Loading...
HomeMy WebLinkAboutSnow Fox Load Calcs.pdf From: Arnold Vigil sierraelectric@live.com Subject: snow fox ,, Date: May 4,2014 at 12:04 PM ' To: Ed Turnbull nobullremodeling@gmail_com Arnold Vigil Sierra Electric 970-389-3844 sierraelectric@live.corn Load calc. for snow fox remodel unit # 201 1100 sq. ft. 3 VA per sq. ft. 3000VA 3000VA at 100% 3000VA General lighting - 3000VA Small appliance load - 3000VA Laundry - 1500VA Range load - 8000VA Dryer load - 5500VA New baseboard heater -1000VA Total Load - 23500 divided by 240V. = 97.91 Amps The unit has a 125 amp main breaker. If you have any questions or concerns please contact me at 970 389 3844. Thanks Arnold Vigil