Loading...
HomeMy WebLinkAboutB17-0307_A0.1_1506116640.pdf2. MAIN LEVEL 0" 3. UPPER LEVEL 10' - 1 3/4" 1. B GARAGE LVL -11' - 1 3/4" PLATE HT. 18' - 2 3/4" INSTALL 90 DEGREE FITTING AND 4 FT. TAIL OF 4 IN. DRAIN TILE EMBEDDED IN FREE DRAINING GRAVEL. NOTE: ALL CONTROL JOINTS, ISOLOATION JOINTS, CONSTRUCTION JOINTS AND ANY OTHER JOINTS IN THE CONCRETED SLABS, OR BETWEEN SLABS AND FOUNDATION WALLS SHALL BE SEALED WITH A CAULK OR SEALEANT. GAPS AND JOINTS SHALL BE CLEARED OF LOOSE MATERIAL AND FILLED WITH POLYUERETHANE CAULK OR OTHER ELASTOMERIC SEALANT APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ROUTE 4" ABS, PVC, OR EQUIVILENT GAS-TIGHT, SUBSLAB PASSIVE SLAB DEPRESSURIZATION VENT FROM BASEMENT TO ROOF THROUGH INTERIOR WALLS (SEE RADON PLANS). ALLOW FOR THE FUTURE INSTALLATION OF AN IN-LINE FAN. PROVIDE A 110 VOLT RECEPTACLE AT THE FAN LOCATION . PLACE LABELS ON VENT AT EACH LEVEL: "RADON MITIGATION SYSTEM". EXTEND VENT PIPE 12" ABOVE ROOF. FAN INSTALL RADON SENSOR AT LOWEST LEVEL 3 A0.1 Radon System Radon system is to comply with Appendix F of the 2015 IRC A sub-slab depressurization system (passive) is to be designed. The vent pipe shall be a minimum dia. of 3" and extend from the permeable layer under the lowest slab with a ' T ' fitting, through the conditioned space of the homes, and out the roof. The exhaust shall be located as a penetration through the roof and located on the non-street side. This exhaust vent shall be 2'-0" above the roof surface and 10'-0" away from any openings or the adjacent building/unit. An electrical box shall be installed in an accessible location along radon sytem vertical piping so possible future vent pipe in-line fans can be added. See sections on this sheet for vertical location of Radon system. See key floor plan on this sheet for location of piping routing for Radon System. Additional notes: N1102.2.1 (R402.2.1) Ceilings with attic spaces. When Secton N1102.1.1 R-38 shall be deemed to satisfy the requirement for R-49 wherever the full height of uncompressed R-38 insulation extends over the wall top plate at the eaves. N1102.2.2 (R402.2.2) Ceilings without attic spaces. Where Secton N1102.1.1 would require insulation levels above R-30 and the design of the roof/ceiling assembly does not allow sufficient space for the required insulation, the minimum required insulation for such roof/ceiling assemblies shall be R-30. This reduction of insulation from the requirements of Secton N1102.1.1 shall be limited to 500 square feet (46 m2) or 20 percent of the total insulated ceiling area, whichever is less. N1102.2.3 (R402.2.3) Eave baffle. For air permeable insulations in vented attics, a baffle shall be installed adjacent to soffit and eave vents. Baffles shall maintain an opening equal or greater than the size of the vent. The baffle shall extend over the top of the attic insulation. The baffle shall be permitted to be any solid material. N1102.2.4 (R402.2.4) Access hatches and doors. Access doors from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces) shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding surfaces. Access shall be provided to all equipment that prevents damaging or compressing the insulation. A wood framed or equivalent baffle or retainer is required to be provided when loose fill insulation is installed, the purpose of which is to prevent the loose fill insulation from spilling into the living space when the attic access is opened, and to provide a permanent means of maintaining the installed R-value of the loose fill insulation. N1102.2.5 (R402.2.5) Mass walls. Mass walls for the purposes of this chapter shall be considered