTY. AMPS. TOTAL QTY. AMPS. TOTAL IFC-320 1 0.2500 0.2500 1 0.2300 0.2300 KDM-R2 DISPLAY 1 0.1000 0.1000 1 0.1000 0.1000 ACPS-2406 0 0.1287 0.0000 0 0.0000 0.0000 BACNet Gateway 0 0.3600 0.0000 0 0.3600 0.0000 LCD-80,LCD-80TM 0 0.1000 0.0000 0 0.1000 0.0000 JNCA 0 0.4000 0.0000 0 0.5000 0.0000 LDM-32 0 0.0400 0.0000 0 0.0000 UZC-256 0 0.0350 0.0000 0 0.0850 0.0000 AMG-1,AMG-E 0 0.0600 0.0000 0 0.0600 0.0000 FFT-7,FFT-7S 0 0.0600 0.0000 0 0.1200 0.0000 AA-30 0 0 AA-100,AA-120 0 0 M302MJ,M502MJ 0 0.0094 0.0000 0 0.0900 0.0000 XPIQ 0 0.0000 0 0.0000 RPT-W,RPT-WF,RPT-F,NCM-W 1 0.0170 0.0170 1 0.0170 0.0170 UDACT Communicator 0 0.0400 0.0000 0 0.1000 0.0000 Notification Appliance 1 1 2.9410 2.9410 SOUNDER BASES 13 0.0010 0.0130 13 0.0150 0.1950 Power Supervision Relays 1 0.0200 0.0200 1 0.0200 0.0200 DH500,DH502 Duct Detectors 0 0.0000 0 0.0000 CHG-120 Battery Charger 0 0 SLC #1 Totals 1 0.2000 0.2000 1 0.2000 0.2000 TOTAL 0.60 3.70 TOTAL CURRENT - STANDBY OPERATION 0.600 HOURS REQUIRED FOR OPERATION 24 BATTERY REQUIREMENTS FOR 4 HRS 14.40 TOTAL CURRENT - ALARM OPERATION 3.703 HOURS REQUIRED FOR OPERATION (15min) 0.25 BATTERY REQUIREMENTS FOR 5 MIN 0.93 TOTAL BATTERY REQUIREMENTS 15.33 BATTERY REQUIRED WITH 20% FACTOR 18.39 BATTERY TO BE INSTALLED 18 AMP-HR Vail Fire & Emergency Services 06/04/14 Carolyn Godfrey