Loading...
HomeMy WebLinkAboutLot 3 Elect Load Calculation .pdfWIRE NUT ELECTRIC INC PO BOX 1112 AVON, CO. 81620 970-926-8855 Load Calculation May 16, 2014 Brian Redinger Solaris Redevelopment Corp. Load Calculation for lot 3 Elk Meadows 300 Amp single phase service for a 4,026 sq. ft. Single Family. General Load: 4026 X 3VA Lighting 12,078VA 1500 X 6 small appliance circuits 9,000VA 2 Laundry 3,000VA Range 7,560VA Dishwasher 1,200VA Refrigerator 1,200VA 2 Dryers 9,000VA AC load greater than heating load including Heat Tape 14,500VA Spa Tub 12,000VA Steam Unit 12,000VA Total 81,538VA First 10 KVA @ 100% 10,000VA Remainder of General Load @ 40% 71,538 X 40% 28,615VA Total General Load 38,615VA 38,615VA / 240V = 161 Amps We are going with a 300 amp service to allow for expansion of future electrical needs. Thank You Please call with any questions