above-grade walls of concrete block, concrete, insulated concrete form (ICF), masonry cavity, brick (other than brick veneer), earth (adobe, compressed earth block, rammed earth) and solid timber/logs. N1102.2.7 (R402.2.7) Floors. Floor insulation shall be installed to maintain permanent contact with the underside of the subfloor decking. N1102.2.8 (R402.2.8) Basement walls. Walls associated with conditioned basements shall be insulated from the top of the basement wall down to 10 feet (3048 mm) below grade or to the basement floor, whichever is less. Walls associated with unconditioned basements shall meet this requirement unless the floor overhead is insulated in accordance with Sections N1102.1.1 and N1102.2.7. N1102.2.9 (R402.2.9) Slab-on-grade floors. Slab-on-grade floors with a floor surface less than 12 inches (305 mm) below grade shall be insulated in accordance with Table N1102.1.1. The insulation shall extend downward from the top of the slab on the outside or inside of the foundation wall. Insulation located below grade shall be extended the distance provided in Table N1102.1.1 by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. Insulation extending away from the building shall be protected by pavement or by a minimum of 10 inches (254 mm) of soil. The top edge of the insulation installed between the exterior wall and the edge of the interior slab shall be permitted to be cut at a 45-degree (0.79 rad) angle away from the exterior wall. N1102.2.10 (R402.2.10) Crawl space walls. As an alternative to insulating floors over crawl spaces, crawl space walls shall be permitted to be insulated when the crawl space is not vented to the outside. Crawl space wall insulation shall be permanently fastened to the wall and extend downward from the floor to the finished grade level and then vertically and/or horizontally for at least an additional 24 inches (610 mm). Exposed earth in unvented crawl space foundations shall be covered with a continuous Class I vapor retarder in accordance with this code. All joints of the vapor retarder shall overlap by 6 inches (153 mm) and be sealed or taped. The edges of the vapor retarder shall extend at least 6 inches (153 mm) up the stem wall and shall be attached to the stem wall. N1102.2.11 (R402.2.11) Masonry veneer. Insulation shall not be required on the horizontal portion of the foundation that supports a masonry veneer. A section below thru the home shows the locations of all insulation/thermal envelope. On these sections, is shown the location of vapor barrier/vapor retarder. Eagle County lies in climate zone 6B. This is a prescriptive method for insulation and code compliance to energy efficient systems #1 Insulation values: show the chart that has the climate zone 6B. Fenestration U-Factor=.32 with a resolution 3.11 C revising the U-factor to .30 in Eagle Co. and .30 in Town of Vail Skylight U-Factor=.55 Ceiling R-Value = R49 Wood Framed Wall R-Value 20+5 or 13+10 (20 in the wall cavity and 5 continuous) Town of Vail, Avon, and Eagle have not adopted the R-5 continuous insulation requirement. Floor R-Value = R30 (or insulation to fill the framing cavity, r-19 min) Basement Wall R-Value =15/19 (R15 on the exterior or interior continuous OR R19 in the wall cavity) The r-19 shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous on the interior OR exterior of the foundation wall Slab R-Value =R10 for 4 feet from the edge of the slab measured horizontally or vertically For heated slabs, R-5 insulation shall be added to the slab edge Crawlspace wall R-Value = 15/19, which means R15 on the interior or exterior of the home or R-13 cavity insulation on the interior of the basement wall plus R-5 continuous on the interior OR exterior of the foundation wall #2 Fenestration and SHGCs (SHGCs are not required in this climate zone of 6) Fenestration U-Factor=.32 with a resolution 3.11 C revising the U-factor to .30 #3 Area weighted U-factor Calculations If some windows do not meet the U-factor .30 then an average of window areas can be calculated. #4 Mechanical system design criteria. 