Loading...
HomeMy WebLinkAboutFA.04.pdfProject Name Solaris Date 9/1/2011 Circuit Number Remote Power Supply #6 / RPS6-1 Voltage Voltage Voltage Location Second Level Retail 201 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.225 380 0.50 0.225 380 0.545 0.225 380 0.273 Minimum Device Voltage 16 End of Line Voltage 19.90 End of Line Voltage 19.85 End of Line Voltage 20.13 Total Circuit Current 0.225 Wire Ohm's Percent Drop 2.47% Percent Drop 2.67% Percent Drop 1.34% Gauge Per 1000 Distance from source to 1st device 260 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.000 260 20.03 0.373 1.83% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.165 80 19.91 0.488 2.39% Device 3 0.060 40 19.90 0.503 2.47% Device Manufacturer Wheelock Device Manufacturer Wheelock END 19.90 0.503 2.47% END 19.90 0.503 2.47% Candela Candela END 19.90 0.503 2.47% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.90 0.503 2.47% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.90 0.503 2.47% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.90 0.503 2.47% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.90 0.503 2.47% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.90 0.503 2.47% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.90 0.503 2.47% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.90 0.503 2.47% END 19.90 0.503 2.47% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.90 0.503 2.47% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.90 0.503 2.47% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.90 0.503 2.47% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.90 0.503 2.47% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.90 0.503 2.47% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.90 0.503 2.47% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.225 380 End of Line Voltage 19.90 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.225 OUT SPARE CAPACITY = 85% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 9/1/2011 Circuit Number Remote Power Supply #6 / RPS6-2 Voltage Voltage Voltage Location Second Level Retail 202 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.349 335 0.68 0.349 335 0.746 0.349 335 0.373 Minimum Device Voltage 16 End of Line Voltage 19.72 End of Line Voltage 19.65 End of Line Voltage 20.03 Total Circuit Current 0.349 Wire Ohm's Percent Drop 3.33% Percent Drop 3.66% Percent Drop 1.83% Gauge Per 1000 Distance from source to 1st device 240 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.092 240 19.87 0.534 2.62% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.165 85 19.73 0.674 3.30% Device 3 0.092 10 19.72 0.680 3.33% Device Manufacturer Wheelock Device Manufacturer Wheelock END 19.72 0.680 3.33% END 19.72 0.680 3.33% Candela Candela END 19.72 0.680 3.33% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.72 0.680 3.33% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.72 0.680 3.33% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.72 0.680 3.33% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.72 0.680 3.33% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.72 0.680 3.33% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.72 0.680 3.33% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.72 0.680 3.33% END 19.72 0.680 3.33% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.72 0.680 3.33% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.72 0.680 3.33% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.72 0.680 3.33% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.72 0.680 3.33% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.72 0.680 3.33% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.72 0.680 3.33% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.349 335 End of Line Voltage 19.72 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.349 OUT SPARE CAPACITY = 77% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 9/1/2011 Circuit Number Remote Power Supply #6 / RPS6-3 Voltage Voltage Voltage Location Second Level Retail 203 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.385 280 0.49 0.385 280 0.688 0.385 280 0.344 Minimum Device Voltage 16 End of Line Voltage 19.91 End of Line Voltage 19.71 End of Line Voltage 20.06 Total Circuit Current 0.385 Wire Ohm's Percent Drop 2.41% Percent Drop 3.37% Percent Drop 1.69% Gauge Per 1000 Distance from source to 1st device 140 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.220 140 20.06 0.344 1.69% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.165 140 19.91 0.491 2.41% END 19.91 0.491 2.41% Device Manufacturer Wheelock Device Manufacturer Wheelock END 19.91 0.491 2.41% END 19.91 0.491 2.41% Candela Candela END 19.91 0.491 2.41% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.91 0.491 2.41% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.91 0.491 2.41% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.91 0.491 2.41% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.91 0.491 2.41% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.91 0.491 2.41% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.91 0.491 2.41% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.91 0.491 2.41% END 19.91 0.491 2.41% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.91 0.491 2.41% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.91 0.491 2.41% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.91 0.491 2.41% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.91 0.491 2.41% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.91 0.491 