HomeMy WebLinkAboutBattery Calcs.xlsxProject Name: Device Description FACP FACP Annunciator FACP Annunciator Wireless Smoke Photoelectric smoke detector Heat Detectors- 135 degree fixed Wireless Heat Detectors-- Fixed and ROR Carbon Monoxide Detectors Wireless sounders 8 Zone Hardwire Expansion Module Ademco Radio Frequency Transciever Infrared Motion Detector Recessed Infrared Motion Detector Cornermount Glass Break Sensor Adjustable Low Temperature Sensor Water Detector Horns Knox Box Projected Batteries To Use: Projected Batteries Total Amp Storage: 4435 Glen Falls Lane Part Number ADE-Vista 128BPE ADE-6160RF ADE-6160RF ADE 5808W3 SYS-BK5603 ADE-5809 ADE-5800CO ADE-5800WAVE ADE-4208U ADE-5883H ADE-995 BOS-ISC-BPR2-WP12 INT-FG-1625F ADE-TS300 GRI-2600 SYS-MHW Knox 1650 12V 8AH 8AH QTY 1 1 0 9 0 1 6 7 0 0 0 0 0 0 0 1 1 Device Current Standby mA 250 30 45 0 0 0 0 0 27.3 30 15 10 12 25 10 0 0 Total System Draws: Converted to Amps: 24 hrs Standby: 15 min Alarm: Total Alarm Panel Amp Hours: Efficiency Factor 20%: Required Amp Hours: Device Current Alarm mA 330 150 150 0 30 0 0 0 27.3 30 15 10 22 50 10 12 0 Total Current Standby mA 250 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 280 0.28 Total Current Alarm mA 330 150 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 492 0.492 6.72 0.123 6.843 1.3686 8.2116 Location Lower mechanical room Garage entry To NFPA 72 and Vail Standards Mechanical room. Garage, Kitchen, Lockoff kitchen, attick. To NFPA 72 and Vail Standards In all bedrooms Garage Outside Garage