HomeMy WebLinkAboutE17-0180 load calcs.pdf Panel -2- 0'.3q Gkca,►yi.oyr-CA LR�..e_
Service: 'P' (EXISTING) Mounting: Flush ZjA Bus:
120/240 Volt,1-PH,3 Wire Mains: MLO 100
Panel Type: AIC: 10K
Load Center Poles: 12 Phase Comments: (3#1 AL.&1#8G.)
Code Description Load Bkr P Circuit P Bkr Load Description Code
-
A DRYER 2250 30 2 1 A l2 1 15/15 1100 *UP BATH/UP BED RM X i
A 2250 / 3 B 4 1 15/15 1220 *BED RM/KIT. LIGHTS X
A RANGE 4000 50 2 5 A 6 1 15/15 1480 *LIVING RM REC/LIVING LTS X
A 4000 / 7- B 8 1 20/20 1640 *UP BEDRM/UP BEDRM X
A REFRIG. 1200 20 1 9_A W10 1 20/20 1080 *KITCHEN REC./KITCHEN REC. R
A WASHER 1200 20 1 11 B 12 1 15/20 1800 *FA/DISP.&DW X
Code Description Conn. DF NEC Demand Load Summary
L Lighting 0.00 125% 0.00 KVA Balance
R Recpt up to 10 kVA 1.08 100% 1.08 KVA Phase A 11.11 KVA 48%
Recpt over 10 kVA 0.00 50% 0.00 KVA Phase B 12.11 KVA 52%
M Motor 0.00 100% 0.00 KVA
Largest Motor 0.00 125% 0.00 KVA
E Equipment 0.00 100% 0.00 KVA Connected 23.22 KVA
A Appliances 14.90 65% 9.69 KVA Design 36.00 KVA
X Misc.Equipment/Mixed Loads 7.24 100% 7.24 KVA Demand 18.01 KVA
Connected Total 23.22 KVA Demand Total 18.01 KVA Spare 18.00 KVA
Connected Load 96.75 Amps Demand Load 75.02 Amps
*INDICATES TWIN C.B.s Spare Load 24.98 Amps NEC Demand 18.01 KVA
Service Design Load 100 Amps NEC Demand 75.02 Amps