Loading...
HomeMy WebLinkAboutLot 3 Mech specs.pdf 5/7/14 Lot 3 Elk Meadows 15000-1 DIVISION 15 MECHANICAL Copyright 2014 - Rader Engineering, Inc. SECTION 15000--SYSTEM OVERVIEW 1. It is the intent of these specifications to outline the anticipated mechanical systems. The successful contractor shall be responsible to size all equipment, provide equipment specifications and coordinate installation of the systems with the General Contractor. These specifications are a supplement to specifications provided by Suman Architects. If there are any conflicts between the two specifications address any questions to the Architect. Equipment manufacturers listed shall be included as the base bid. Contractors may propose alternate equipment/systems to the base bid as an alternate price to the base bid. 2. Rader Engineering has performed load calculations for the home and they are as follows. These output loads shall be used for sizing the boilers and heating equipment. Also see Heat Loss & Gain Summary for loads for individual rooms. a. The building heat loss is 71,400 BTU/H. b. The domestic water heating load is 70,400 BTU/H. c. The kitchen make-up air load is 72,000 BTU/H. This is based on 1000 CFM. d. There is no snowmelting. 3. BOILER: Provide and install a high efficiency wall-hung condensing boiler to provide heat for space heating, domestic hot water and kitchen make-up air. The base bid shall be for (1) Lochinvar WHN 285. The heating system shall be designed to maximize the boiler efficiency by allowing the system to operate below condensing temperatures (less than 130°F return water temperature) at all times except during a call for domestic water heating and kitchen make up air. During a call for domestic water heating or kitchen make up air the boiler supply temperature setpoint shall be ramped up to 160°F. Include a condensate neutralization basin. Terminate flue above the roof, per manufacturer’s installation instructions. Sidewall termination is not permitted. Boilers shall be located in the Mech Room. Do not prioritize domestic water heating. Connect an outside air temperature sensor directly to the boiler. 4. RADIANT FLOOR HEATING: The home is to be heated by a radiant floor system throughout. The tubing shall be installed in the concrete slab or in a concrete topping slab. Provide individual loop balancing valves as provided by the tubing manufacturer to adjust the flow rate to each loop. Do not install tubing under built-in cabinets. Tubing shall be run under all bath tubs and under 5/7/14 Lot 3 Elk Meadows 15000-2 all showers and extend into benches of the showers. Tubing shall also be run into closets associated with the Bedroom zones. Route tubing to avoid wall locations. Include temperature reset controls to automatically adjust radiant floor heating water temperatures based on outdoor temperatures. Manifold locations must be coordinated with, and approved by, the Developer. Locate all radiant zone valves in the mechanical room. A common supply pipe can be run to serve all zones but individual dedicated return lines (one per zone) will be required to be “home-run” to the mechanical room. The heating zones are as follows: 1. Garage 2. Entry, Mud, Hall, Laundry 3. Bed 1, Bath 1 4. Bed 2, Bath 2 5. Family Room 6. Den 7. Kitchen, Living, Dining, Hall, Powder 8. Bed 3, Bath 3 9. Master Bed, Closet 10. Master Bath 5. AIR CONDITIONING and KITCHEN MAKE UP AIR: Install a fan coil with 2000 CFM capacity to provide 2 zones of cooling for the upper level. This fan coil shall also be utilized for kitchen make-up air. During a call for make-up air, the dampers shall change position to allow 1000 CFM of outside air to be delivered to the Kitchen zone to replace the air exhausted by the kitchen hood. Include controls to automatically temper the make up air to 70 degrees during the winter months. Include a MERV 11 air filter. Provide vibration isolators as required. Duct connections to the fan coil shall be made with flexible canvas connectors. Provide a freezestat to protect the hydronic coil from freezing by disabling the fan if near freezing conditions are detected. Coordinate exact location of the fan coil and duct routings with the Architect and Developer. The condensing unit shall have a nominal 4-ton capacity. Include low ambient control, filter drier, high and low pressure switches, fan motor with ball bearings, hard shutoff TXV, Evaporative freeze thermostat, cycle protector, compressor start assist capacitor and relay. The cooling zones are as follows: 1. Den, Kitchen, Living, Dining 2. Bed/ Bath 3, Master Suite 5/7/14 Lot 3 Elk Meadows 15000-3 6. GRILLES & REGISTERS: All supply and return grilles shall be Titus CT series linear bar grilles or equivalent. All floor grilles shall be pencil proof and shall have flangeless frames. All wall and ceiling grilles can be flanged frames. Size for NC of 25 maximum in bedrooms and 30 maximum in living areas. 