Loading...
HomeMy WebLinkAboutA17-0064_Wiring Diagram End of line relay_1506966720.pdfCompatible Devices +up 2(1i2 10:21, AM Smoke Detector: System Sensor 4W-B 4-Wire P/E Smoke Detector Detection: Photoelectric Wiling: 4-wire Operating Voltage: 12/24 V non-polarized nominal, 8.5 min. to 35 max. Maximum Ripple Voltage: 30% of nominal (peak to peak) Alarm Current: 20mA max. 0 12V, 23mA 0 24V Standby Current: 50 pA max. avg. Alarm Contact Ratings: 0.5 A 0 30V AC/DC Temperature Range: 32° to 120°F (0° to 49°C) Humidity Range: 0% to 95% RH, noncondensing Sensitivity: 2.5%/ft. nominal Wiring Gauge: 14-22 AWG Dimensions: 2.0" (51mm) H x 5.3" (127mm) Dia. Weight: 6.3 oz. (178 g) Power Supervision Relay: System Sensor EOLR-1 SPST N/O Relay Model EOLR-1 is an epoxy encapsulated, single-pole single-throw, normally open relay that can be used as an end of line device in fire alarm systems, e.g. to supervise power supplies. Specifications EOLR-1 Operating Voltage 9 to 40 VDC Operating Current 20 mA DC max. Operating Temperature —22°F to 140°F (-30°C to 60°C) Humidity Range 10 — 93% RH Wire Length 8" minimum Contact Ratings 120 VAC: 0.5 A max. (resistive load) 30 VDC: 3 A max. (resistive load) AES Annunciator R3 Page 2 EOL RELAY (A77.7168) AUX OR SMOKE POWER IDC EOL RESISTOR 4-WIRE CONTROL PANEL 4W-B or 4W-B or 4W1*-43 4WT-B SO134-00 http://vmw.systemsensor.com/pdf/I56-1800.pdf • External Devices: • FireLite FCPS-24FSx : 24 Volt Remote Power Supply • System Sensor 4W-B: 4-Wire P/E Smoke Detector FIGURE 3B: WIRING DIAGRAM, 4W-B AND 4WT-B o System Sensor EOLR-1: EOL Power Supervision Module for 4-Wire Smokes A77-716B 12/24 VDC MAXIMUM RED INPUT CURRENT 19.3mA BLACK VIOLET VIOLET 3.0A @ 3OVDC 120VAC If you have any questions concerning System Sensor products or their application. please contztet Technical Services at 1-800-SENSOR2 (736-7672), extension 2. http://www.systemsensor.com/pdf/bulletins/eol relay.oclf