E17-0203_LOAD CALC.pdf
ti OF g, ! 4k:14110'Id Z' 4. ` ,s, IVER 4,, 2'�c� WHITE RIVER ELECTRIC,INC. - 'kin'0 PO Box 1118•Avon,Colorado 81620 970-949-1403-fax 970-926-5049 10/04/17 n www.whiteriverelectrFc.corn LOAD CALCULATION PER N.E.C. 220.82 142 WEST MEADOW DRIVE PRIMARY - 10/04/2017 240-V/ 1-PH SUPPLY GENERAL LOADS TYPE/QNT VA LOAD IN VOLT-AMPS GENERAL LIGHTING 4840 3 14520 KITCHEN SMALL APPLIANCE CIRCUITS 6 1500 9000 LAUNDRY SMALL APPLIANCE CIRCUITS 2 1500 3000 DISHWASHER 2 1200 2400 DISPOSAL 2 1600 3200 RANGE/OVEN 1 4000 4000 COOKTOP 1 2800 2800 CLOTHES WASHER 2 1800 3600 CLOTHES DRYER 2 4400 8800 REFRIGERATOR 2 700 1400 MICROWAVE 2 800 1600 UC REFRIGERATOR 2 400 800 INSTA HOT 2 700 1400 STEAM GENERATORS 1 5000 5000 HEAT TRACE 7 1400 9800 EXHAUST FAN 7 200 1400 WHIRLPOOL TUB 1 1200 1200 HOT TUB 1 5000 5000 TOTAL GENERAL LOADS 78920 FIRST 10 KVA 10000 40%OF REMAINING 27568 HEATING AND AIR CONDITIONING LOADS 100%OF AIR CONDITIONING LOADS CONDENSING UNIT 2 1800 3600 CONDENSING UNIT 1 4000 4000 65%OF ELECTRIC BASEBOARD BASEBOARD HEATER 1 2000 2000 100%OTHER HEATING LOADS BOILER 2 200 400 BOILER PUMPS 6 600 3600 NET CALCULATED LOAD VA 51168 SERVICE VOLTAGE 240 MINIMUM SERVICE PER 220.82 213 SERVICE BUSSING/MAIN AMPACITY 400