7. KITCHEN EXHAUST: The kitchen exhaust duct shall be sized for 1000 CFM, 10” diameter minimum. 8. BATH EXHAUST: Provide Panasonic bath exhaust fans for all bathrooms. Fans shall exhaust 70 CFM minimum. Fans to be Panasonic FV-08VRL1. 9. WATER HEATER: The domestic water heating system shall be supplied from the central boiler system. Provide 1 indirect water heater with a storage capacity of 82 gallons, Lochinvar Squire SIT 080. Include a domestic hot water recirculation system with pump and dedicated recirculation piping. Recirc pump shall be controlled by an integral timer & aquastat. Water Heater shall be located in the Mech Room. 10. TEMPERATURE CONTROLS: The temperature control system desired shall include 7-Day programmable touchscreen thermostats with humidity control. Honeywell TH8321R1001 or equivalent. 11. HYDRONIC PUMPS: All hydronic heating pumps shall be Grundfos wet-rotor type pumps. Pumps with a ¾ hp and greater motor size shall be installed with piping isolators to minimize vibration transmission to the piping. Piping isolators shall be Mason Industries Safeflex SFDEJ or equal (elastomeric piping isolators, peroxide cured EPDM with Kevlar reinforcement). 12. HOSE BIBBS: Provide freeze resistant exterior hose bibs and interior hot & cold hose bibs as shown on the Architectural plans. Install a hot and cold hose bibb in the garage and a frost-proof hose bibb at the rear of the house. 13. STEAM GENERATOR: Provide a steam generator for the Master Shower, Mr. Steam or equal. Refer to architectural drawings for locations. Contractor shall coordinate with manufacturer for proper steam generator sizing. Include auto drain and controls to adjust time & temperature from inside shower. 14. GAS PIPING: Route gas lines to all loads which include the following: Boiler, Living Room Fireplace and exterior BBQ grill. 15. Install a recessed dryer vent box at all dryers. Ducting between the dryer boxes and the exterior shall be 4” rigid metal. Flexible ductwork is not allowable. 5/7/14 Lot 3 Elk Meadows 15000-4 16. Fill heating water system with 30% propylene glycol / 70% water solution, by volume, for freeze protection to 8°F and burst protection to -20°F. Include corrosion inhibitors. ADD ALTERNATE OPTIONS: 1. Provide an ADD Alternate price to install a point-of-use Reverse Osmosis water filtration system to provide R.O. water to a dedicated faucet near the Kitchen Sink. 2. Provide an ADD alternate price to upsize the water heater to a Lochinvar SIT 119. 3. Provide an ADD alternate price to install a Lennox HEPA-40 Bypass Air Filtration System onto the air conditioning system. 4. Provide an ADD alternate price to install a 2-stage condensing unit in lieu of a single stage unit. 5. Provide an ADD Alternate price to install a steam humidification to the air conditioning system. Humidifier shall be manufactured by Nortec or equal. Unit shall be equipped with a steam distribution tube installed in the supply ductwork. Humidifier will have a capacity of 8 lbs/hr minimum. Include controls to automatically reset the indoor humidity levels based on outdoor temperatures. Include a high limit duct-stat downstream of the steam injection tube. Include air proving switch. 6. Provide an ADD alternate price to install cast iron waste lines above ground. END OF SECTION 15000 5/7/14 Elk Meadows 15010-1 SECTION 15010--GENERAL PROVISIONS PART 1.00--GENERAL 1.01 SCOPE OF WORK Work shall consist of furnishing all labor and materials necessary for the installation of complete and operating mechanical systems. 1.02 EXAMINATION OF PREMISES Visit the premises before submitting bid as no extras will be allowed for lack of knowledge of existing conditions. 1.03 CODES AND STANDARDS Comply with all applicable codes, laws, industry standards and utility company regulations. 1.04 PERMITS, FEES AND NOTICES Permit to be supplied by General Contractor under General Building Permit. 