Loading...
HomeMy WebLinkAboutBattery Calcs-Elk Meadows #2.xlsxProject Name: Device Description FACP FACP Annunciator FACP Annunciator Smoke Detectors Heat Detectors Carbon Monoxide Detectors 4 Zone Programmable Relay Card Exterior Horn/Strobe 8 Zone Hardwire Expansion Module Ademco Radio Frequency Transciever Infrared Motion Detector Recessed Infrared Motion Detector Cornermount Glass Break Sensor Adjustable Low Temperature Sensor Combustible Gas Detector Water Detector End Of Line Power Supervision Module Horns Addressable Modules Projected Batteries To Use: Projected Batteries Total Amp Storage: Elk Meadows #2 Part Number ADE-Vista 128BPE ADE-6160 ADE-6160RF ESL 541NCSXT SYS-BK5603 SYS-BKCO1224TR ADE-4204 SYS-P2RK ADE-4208U ADE-5883H ADE-995 BOS-ISC-BPR2-WP12 INT-FG-1625F ADE-TS300 MAC-GD2A GRI-2600 ESL-204-12/24 SYS-MHW ADE-4193SN 2 x 12V 7AH 14 AH Quantity 1 1 0 8 1 4 1 1 0 0 0 0 0 0 1 0 1 2 14 Current Draw Standby mA 250 45 45 0.7 0 20 15 0 27.3 30 15 10 12 25 45 10 0 0 1.5 Total System Draws: Converted to Amps: Current Draw in Alarm mA 330 150 150 30 30 40 160 218 27.3 30 15 10 22 50 70 10 14 12 1.5 24 hrs Standby: 15 min Alarm: Total Alarm Panel Amp Hours: Efficiency Factor 20%: Required Amp Hours: Total Device Current Draw Standby mA 250 45 0 5.6 0 80 15 0 0 0 0 0 0 0 45 0 0 0 21 461.6 0.4616 Total Device Current Draw in Alarm mA 330 150 0 240 30 160 160 218 0 0 0 0 0 0 70 0 14 24 21 1417 1.417 11.0784 0.35425 11.43265 2.28653 13.71918