2.41% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.91 0.491 2.41% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.385 280 End of Line Voltage 19.91 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.385 OUT SPARE CAPACITY = 74% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 9/1/2011 Circuit Number Remote Power Supply #6 / RPS6-6 Voltage Voltage Voltage Location Second Level Retail 206 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.272 240 0.32 0.272 240 0.416 0.272 240 0.208 Minimum Device Voltage 16 End of Line Voltage 20.08 End of Line Voltage 19.98 End of Line Voltage 20.19 Total Circuit Current 0.272 Wire Ohm's Percent Drop 1.56% Percent Drop 2.04% Percent Drop 1.02% Gauge Per 1000 Distance from source to 1st device 100 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.060 100 20.23 0.174 0.85% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.060 70 20.13 0.268 1.31% Device 3 0.060 25 20.11 0.292 1.43% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.092 45 20.08 0.319 1.56% END 20.08 0.319 1.56% Candela Candela END 20.08 0.319 1.56% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 20.08 0.319 1.56% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 20.08 0.319 1.56% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 20.08 0.319 1.56% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 20.08 0.319 1.56% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 20.08 0.319 1.56% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 20.08 0.319 1.56% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 20.08 0.319 1.56% END 20.08 0.319 1.56% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 20.08 0.319 1.56% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 20.08 0.319 1.56% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 20.08 0.319 1.56% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 20.08 0.319 1.56% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 20.08 0.319 1.56% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 20.08 0.319 1.56% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.272 240 End of Line Voltage 20.08 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.272 OUT SPARE CAPACITY = 82% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 9/1/2011 Circuit Number Remote Power Supply #6 / RPS6-7 Voltage Voltage Voltage Location Second Level Kitchen Unit 207 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.885 245 0.97 0.885 245 1.383 0.885 245 0.692 Minimum Device Voltage 16 End of Line Voltage 19.43 End of Line Voltage 19.02 End of Line Voltage 19.71 Total Circuit Current 0.885 Wire Ohm's Percent Drop 4.73% Percent Drop 6.78% Percent Drop 3.39% Gauge Per 1000 Distance from source to 1st device 100 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.165 100 19.84 0.565 2.77% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.165 30 19.70 0.702 3.44% Device 3 0.165 30 19.59 0.809 3.96% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.060 25 19.53 0.871 4.27% Device 5 0.165 30 19.47 0.934 4.58% Candela Candela Device 6 0.165 30 19.43 0.966 4.73% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.43 0.966 4.73% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.43 0.966 4.73% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.43 0.966 4.73% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.43 0.966 4.73% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.43 0.966 4.73% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.43 0.966 4.73% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.43 0.966 4.73% END 19.43 0.966 4.73% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.43 0.966 4.73% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.43 0.966 4.73% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.43 0.966 4.73% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.43 0.966 4.73% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.43 0.966 4.73% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.43 0.966 4.73% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.885 245 End of Line Voltage 19.43 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.885 OUT SPARE CAPACITY = 41% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 9/1/2011 Circuit Number Remote Power Supply #6 / RPS6-8 Voltage Voltage Voltage Location Spare Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.000 0 0.00 0.000 0 0.000 0.000 0 0.000 Minimum Device Voltage 16 End of Line Voltage 20.40 End of Line Voltage 20.40 End of Line Voltage 20.40 Total Circuit Current 0.000 Wire Ohm's Percent Drop 0.00% Percent Drop 0.00% Percent Drop 0.00% Gauge Per 1000 Distance from source to 1st device 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0 20.40 0.000 0.00% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.40 0.000 0.00% END 20.40 0.000 0.00% Device Manufacturer Wheelock Device Manufacturer Wheelock END 20.40 0.000 0.00% END 20.40 0.000 0.00% Candela Candela END 20.40 0.000 0.00% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 20.40 0.000 0.00% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 20.40 0.000 0.00% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 20.40 0.000 0.00% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 20.40 0.000 0.00% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 20.40 0.000 0.00% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 20.40 0.000 0.00% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 20.40 0.000 0.00% END 20.40 0.000 0.00% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 20.40 0.000 0.00% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 