1.05 SUBSTITUTIONS AND APPROVALS A. Some materials are specified by manufacturer's name. Materials of equivalent quality may be used if accepted by the Engineer and approved by the Owner. B. Bidder's Choice: Materials or equipment listed by several manufacturer's names are intended to be bidder's choice, and any of the listed manufacturers may be bid without soliciting prior approval. C. Contractor to be responsible for any changes and costs to accommodate any equipment except the first named in the specification. D. Substitutions for Material Equipment and materials not listed as equivalents may be proposed as alternates to specified items by submitting it as a separate line item to the base bid on the Bidder's letterhead. Alternates are encouraged for products recommended by Contractor that meet these specifications. Such alternate proposals shall not be substituted for the base bid and must be accompanied by full descriptive data on the proposed equipment, together with a statement of the cost to be deducted for each item. If any such alternates are considered, the Contractor shall submit a list of the proposed 5/7/14 Elk Meadows 15010-2 alternate substitution items within 14 days of award of contract. The request for proposed substitutions shall not be accepted by the Engineer due to scheduling or delivery concerns. 1.06 ROOF CURBS Roof curbs and roof flashings shall be furnished under the Architectural Division (except for any curbs specified herein). Furnish and install all counter flashings of the same material as the flashing. 1.07 FOUNDATIONS AND SUPPORTS Furnish and install all foundations, bases, hangers, anchors, guides and supports for mechanical equipment, piping and ducts. 1.08 INSTALLATION AND ARRANGEMENT Install all work to permit removal of coils, shafts and wheels, filters, and all other parts which might require periodic replacement of maintenance. Install all equipment per manufacturer's installation instructions and acceptable industry standards. 1.09 PROTECTION OF WORK AND PROPERTY Be responsible for the protection of existing facilities whether or not such facility is to be removed or relocated. Move or remove any facility so as not to cause interruption of the work or Owner's operation. 1.10 EXCAVATION AND BACKFILL Do all excavating and backfilling required by the work in this division. 1.11 CONCRETE All poured in place concrete shall be furnished under the Architectural Divisions of these Specifications. 1.12 MOTORS A. Squirrel cage type, open drip proof, normal starting torque, with thermal overload protection and ball bearings when available. B. Where commercially available, motors rated greater than 1000 watts shall have a power factor of at 85% under rated load. Where not commercially available, power factors shall be capacitor corrected by equipment manufacture to at least 90% under rated load. 5/7/14 Elk Meadows 15010-3 1.13 ACCESS DOORS Furnish access doors of type suitable to Developer and provide to General Contractor to construct into the building. Access doors should be provided in all locations where access is required. Access doors to be priced as line item for each proposed door. 1.14 IDENTIFICATION Main domestic cold water, main domestic hot water, all heating water zone valves, snowmelt zones, and all gas valves shall be identified by brass, plastic disc, or other permanent label accepted by Engineer. 1.15 ELECTRICAL EQUIPMENT AND WIRING FOR MECHANICAL DIVISION A. Unless otherwise indicated, all motors and controls shall be furnished, set in place and wired in accordance with the following schedule. (MD is Mechanical Division - ED is Electrical Division). Item Furnished under Set in place or mounted under Wired and connected under 1. Equipment motors and thermal overload, resistance heaters, line voltage tstats, etc. MD MD ED 2. Disconnect switches, fused or unfused, H.P. rated switches, thermal overload switches and fuses, manual operating switches (3) ED(1) ED(1) ED 3. Low voltage pushbutton stations, pilot lights, multi-speed switches, float switches, thermostats, control relays, control transformers, control panels, motor valves, damper motors, solenoid valves, and interlocks MD MD(2) MD(2) 5/7/14 Elk Meadows 15010-4 4. Contactors, 120V control circuit outlets for control panels and for boiler controls. ED ED ED 5. Fire and smoke detectors Alarm Co. Alarm Co. Alarm Co. 6. Site sprinklering control panels, solenoid valves, switches, etc. and all wiring starting at the distribution panel circuit breaker (see site sprinklering section) Landscaper Landscaper Landscaper (1) If furnished as part of factory wired equipment, wiring and connections only by ED (2) If float switches, line thermostats, time switches, etc., carry the FULL LOAD CURRENT to any motor, they shall be furnished by the Mechanical Division, but shall be set in place and connected under the Electrical division, except that where such items are no integral part of the mechanical equipment, or directly attached to ducts, piping, etc., they shall be set in place under the Mechanical Division and connected by the Electrical Division. If they do not carry the FULL LOAD CURRENT to any motor they shall be furnished, set in place and wired under the Mechanical Division. Control devices carrying full load current furnished Mechanical and wired by Electrical shall be located at the device being controlled, unless shown on drawings or mutual agreement is made between the contractors with no change in the contract price. (3) Wiring from alarm contacts to alarm system by ED; all control function wiring by MD. B. Connections to all controls directly attached to ducts, piping and mechanical equipment shall be made with flexible connectors. 