HEPWORTH-PAWLAK GEOTECH!'JICl\L
July 31, 2014
Nedbo Construction
Attn: Nate Brandenburg
P.O. Box 3419
Vail, Colorado 81658
nate@nedbo.com
l '', rll. !)~ -·-+--1 i-!
; ,-',_' I+:-, -+
ii 111 'i:
Job No. 114 179A
Subject:
Gentlemen:
Construction Observation and Testing Completion Letter, Deck Pads and
Elevator Addition, Northwood Condominiums, Unit Fl, 600 Vail Valley
Drive, Vail, Colorado
As requested by Warren Krok ofNedbo Construction, we are providing a summary of our
observation and testing services provided for the above referenced project. The reports of
the services requested and performed for the project are attached. We previously
evaluated the bearing soils for design of foundations at the site and presented our findings
in a report dated May 30, 2014, Job No. 114 179A.
The foundation bearing soils exposed at the bottom of the excavation were observed on
May 21 and 27, 2014, dowel holes and epoxy placement were observed on May 28, 2014,
and fresh concrete placed for the foundation was sampled and tested on May 28 and 30,
2014 according to the project specifications.
Based upon inferences drawn from our observation and testing, as documented by the
attached daily field reports, it is our professional opinion that the referenced construction
has achieved the specified conditions. Please recognize that construction observation and
testing are sampling functions that involve direct observation and testing of very limited
amount of the overall work to evaluate the construction compliance.
If you have any questions or need further assistance, please call our office.
Sincerely,
SLP/ksw
Attachments:
cc: Nedbo Construction -Warren Krok(\\ an~t;'.W~nedho.qim)
Parker 303-841-7119 • Cnloradl1S~•rings 719-633-5562 • Siln:rthnrne 970-468-1989
~
HEPWORTH -PAWLAK GEOTECHNICAL
5020 County Road 154
Glenwood Springs, CO 81601
Phone: 970-945-7988
Fax: 970-945-8454
REINFORCEMENT STEEL INSPECTION REPORT
Client: Nedbo Construction
Attn: Nate Brandenburg
P.O. Box 3419
Vail, Colorado 81658
Job No.: 114179A Day:
Date:
Page:
Wednesday
5/28/14
1 of 1
Project: Proposed Deck Pads and Elevator Additions, Northwood Condominiums, Unit F1, 600
Vail Valley Drive, Vail, Colorado
Area of Inspection:
Reference Documents
Used:
structural drawings provided by Vasequez Concrete and Red Head
hollow base material screen instructions
Inspection Status: D Preliminary rgj Final
rgj Concrete reinforcement as noted above was judged to be in reasonable conformance with the
referenced construction documents.
D Exceptions Noted: holes were a depth of 6" and free of debris prior to placement of epoxy
and dowels. Red Head C6+ and Red Head A7 adhesives were used in the
epoxy process
Verbal
Communication:
Distribution:
Nate with Nedbo Construction and Gilbert with Vasquez Concrete were
informed of our inspection results.
Nedbo Construction -Nate Brandenburg (nate@nedbo.com)
Justin Orgill Steven L. Pawlak, P.E.
Field Technician Reviewed By
C~ech
HEPWORTH -PAWLAK GEOTECHNICAL
5020 County Road 154
Glenwood Springs, CO 81601
Phone: 970-945-7988
Fax: 970-945-8454
hpgeo@hpgeotech.com
CONCRETE TEST REPORT
Nedbo Construction
Attn: Nate Brandenburg
P.O. Box 3419
Vail, Colorado 81658
Job No. 114179A
Date Cast: 05-28-14
Sheet: 1of1
Project: Proposed Deck Pads and Elevator Additions, Northwood Condominiums, Unit F1,
600 Vail Valley Drive, Vail, Colorado ~_.,.,-----
Placement Location: F1 Elevator Pit FooUng a~ Way FooU~
Supplier: United Time Batched: Not on ticket Load Size (Yds): 3
Truck No: 0000 Time Arrived: 1:40 pm Yds Delivered: 3
Ticket No: 33501623 Time Placed: 1:45 pm Yds Ordered: 3
Mix Design: 35010400
Method of Placement: Truck Sample Point: Truck Discharge
Time Sampled:
Air Temp:
Concrete Temp:
Water Added:
1:59 pm Wet Unit Wt:
70° Slump:
72° Air Content:
8 gallons per Contractor
142.4 pcf
3.0 inches
5.3 %
Communication: The Contractor and Supplier were informed of our field test results.
