HomeMy WebLinkAboutB17-0306_Vail Snowsports Museum - ComCheck Report 20170802_1501886100.pdfCOMcheck Software Version 4.0.6.1
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
75 S. Frontage Road
Vail, CO
Owner/Agent:
Susie Tjossem
Colorado Snowsports Museum and
Hall of Fame
231 S. Frontage Road East
Vail, CO 81657
Designer/Contractor:
Andrew Wilder
Wilder Engineering LLC
1170 Blue Sage Drive
Steamboat Springs, CO 80487
970-819-7848
Project Information
Energy Code:
Colorado Snowsports Museum
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Exhibit Space (Museum:General Exhibition)2681 1.05 2815
2-Muesum Store (Retail:Sales Area)724 1.59 1151
3-Office (Common Space Types:Office - Enclosed)288 1.11 320
4-Restrooms (Common Space Types:Restrooms)129 0.98 126
5-Storage (Common Space Types:Storage >=50 - <=1000 sq.ft.)253 0.63 159
6-Break Room (Common Space Types:Food Preparation)136 1.21 165
4736Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Exhibit Space ( Museum:General Exhibition 2681 sq.ft.)
LED 1: F2: Pendant LED Linear: LED Linear 33W:1 14 42 588
Track lighting 1: F1: LED Track: Wattage based on circuit breaker capacity (20 amps x 120
volts)
0 0 2400 Exempt
Exemption:Display Lighting in Galleries/Museums
Muesum Store ( Retail:Sales Area 724 sq.ft.)
LED 2: F3: Recessed LED Linear: LED Panel 33W:1 6 31 186
Track lighting 1: F1: LED Track: Wattage based on circuit breaker capacity (20 amps x 120
volts)
0 0 2400 2400
Office ( Common Space Types:Office - Enclosed 288 sq.ft.)
LED 3: F4: 2x2 Recessed: LED Panel 40W:1 4 39 156
Restrooms ( Common Space Types:Restrooms 129 sq.ft.)
LED 5: F6: Downlight: LED A Lamp 25W:1 2 19 38
LED 6: F7: Vanity: LED A Lamp 9W:1 2 9 18
Storage ( Common Space Types:Storage >=50 - <=1000 sq.ft. 253 sq.ft.)
LED 7: F8: LED Linear 33W:1 5 33 165
Break Room ( Common Space Types:Food Preparation 136 sq.ft.)
LED 3: F4: 2x2 Recessed: LED Panel 40W:1 2 39 78
Project Title:
Data filename:
Colorado Snowsports Museum
C:\_Wilder Engineering\_Projects\Rader Engineering\201773 - Vail Ski Museum\Calculations\Ski
Museum.cck
08/01/17Report date:
61 ofPage
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
LED 4: F5: Under Cabinet: LED Undercabinet Unit 24W:1 3 29 87
3716Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.0.6.1 and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Andrew Wilder - PE
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
Colorado Snowsports Museum
C:\_Wilder Engineering\_Projects\Rader Engineering\201773 - Vail Ski Museum\Calculations\Ski
Museum.cck
08/01/17Report date:
62 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.6.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Colorado Snowsports Museum
C:\_Wilder Engineering\_Projects\Rader Engineering\201773 - Vail Ski Museum\Calculations\Ski
Museum.cck
08/01/17Report date:
63 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Colorado Snowsports Museum
C:\_Wilder Engineering\_Projects\Rader Engineering\201773 - Vail Ski Museum\Calculations\Ski
Museum.cck
08/01/17Report date:
64 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Colorado Snowsports Museum
C:\_Wilder Engineering\_Projects\Rader Engineering\201773 - Vail Ski Museum\Calculations\Ski
Museum.cck
08/01/17Report date:
65 ofPage
Project Title:
Data filename:
Colorado Snowsports Museum
C:\_Wilder Engineering\_Projects\Rader Engineering\201773 - Vail Ski Museum\Calculations\Ski
Museum.cck
08/01/17Report date:
66 ofPage