Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
E17-0125.001 Load Calcs.pdf
40 OF gr x Non-Dwelling Load Calculations Submitted by: Native Electric, Inc. Eagle Colorado j 10/05/17 Owner Name: Brandess-Cadmus Real Estate CO Phone: 970-470-1800 Location: 281 Bridge St,Vail (Upper Office) Total SQ. FT:700 General Contractor:CHL Construction Phone: 970-926-1268 Electrical Contractor Contact Name: Larry Arguello Phone: 970-904-6509 Genral Factors: QTY Multiplier/Demand Total VA Receptacle Load (Non-continuous) NEC 220-3 (b)(9) @90VA 2 Fixed Multioutlet Assemblies(Non-continuous) NEC 220-3 (b)(8) 3 Receptacle Load Demand Factor NEC 220-13 4 6000 6000 @1500 Each 4 Unknown Receptacle Load NEC 220-3 (a) General Lighting Load NEC 220-3(a) 5 700 FT 2100 2100 @3W/VA x Sq. FT. 6 Lighting Load Demand Factors NEC 220-11 1 1500 1500 7 Track Lighting(in Addition to General Lighting) NEC 220-12(b) 8 Sign and/or Outline Lighting Outlet NEC 220-3(b)(6) 9 Show Window Lighting NEC 220-12(a) 10 Continuous Load NEC 215-2(a), 215-3, and 230-42(a) 11 Kitchen Equipment NEC 220-20 (Microwave/Refrig) 2 3000 3000 12 Non-Coincident Loads NEC 220-21 13 Motor Loads NEC 220-4(a),430-24,430-25,430-26 and Article 440 14 All Other Loads(Baseboard Heater) 1 3200 3200 15 Total Volt-Ampere Demand Load (3 through 14) 13,700VA 16 Minimum Amperes Total VA%208V 65.86AMP 17 Minimum Size Service and/or Feeder NEC 240-6(a) 208V/100AMP 18 Size the Service and/or Feeder Conductors NEC 240-3 © 19 Minimum Size Conductro NEC 220-22 Minimum Size Grounding Electrode Conductor or 20 Equipment Grounding Conductor NEC 250-66, 250-122