Time Cylinders Cast: 2:09 pm
Initial Cure Time On Site: 1 day Field Storage: Insulated Cure Box
Date in Lab: 05-29-14 Cylinder Temperature at Pick Up: 87° Min/Max: 74°/95°
Compressive Strength Data
2014 Compressive 28 Day Lab Age Load Diameter Area
Days Date lbs. in. in2 Strength (psi) Avg. (psi) Number
330A 7 06-04-14 37,200 4.01 12.63 2950
330B 28 06-25-14 51,800 4.01 12.63 4100
330C 28 06-25-14 51,500 4.01 12.63 4080 4090
3300 Hold/56 Discarded
Specified Strength for Structure: 3000 psi at 28 days Specified Strength for Mix: 3000 psi at 28 days
Notes:
Distribution:
Nedbo Construction -Nate Brandenburg (nate@nedbo.com)
United -Rick Seymour (rseymour@united-gj.com)
Justin Orgill
Field Technician
/ljg
Thomas J. Westhoff, CET
Reviewed By
·~ech
HEPWORTH -PAWLAK GEOTECHNICAL
5020 County Road 154
Glenwood Springs, CO 81601
Phone: 970-945-7988
Fax: 970-945-8454
hpgeo@hpgeotech.com
CONCRETE TEST REPORT
Nedbo Construction
Attn: Nate Brandenburg
P.O. Box 3419
Vail, Colorado 81658
Job No. 114179A
Date Cast: 05-30-14
Sheet: 1 of 1
Project: Proposed Deck Pads and Elevator Additions, Northwood Condominiums, Unit F1,
600 Vail Valley Drive, Vail, Colorado
Placement Location: F1 Elevator Pit Wall a~ Way W~
Supplier: United Time Batched: 1 :03 pm Load Size (Yds): 5
Truck No: 42 Time Arrived: 1:23 pm Yds Delivered: 5
Ticket No: 121 Time Placed: 1:28 pm Yds Ordered: 5
Mix Design: 35010400
Method of Placement: Truck Sample Point: Truck Discharge
Time Sampled:
Air Temp:
Concrete Temp:
Water Added:
1:34 pm
50°
64°
None
Wet Unit Wt:
Slump:
Air Content:
140.0 pcf
4% inches
6.8%
Communication: The Contractor and Supplier were informed of our field test results.
Time Cylinders Cast: 1 :44 pm
Initial Cure Time On Site: 3 days Field Storage: Insulated Cure Box
Date in Lab: 06-02-14 Cylinder Temperature at Pick Up: 55° Min/Max: 54°/74°
Compressive Strength Data
2014 Compressive 28 Day Lab Age Date Load Diameter Area Strength (psi)
Number Days lbs. in. in2 Avg. (psi)
338A 7 06-06-14 28,800 4.01 12.63 2280
338B 28 06-27-14 48,400 4.01 12.63 3830
338C 28 06-27-14 46,000 4.01 12.63 3640 3740
3380 Hold/56 Discarded
Specified Strength for Structure: 3000 psi at 28 days Specified Strength for Mix: 3000 psi at 28 days
Notes:
Distribution:
Nedbo Construction -Nate Brandenburg (nate@nedbo.com)
United -Rick Seymour (rseymour@united-gj.com)
Justin Orgill
Field Technician
/ljg
Thomas J. Westhoff, CET
Reviewed By