20.40 0.000 0.00% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 20.40 0.000 0.00% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 20.40 0.000 0.00% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 20.40 0.000 0.00% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 20.40 0.000 0.00% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.000 0 End of Line Voltage 20.40 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.000 OUT SPARE CAPACITY = 100% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 5/14/2014 Circuit Number Remote Power Supply #6 / RPS6-4 Voltage Voltage Voltage Location Second Level Retail 204 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.737 435 1.29 0.737 435 2.045 0.737 435 1.023 Minimum Device Voltage 16 End of Line Voltage 19.11 End of Line Voltage 18.35 End of Line Voltage 19.38 Total Circuit Current 0.737 Wire Ohm's Percent Drop 6.34% Percent Drop 10.03% Percent Drop 5.01% Gauge Per 1000 Distance from source to 1st device 100 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.060 100 19.93 0.470 2.30% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.060 25 19.82 0.578 2.83% Device 3 0.165 65 19.57 0.834 4.09% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.092 65 19.38 1.022 5.01% Device 5 0.060 60 19.24 1.159 5.68% Candela Candela Device 6 0.060 25 19.19 1.207 5.92% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) Device 7 0.060 15 19.17 1.230 6.03% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 Device 8 0.060 30 19.14 1.265 6.20% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 Device 9 0.060 25 19.12 1.284 6.29% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 Device 10 0.060 25 19.11 1.293 6.34% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 Device 11 19.11 1.293 6.34% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.11 1.293 6.34% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.11 1.293 6.34% END 19.11 1.293 6.34% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.11 1.293 6.34% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.11 1.293 6.34% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.11 1.293 6.34% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.11 1.293 6.34% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.11 1.293 6.34% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.11 1.293 6.34% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.737 435 End of Line Voltage 19.11 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.737 OUT SPARE CAPACITY = 51% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 5/14/2014 Circuit Number Remote Power Supply #6 / RPS6-5 Voltage Voltage Voltage Location Second Level Retail 205 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.377 280 0.45 0.377 280 0.673 0.377 280 0.337 Minimum Device Voltage 16 End of Line Voltage 19.95 End of Line Voltage 19.73 End of Line Voltage 20.06 Total Circuit Current 0.377 Wire Ohm's Percent Drop 2.21% Percent Drop 3.30% Percent Drop 1.65% Gauge Per 1000 Distance from source to 1st device 130 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.165 130 20.09 0.313 1.53% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.060 45 20.03 0.374 1.83% Device 3 0.060 40 19.99 0.412 2.02% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.092 65 19.95 0.450 2.21% END 19.95 0.450 2.21% Candela Candela END 19.95 0.450 2.21% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.95 0.450 2.21% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.95 0.450 2.21% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.95 0.450 2.21% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.95 0.450 2.21% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.95 0.450 2.21% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.95 0.450 2.21% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.95 0.450 2.21% END 19.95 0.450 2.21% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.95 0.450 2.21% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.95 0.450 2.21% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.95 0.450 2.21% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.95 0.450 2.21% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.95 0.450 2.21% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.95 0.450 2.21% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.377 280 End of Line Voltage 19.95 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.377 OUT SPARE CAPACITY = 75% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method PS-8 BATTERY CAPACITY CALCULATION FOR RPS6 OPERATION ON BATTERY BACKUP POWER DEVICE TYPE QTY STAND-BY CURRENT QTY ALARM CURRENT EACH TOTAL EACH TOTAL RPS6-1 1 0.000 0.000 1 0.225 0.225 RPS6-2 1 0.000 0.000 1 0.349 0.349 RPS6-3 1 0.000 0.000 1 0.385 0.385 RPS6-4 1 0.000 0.000 1 0.737 0.737 RPS6-5 1 0.000 0.000 1 0.377 0.377 RPS6-6 1 0.000 0.000 1 0.272 0.272 RPS6-7 1 0.000 0.000 1 0.885 0.885 RPS6-8 1 0.000 0.000 1 0.000 0.000 MAIN PC BOARD 1 0.129 0.129 1 0.129 0.129 Number of Slave power Supplys 0 0.006 0.000 0 0.006 0.000 0 0.000 0.000 0 0.000 0.000 0 0.000 0.000 0 0.000 0.000 TOTAL CURRENT 0.129 3.359 TOTAL CURRENT - STANDBY OPERATION 0.129 HOURS REQUIRED FOR OPERATION 24.00 BATTERY STANDBY REQUIREMENTS 3.10 TOTAL CURRENT - ALARM OPERATION 3.359 HRS REQUIRED FOR OPERATION 0.250 (15 MIN) BATTERY ALARM REQUIREMENT 0.84 TOTAL BATTERY REQUIREMENTS 3.94 BATTERY REQUIRED WITH 20% FACTOR 4.72 7 AMP-HOUR BATTERIES INSTALLED AMPS AVAILABLE CURRENT 8 TOTAL CURRENT 3.359 SPARE CAPACITY 58.01% Vail Fire & Emergency Services 06/04/14 Carolyn Godfrey