HomeMy WebLinkAboutLANDERS 2 - Sheet - A3-1 - DETAILS & ENERGY CODE.pdfR-51 INSULATION
MAIN LEVEL T.O.PLY.
TREATED SILL PLATE W/
CAPILLARY BREAK
MAIN LEVEL
RIM JOIST
STUCCO EIFS SYSTEM (1 1/2") TO MATCH EXISTING
OVER WEATHER BARRIER HOUSE WRAP
R-22
INSULATION
AT RIM JOIST
1 1/2" FINISH FLOOR
OVER 1 1/2" LIGHT-WEIGHT
CONCRETE HEATED FLOOR
2X6 WOOD STUD WALL EXTERIOR 1/2"
SHEATHING
THERMAL BREAK
2" 5"
4"
4' - 0"
NOTE: SLAB TO EXTEND AT
SPECIAL CONDITIONS RE:
STRUCT. DWGS.
MIN. FROST DEPTH
FOUNDATION PROTECTION SYSTEM:
COMPOSITE DRAINAGE BOARD W/ FILTER FABRIC
TO CONTINUE FROM FOOTING TO WITHIN 8" BELOW
FINISH GRADE.
-OVER-
1" "DOW" (OR EQUAL) STYROFOAM INSUL. = R-5
TO EXTEND FROM FTG. TO TOP-OF-WALL.
-OVER-
WATERPROOF MEMBRANE ON CONCRETE WALL
TO CONTINUE FROM FOOTING TO 2'-6" ABOVE
FINISHED GRADE.
ALTERNATE: USE 3/4" "DRAIN & DRY" BOARD
INSTEAD OF COMPOSITE DRAINAGE BOARD =
TO CONTINUE FROM FOOTING TO WITHIN 8"
BELOW FINISH GRADE. = R-3.1
5/8" TYPE "X" GWB
R-10 SLAB PERIMETER
INSULATION (1 FT. LENGTH):
1/2" RIGID INSULATION
+ 1 1/2" EIFS INSULATION
R-22 BLOWN-IN INSULATION
TO COMPLETELY FILL 2X6
STUD WALL CAVITY.
R-10 UNDER-SLAB RIGID
BOARD INSULATION (2")
3 FT. LENGTH
HEATED CONCRETE SLAB
(IN-FLOOR RADIANT
HEATING SYSTEM)
GRANULAR FILL
REFER TO STRUCTURAL DRAWINGS
FOR FOUNDATION/FOOTING DESIGN
AND REINFORCEMENT SLOPED 4" PERFORATED DRAIN
PIPE. ALL FOUNDATION WALLS
INCLUDING INTERIOR WALLS.
RE: SOILS REPORT
5/8" TYPE "X" GYPSUM WALL
BOARD (HELD UP FROM SLAB 3/8")
BASE TRIM (PROFILE TBD)
FINISH GRADE:
6" BELOW SILL PLATE MIN.
SLOPE AWAY
POLYETHYLENE
VAPOR BARRIER
PLYWOOD SHEATHING TO
OVERLAP SILL PLATE 2"
1' - 0"
3' - 0"
CODE MINIMUM
RECOMMENDED: FULL COVERAGE
OF UNDER-SLAB INSULATION
TREATED SILL PLATE W/
CAPILLARY BREAK
THERMAL BREAK
2" 5"
4" 4' - 0"
MIN. FROST DEPTH
FOUNDATION PROTECTION SYSTEM:
COMPOSITE DRAINAGE BOARD W/ FILTER FABRIC
TO CONTINUE FROM FOOTING TO WITHIN 8" BELOW
FINISH GRADE.
-OVER-
1" "DOW" (OR EQUAL) STYROFOAM INSUL. = R-5
TO EXTEND FROM FTG. TO TOP-OF-WALL.
-OVER-
WATERPROOF MEMBRANE ON CONCRETE WALL
TO CONTINUE FROM FOOTING TO 2'-6" ABOVE
FINISHED GRADE.
ALTERNATE: USE 3/4" "DRAIN & DRY" BOARD
INSTEAD OF COMPOSITE DRAINAGE BOARD =
TO CONTINUE FROM FOOTING TO WITHIN 8"
BELOW FINISH GRADE. = R-3.1
R-22 BLOWN-IN INSULATION
TO COMPLETELY FILL 2X6
STUD WALL CAVITY.
