HomeMy WebLinkAboutBegin_Workflow - Review Comments - 06-06-2014_13-30-08.pdfBegin_Workflow Review Comments 06062014_133008
Review
Cycle Department Markup Snapshot
1 Building File: MP2.0.pdf
ChangeMark: mhaeberle
Description: B001
Comment: Secondary drains to be independent of primary drains per 2012 iPC. Revise plans to show code compliance
1 Building File: S1.01.pdf
ChangeMark: mhaeberle
Description: B001
Comment: Identify special inspections and program per Chapter 17 IBC
1 Building File: S1.01.pdf
ChangeMark: mhaeberle
Description: B002
Comment: Show compliance with Chapter 16 for proposed guards and hand railings Please inlcude complince for additional load stressing on glass guards
1 Building File: _COVER.pdf
ChangeMark: mhaeberle
Description: B001
Comment: Provide code analysis to include: Building Type Occupancy Fire resisitve construction of variuos building elements special inspection critieria for fire
protection of damaged elements and new Roof classification Codes proposed work designed to
1 Building File: _COVER.pdf
ChangeMark: mhaeberle
Description: B002
Comment: Provide details of fire resistive elements of new and repaired construction showing compliance with the IBC 2012 edition