1. Minimum winter design temp of -20 degrees F. (resolution to section R303.9) 2. Heat loss calculations are required for all dwelling units (resolution to section R303.9) (Heat calcs, zones and layouts are due with the mech. permit application) 3. Minimum efficiency of main heat source is to be 92% 4. A whole house mechanical ventilation system (R303.4) is to be designed where the air infiltration rate of a dwelling unit is 5 air changes per hour or less where tested with a blower door at a pressure of 0.2 inch w.c (50 Pa) in accordance with Section N1102.4.1.2, the dwelling unit shall be provided with whole-house mechanical ventilation in accordance with Section M1507.3. 5. N1102.4.1.2 (R402.4.1.2) Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 3 air changes per hour in Zones 3 through 8. Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals). Where required by the building official, testing shall be conducted by an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the building official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. #5 Mechanical and service water heating system and equipment types, sizes and efficiencies. Note and locate water heater or side arm off boiler. Label efficiency of water heater and whether gas or electric is shown on plan set. #6 Equipment and system controls. Label location of thermostats and heating zones on key plans. Provide at least on programmable thermostat Initially programmed set point of heating no higher than 70 degrees and cooling no lower than 78 degrees #7 Duct sealing, duct insulation, and pipe insulation and locations. 1. Show locations of ductwork in area not in the heated envelope (shown on drawings for mech. permit) 2. All ducts to be sealed in accordance with the International Mechanical Code (M1601.4.1) 3. Ducts outside building envelope to be insulated with R-8, all other ducts with R-6 4. Building framing cavities shall not be used as supply ducts 5. Duct tightness test (section 403.2.2) Duct tightness test is not required if air handler and ducts are ALL located within conditioned space Duct tightness shall be verified by a) Post construction test Leakage to outdoors:<8 cfm/per 100 s.f. pf conditioned floor area or Total leakage:<12 cfm/ pre 100 b) Rough-in test Total leakage <6 cfm/per 100 s.f. of conditioned floor area test at a pressure differential of .1 in w.g. (25 Pa) across rough-in system #8 Air sealing details: General note: All exterior joints are to be caulked, gasketed, weather stripped, or otherwise sealed. Floor plates and sheathing joints are to be sealed. Refer to chart for locations and methods. FROM JOHN MANSFIELD WEB SITE WALL INSULATION: TYPICAL EXTERIOR WALL 2" SPRAY FOAM =R-13 3.5" BATT =R-13 TOTAL WALL CAVITY INSULATION =R-26 (R-25 MIN) (ALTERNATIVE TO EXTERIOR CONTINUOUS INSULATION) TYPICAL FOUNDATION WALL AT LIVING SPACE 3.5" BLOWN-IN BATT (R-4.23 PER INCH). =R-13 1” RIGID INSULATION CONTINUOUS =R-4 2" DRAIN AND DRY ON EXT. OF FDN WALL = =R-10 TOTAL WALL R-VALUE =R-27 (R-19 MIN) TYPICAL SLAB EDGE/FROST WALL FOUNDATION WALL 2" DRAIN AND DRY ON EXT. OF FDN WALL = =R-10.00 (R-10 MIN) UNDER SLAB INSULATION: 2" RIGID INSULATION =R-10.00 (R-10 MIN) 3/4" SLAB EDGE