R-10 UNDER-SLAB RIGID
BOARD INSULATION (2")
RECOMMENDED FULL
COVERAGE
HEATED CONCRETE SLAB
(IN-FLOOR RADIANT
HEATING SYSTEM)
GRANULAR FILL
SLOPED 4" PERFORATED DRAIN
PIPE. ALL FOUNDATION WALLS
INCLUDING INTERIOR WALLS.
RE: SOILS REPORT
5/8" TYPE "X" GYPSUM WALL
BOARD (HELD UP FROM SLAB 3/8")
BASE TRIM
(PROFILE TBD)
FINISH GRADE:
6" BELOW SILL PLATE MIN.
SLOPE AWAY
POLYETHYLENE
VAPOR BARRIER
PLYWOOD SHEATHING TO
OVERLAP SILL PLATE 2"
R-14 BLOWN-IN INSULATION
TO COMPLETELY FILL 2X4
STUD FURRING WALL CAVITY.
WOOD CAP OVER
RIGID INSULATION
R-5 (1") CONTINUOUS
RIGID INSULATION R-10 INSULATION
1/2" RIGID INSULATION
+ 1 1/2" EIFS INSULATION
R-5 (1") CONTINUOUS
RIGID INSULATION
CLIMATE
ZONE
FENESTRATION
U-FACTOR
SKYLIGHT
U-FACTOR
GLAZED
FENESTRATION
SHGC
CEILING
R-VALUE
WOOD FRAME
WALL R-VALUE
MASS WALL
R-VALUE
FLOOR
R-VALUE
BASEMENT
WALL R-VALUE
SLAB R-VALUE
& DEPTH
CRAWLSPACE
WALL R-VALUE
6 .32 .55 NOT
REQUIRED 49 20 + 5
(OR 13 + 10)
15 / 20 30 15 / 19 10 , 4 ft. 15 / 19
FROM TABLE R402.1.1 - IRC 2012
FROM TABLE N1102.1.1 - IECC 2012
INSULATION MINIMAL VALUES BY CODE
a b c
d e f e
a. Eagle County lies in climate zone 6B.
b. This is a prescriptive maximum u-factor for all windows and
doors.
c. This means R-20 for cavity insulation + R-5 for exterior
continuous insulation. The Town of Vail has not adopted
the additional R-5 at this time.
d. The second R-value applies when more than half the
insulation is on the interior of the mass wall.
e. "15/19" means R-15 continuous insulation on the interior or
exterior of the basement wall -or- R-19 cavity insulation at
the interior of the basement wall (a combination cavity and
continuous must equal R-19 as well).
f. R-5 shall be added for heated slabs. The R-values and
depth dimension can be spread between perimeter and
under-slab locations.
ADDITIONAL NOTES:
N1102.2.1 (R402.2.1) Ceilings with attic spaces.
When Secton N1102.1.1 R-38 shall be deemed to satisfy the requirement for R-49 wherever the
full height of uncompressed R-38 insulation extends over the wall top plate at the eaves.
N1102.2.2 (R402.2.2) Ceilings without attic spaces.
Where Secton N1102.1.1 would require insulation levels above R-30 and the design of the
roof/ceiling assembly does not allow sufficient space for the required insulation, the minimum
required insulation for such roof/ceiling assemblies shall be R-30. This reduction of insulation from
the requirements of Secton N1102.1.1 shall be limited to 500 square feet (46 m2) or 20 percent of
the total insulated ceiling area, whichever is less.
N1102.2.3 (R402.2.3) Eave baffle.
For air permeable insulations in vented attics, a baffle shall be installed adjacent to soffit and eave
vents. Baffles shall maintain an opening equal or greater than the size of the vent. The baffle shall
extend over the top of the attic insulation. The baffle shall be permitted to be any solid material.
N1102.2.4 (R402.2.4) Access hatches and doors.
Access doors from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces)
shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding
surfaces. Access shall be provided to all equipment that prevents damaging or compressing the
insulation. A wood framed or equivalent baffle or retainer is required to be provided when loose fill
insulation is installed, the purpose of which is to prevent the loose fill insulation from spilling into the
living space when the attic access is opened, and to provide a permanent means of maintaining
the installed R-value of the loose fill insulation.
N1102.2.5 (R402.2.5) Mass walls.
Mass walls for the purposes of this chapter shall be considered above-grade walls of concrete
block, concrete, insulated concrete form (ICF), masonry cavity, brick (other than brick veneer),
earth (adobe, compressed earth block, rammed earth) and solid timber/logs.