1.16 FLUSHING AND CLEANING Before final connections are made in the piping systems, all piping shall be blown out with air and then washed out with cleaning compounds. Clean the boiler by the same procedure. 5/7/14 Elk Meadows 15010-5 1.17 TESTING A. Test all drain and waste lines with standing water test of twelve feet of head, held long enough to inspect each joint. B. Test all steam and water piping, before connecting to units, at 100 psig air pressure. C. Test all gas piping under 50 psig air pressure. D. All tests required by code must be done, to the satisfaction of the local authorities having jurisdiction, before covering. E. Test refrigeration piping with oil pumped, dry nitrogen at 150 psi and then evacuate, fill with refrigerant and test with Halide Torch or electronic leak detector. Evacuate and dry the system with dry nitrogen. F. All hydrostatic tests to be held for a minimum of six hours. Air tests to be held for a minimum of two hours. 1.18 BALANCING A. The balancing of the system shall be part of this contract, include in bid the cost of balancing and adjusting. B. Furnish and install such items as thermometer wells, pressure test cocks, access doors, etc., as required to allow tests and adjustments to be made. C. Adjust and balance all air and water systems. Check, adjust and balance all systems to meet the design conditions and tabulate all information on acceptable forms. All systems shall be checked for proper performance during design conditions, both heating and cooling. 1.19 OPERATING AND MAINTENANCE INSTRUCTIONS Deliver operating and maintenance instruction to the Owner on completion of the work and instruct Owner in their use. 1.20 WARRANTY A. All materials and equipment shall be new unless other-wise specified. Guarantee all workmanship, material and equipment and replace any found defective without cost to the Owner, for one year after final acceptance, as defined in General Conditions. B. Each warranty for longer than the one year described above (that comes with 5/7/14 Elk Meadows 15010-6 equipment used on the job) shall be passed onto the Owner with dates of start and end of warranty. 1.21 PROJECT RECORD DRAWINGS Contractor to provide the Developer with one clean set of final drawings. END OF SECTION 5/7/14 Elk Meadows 15250-1 SECTION 15250--INSULATION 1.01 PIPING AND EQUIPMENT A. Domestic Cold Water Pipe, Valves and Fittings. 1. All piping shall be insulated with flexible, closed-cell elastomeric insulation. Insulation shall have a flame spread index of less than 25 and a smoke-developed index of less than 50 when test in accordance with ASTM E 84, latest revision. Minimum R-Value of 3.0 for all piping. Insulation shall have a maximum water vapor transmission of 0.08 perm-inches when tested in accordance with ASTM E 96. Procedure A, latest revision. 2. All buried pipe and fittings (except water service from street to buildings) spiral wrapped with "Protecto Wrap" No. 200 coating or equivalent, 50% overlap. No insulation is required. B. Domestic Hot Water Pipe and Fittings 1. All hot water supply lines and circulating water lines insulated with with flexible, closed-cell elastomeric insulation. Insulation shall have a flame spread index of less than 25 and a smoke-developed index of less than 50 when test in accordance with ASTM E 84, latest revision. Minimum R-Value of 3.0 for all piping. Insulation shall have a maximum water vapor transmission of 0.08 perm-inches when tested in accordance with ASTM E 96. Procedure A, latest revision. 2. All buried pipe and fittings shall be insulated in the same manner, with 4-1/2 lb./cu.ft. insulation, spiral wrapped with "Protecto Wrap" No. 200 coating or equivalent, 50% overlap. C. Heating Piping; Heating Water, and Antifreeze Piping; Pipe, Valves and Fittings. 1. All piping shall be insulated with flexible, closed-cell elastomeric insulation. Insulation shall have a flame spread index of less than 25 and a smoke-developed index of less than 50 when test in accordance with ASTM E 84, latest revision. Minimum R-Value of 3.0 for all piping. Insulation shall have a maximum water vapor transmission of 0.08 perm-inches when tested in accordance with ASTM E 96. Procedure A, latest revision. 