INSULATION =R-7.00 (R-7 MIN) CANTILEVERED FLOOR INSULATION: 11 7/8" BLOWN-IN BATT (R-4.23 PER INCH) =R-50.23 (R-30 MIN) ROOF INSULATION: 12” SIP PANELS =+ R-49 (R-49 MIN) WINDOWS: FIXED =U-0.30 OPERABLE (AWNING AND CASEMENT) =U-0.30 PATIO DOOR AND SLIDING DOOR UNITS =U-0.30 INSULATION SUBCONTRACTOR MUST VERIFY THAT THE R-VALUES/U-VALUES OF PROPRIETARY PRODUCTS MEET OR EXCEEDS THE VALUES LISTED ABOVE AND THAT INSTALLATION PERFORMED IS PER MANUFACTURER'S SPECIFICATION. ALL WALL INSULATION SHALL COMPLETELY FILL STUD SPACES AND HAVE PROPER AIR-BARRIER SHEATHING ON BOTH SIDES OF THE STUD SPACES. INTERIOR WALLS ARE TO RECEIVE UNFACED SOUND ATTENUATION BATTS FOR ALL WALLS THAT DIVIDE HABITABLE ROOM (EXAMPLE: BEDROOM TO CLOSET WALL DOES NOT NEED SOUND INSULATION BEDROOM TO HALLWAY OR BEDROOM TO BEDROOM DOES) 2X6 = R-19 2X4 = R-13 PRESCRIPTIVE DESIGN INSULATION VALUE SUMMARY 2015 IECC AND TOWN OF VAIL ADOPTED AMENDMENTS 5/8" TYPE "X" GYPSUM WALL BOARD ON VAPOR RETARDER TYPICAL EXTERIOR 2X6 STUD WALL DETAIL WALL SHEATHING WITH THERMAL AND AIR INFILTRATION BARRIER ON EXTERIOR FACE R-13 BATT INSULATION TO FILL REMAINDER OF 2X6 STUD WALL CAVITY. R-13 SRRAY 2" OF FOAM INSULATION ON INTERIOR FACE OF EXTERIOR WALL SHEATHING TOTAL R-VAULE OF WALL = R-26 SIDING MATERIAL * WOOD SIDING * STUCCO SIDING * THIN-STONE PANELS ALL MATERIALS TO BE ATTACHED PER MANUFACTURER SPECS AND BEST PRACTICES 2. MAIN LEVEL 0" .5 A LOWER LEVEL -17' - 1 3/4" 1.5 A MAIN LEVEL -6' - 0" 2.5 A UPPER LVL 4' - 1 3/4" .8 A LANDING -11' - 1 3/4" EXTEND VENT PIPE 12" ABOVE ROOF. FAN INSTALL RADON SENSOR AT LOWEST LEVEL FAN LOCATION IN LAUNDRY ROOM MECH ROOM R-26 EXTERIOR WALL (TYP) SEE WALL DETAIL THIS SHEET R-38 BIBS INSULATION AT OVERHANGE (R-30 MIN.) DASH LINE INDICATES LOCATION OF VAPOR BARRIER/RETARDER IN ASSEMBLY 12” SIP PANELS +R-49 ALSO ACTS AS AIR BARRIER AND VAPOR BARRIER ALUM CLAD WOOD WINDOWS U VALUE = .30 MAX. R-10 SLAB EDGE INSULATION (SEE FOUNDATION DETAIL) R-10 RIGID INSULATION UNDER SLAB CONC. SLAB (HEATED) RADON SYSTEM IN GRAVEL UNDER SLAB R-13, R-19, OR R-30 UNFACED SOUND ATTENUATION BATTS AT INTERIOR WALLS / FLOORS, WHERE NEEDED FOR NOISE CONTROL. R-10 DRAIN AND DRY INSULATION BELOW GRADE R-10 RIGID INSULATION ABOVE GRADE R-17 FURRING INSULATION (SEE FOUNDATION DETAIL MECHANICAL SYSTEM: IN-FLOOR HYDRONIC RADIANT HEATING, +92% EFFICIENT CLOSED LOOP GAS SYSTEMS. DESIGN-BUILD BY MECH. SUB-CONTRACTOR. R-30 AT GARAGE 1 2 3 4 6 8 A5.0 3 A5.0 7 1 1 970.328.5151 OFFICE PO Box 1587, Eagle, CO 81631 www.martinmanleyarchitects.com Project number Date REVISIONS 8/29/2017 4:17:52 PM A0.1 ECO SHEET 1719 1709 GENEVA DUPLEX PERMIT SET 8-4-17 DAVE HILB 1709 GENEVA DRIVE, VAIL, CO MATTERHORN VILLAGE FILING 1, LOT 4 1/4" = 1'-0" 4 SECTION B - RADON CHASE MECHANICAL AND RADON SYSTEMS THE MECHANICAL SYSTEM FOR EACH SIDE OF THE DUPLEX WILL BE A "DESIGN-BUILD" TYPE SYSTEM. THE ARCHITECT HAS PROVIDED A PROPER SIZED MECHANICAL ROOM AND A VERTICAL CHASE TO THE ROOF FOR THE NEEDS OF THE MECHANICAL SUB- CONTRACTOR. THE HEATING SYSTEM: IN-FLOOR RADIANT HEATING WITHIN A 1 1/2" LAYER OF LIGHTWEIGHT CONCRETE ON UPPER LEVELS AND WITHIN THE 4" CONCRETE OF THE BASEMENT LEVEL. THE BOILER WILL BE A HIGH-EFFICIENCY GAS FUELED BOILER. THE WATER HEATER WILL BE A SIDE-ARM TYPE OF WATER HEATER. A RADON MITIGATION SYSTEM WILL BE INSTALLED TO MEET IRC2015 CODE REQUIREMENTS. SEE SECTIONS THIS SHEET FOR A PROJECT SPECIFIC DIAGRAM. 12" = 1'-0" ECO SHEET NOTES 12" = 1'-0" INSULATION VALUES 1" = 1'-0" 1 WALL DETAIL 1/4" = 1'-0" 2 SECTION A - RADON CHASE 1/4" = 1'-0" 3 SECTION B - MB @ E ECO PERMIT SET DATE: 8-4-17 1 No. Description Date 1 Permit Revisions 1 8-29-17 09/22/17