HomeMy WebLinkAboutSnow Retension Plan.pdf1657 South 580 East American Fork, UT, 84003
Ph: 801.756.8666 | Fx: 801.756.7891 | trasnowandsun.com
20140814-BI Bighorn Condos Vail.dwg
REVISIONS
STAMP
1. Snow Bracket / Snow Fence layout has been
engineered for this specific roof application. Any
deviation from the prescribed layout will void the
product or system warranty.
2. Install Snow Brackets / Snow Fence per
specifications and details provided by TRA Snow
and Sun. Installer is responsible for the correct
installation of all snow retention system
components.
3. Installer shall check existing job site conditions
and dimensions prior to installation. Installer shall
report any discrepancies or conflicts to TRA Snow
and Sun prior to commencing work.
4. Drawings and quotes are based upon information
provided by the customer to TRA Snow and Sun.
TRA Snow and Sun is not liable for any information
that is found to be incorrect or false.
5. Any snow bracket quantity shown is for estimating
purposes only and is based on the calculated
number of snow brackets per roofing square.
Installer is responsible to verify proper snow
bracket quantity based on actual number of roofing
squares.
GENERAL NOTES
DISCLAIMER: These drawings are the property of TRA Snow
and Sun and any reuse or further distibution thereof in part or
in whole without written consent from TRA Snow and Sun is
prohibited. Drafter is not an architect or engineer.
SNOW RETENTION NOTES
ROOFING MAT'L:
DECK SHEATHING:
GROUND SNOW LOAD:
MAT'L/COLOR:
MOUNT SPACING:
FENCE TYPE:
EST. NO. ROOFING SQ
BRACKET TYPE:
SPACING/WIDTH:
RIB HEIGHT:
ROOF SLOPES:
KEY NOTES
CLAMP ON
SNOW FENCE
SNOW FENCE
DECK MOUNT
SNOW
BRACKET
EXPANSION
JOINT
BIGHORN CONDOS
CY
SR1.0
1 1
SNOW RETENTION PLAN
3/32" = 1'-0"
1
BRACKETS/SQ
SR1: J SNOW BRACKET (SEE DETAIL 2-3/SR1.0)
1. ALL J SNOW BRACKET EAVE COURSES TO
BE INSTALLED 143
32" FROM EAVE, U.N.O.
J SNOW BRACKET LAYOUT DETAIL
1/4"=1'-0" 4:12 SLOPE 18.5 BPS
2 J SNOW BRACKET INSTALLATION DETAIL
NO SCALE
3
PART / DESC QTY
SNOW RETENTION PART SCHEDULE
INSTALLATION:
AFTER METAL TILE HAS BEEN INSTALLED ON
DECK WITH 2"x2" BATTEN, INSTALL THE J
BRACKET WITH THE TRIANGULAR END TOWARDS
THE DOWNHILL SLOPE. INSTALL A HIGH QUALITY
BUTYL CAULK BELOW THE TRIANGULAR END OF
THE BRACKET. THEN INSTALL ONE 3/16" SCREW INTO
THROUGH HOLE IN THE SNOW BRACKET THROUGH
HOLE IN METAL/GRANULE TILE 2"x2" BATTEN A
MINIMUM OF 1 1/4".
SNOW BRACKET 'J'
METAL/GRANULE TILE
ROOF
08/27/14