N1102.2.7 (R402.2.7) Floors.
Floor insulation shall be installed to maintain permanent contact with the underside of the subfloor
decking.
N1102.2.8 (R402.2.8) Basement walls.
Walls associated with conditioned basements shall be insulated from the top of the basement wall
down to 10 feet (3048 mm) below grade or to the basement floor, whichever is less. Walls associated
with unconditioned basements shall meet this requirement unless the floor overhead is insulated in
accordance with Sections N1102.1.1 and N1102.2.7.
N1102.2.9 (R402.2.9) Slab-on-grade floors.
Slab-on-grade floors with a floor surface less than 12 inches (305 mm) below grade shall be
insulated in accordance with Table N1102.1.1. The insulation shall extend downward from the top of
the slab on the outside or inside of the foundation wall. Insulation located below grade shall be
extended the distance provided in Table N1102.1.1 by any combination of vertical insulation,
insulation extending under the slab or insulation extending out from the building. Insulation extending
away from the building shall be protected by pavement or by a minimum of 10 inches (254 mm) of
soil. The top edge of the insulation installed between the exterior wall and the edge of the interior
slab shall be permitted to be cut at a 45-degree (0.79 rad) angle away from the exterior wall.
N1102.2.10 (R402.2.10) Crawl space walls.
As an alternative to insulating floors over crawl spaces, crawl space walls shall be permitted to be
insulated when the crawl space is not vented to the outside. Crawl space wall insulation shall be
permanently fastened to the wall and extend downward from the floor to the finished grade level and
then vertically and/or horizontally for at least an additional 24 inches (610 mm). Exposed earth in
unvented crawl space foundations shall be covered with a continuous Class I vapor retarder in
accordance with this code. All joints of the vapor retarder shall overlap by 6 inches (153 mm) and be
sealed or taped. The edges of the vapor retarder shall extend at least 6 inches (153 mm) up the stem
wall and shall be attached to the stem wall.
N1102.2.11 (R402.2.11) Masonry veneer.
Insulation shall not be required on the horizontal portion of the foundation that supports a masonry
veneer.
970.328.5151 OFFICE
PO Box 1587, Eagle, CO 81631
www.martinmanleyarchitects.com
Project number Date REVISIONS5/2/2014 7:15:22 AM
A3.1 DETAILS & ENERGY CODE
1354 LANDERS RENOVATION
Permit Set
03-06-14
John & Debra Landers
1454W Greenhill Court
Vail, CO 81658
1 1/2" = 1'-0"
1
EAVE 1 DETAIL
1" = 1'-0"
3 DETAIL - FOUNDATION
1" = 1'-0"
4
DETAIL - STEPPED FOUNDATION
RAILING DETAIL: MATCH EXISTING METAL RAILING.
MATCH STUCCO WALLS W/ STONE CAP.
MATCH STONE, CAP, STUCCO,
AND WINDOW DETAILS.
AT ALL NEW ROOF CONSTRUCTION - R-49 MINIMUM INSULATION VALUE WITHIN
11 1/4" RAFTER SPACE. ARCHITECT RECOMMENDS 2" SPRAY FOAM R-14 AND 9 1/4"
BLOWN-IN INSULATION R-37 FOR A TOTAL OF R-51.
INSULATION SUMMARY
ALL MINIMUM INSULATION VALUES FROM IRC 2012
ROOF RAFTERS = R-49 (MIN. R-51)
EXTERIOR WALL INSULATION = R-22 (MIN. R-20)
BASEMENT WALL INSULATION = R-19 (MIN. R-19)
HEATED SLAB INSULATION = R-15 (MIN. R-15)
WINDOWS U-VALUE MAX. = U-.32 (MAX. U-.32)
INSULATION SUBCONTRACTOR MUST VERIFY THAT R-VALUES OF PROPRIETARY
PRODUCTS MEET OR EXCEED THE R-VALUES LISTED ABOVE AND THAT
INSTALLATION PERFORMED PER MANUFACTURER'S SPECIFICATIONS. ALL
INSULATION SHALL COMPLETELY FILL STUD/JOIST SPACES AND HAVE PROPER AIR-
BARRIER SHEATHING ON BOTH SIDES OF THE STUD/JOIST SPACES.
No. Description
Date
07/16/14