5/7/14 Elk Meadows 15250-2 D. Insulation for all types of piping shall be carried full size through the hangers. 1.02 DUCT INSULATION Inside Duct Liner - See Section 15800 - Ductwork. END OF SECTION 5/7/14 Elk Meadows 15400-1 SECTION 15400--PLUMBING 1.01 WATER PIPING A. Water Service 1. Water meter to be purchased by General Contractor, installed by Plumbing Contractor in accordance with the governing body's regulations. 2. All pipe outside the building: 3" and smaller Type "K" copper with wrought copper fittings and hard solder with a minimum melting point of 1100 degree F. 3. All pipe outside the building: 4" and larger ductile iron piping. 4. Piping outside the building shall have not less than eight feet of cover from finished grade. B. Piping (Inside Building) 1. Piping inside building; buried lines, type "K" copper water tube, wrought copper fittings and 1100 degree F solder. Non-buried lines, type "M" copper water tube, wrought copper fittings. All solder and fluxes shall have no lead content. Piping may also be cross-linked polyethylene (PEX) tubing manufactured to ASTM 876 and F877 standards, for Domestic Water Piping. Tubing shall be manufactured by Wirsbo or equal and installed per manufacturer’s installation instruction. 2. All buried pipe within the building insulated per Insulation Section and surrounded by 4" clean sand or clean on site tailings. All buried pipe outside the building surrounded by 4" clean sand or clean on site tailings. 3. Valves and Specialties Gate Valves: Bronze, Class 125, 200 lb. W.O.G. Globe Valves: Bronze, Class 125, 200 lb. W.O.G. Swing Check Valves: Bronze, Class 125, 200 lb. W.O.G. Dielectric Unions: Furnish and install a dielectric union at all connections where non-ferrous material Strainers: 250 lb. semi-steel or cast iron "Y" type with monel or brass screen Pressure Temp. Taps: Universal Controls Corporation #45-PT-N. Sisco BNO-500 1/2 NPT, Nordel Core 5/7/14 Elk Meadows 15400-2 1.02 SOIL, WASTE AND VENT PIPING A. General 1. Coordinate exact location of waste risers with Architect and General Contractor before installation. 2. Combine vent pipes as possible and penetrate roof on back side of home. Coordinate exact location with Architect and General Contractor before installation. B. Materials; Soil, Waste and Vent Piping (Inside Building) 1. Waste and vent lines for residential may be Schedule 40 ABS-DWV plastic pipe and fittings (ASTM D2661) or Schedule 40 PVC-DWV plastic pipe and fittings (ASTM D2665). All pipe and fittings shall bear NSF-DWV mark and shall be joined with solvent weld joints as recommended by the manufacturer. Provide Add alternate price to install Waste lines above ground; standard weight, C.I. soil pipe and fittings or hubless, C.I. soil pipe and fittings. Up through 2-1/2" may be standard weight, galvanized steel pipe with black, C.I. drainage fittings. 1.03 GAS PIPING A. General 1. Surround all buried pipe with 4" clean sand or on site tailings before backfilling. 2. Gas meter and service from the main to the meter will be furnished and installed by the utility company, paid for by the Owner. 3. Gas piping from the meter through the building will be done under this division and connected to all equipment required. B. Piping 1. Schedule 40 black steel pipe, 150 lb. malleable iron screwed fittings on above ground pipe, welded fittings with all piping coated and wrapped on buried pipe. CSST prohibited except for final connections to appliances only. 5/7/14 Elk Meadows 15400-3 C. Valves and appurtenances shall be of a type designed and approved for use with fuel gas. 1.04 FLASHINGS Provide roof flashings, to be installed by roofer. 1.05 CLEANOUTS Install full size brass cleanout plugs per local code requirements or otherwise required. Brass plugs with chrome plated cover plates for walls, flush with wall. When outside, heavy duty cast iron tractor cover set in two foot square by 6" deep concrete pad or in concrete or asphalt surface. "Y" in the line and vertical riser of C.I. pipe. 1.06 FIXTURES AND EQUIPMENT A. Fixtures 1. Install fixtures and/or rough-in according to the Architects fixture schedule. 2. Secure fixtures to walls and floor or countertops in accordance with manufacturer's roughing-in and setting requirements and form a rigid installation. 3. All pipe at the fixtures which may be exposed to view shall be brass chrome finish, finished with chrome escutcheons where they project from walls and floors. 4. Stop valves shall be furnished and installed at all fixtures, for all equipment and at rough-in locations. 5. Vacuum breakers shall be provided at all outlets with hose connections. END OF SECTION 5/7/14 Elk Meadows 15600-1 SECTION 15600--HEAT AND REFRIGERATION 1.01 PIPEWORK A. Piping 1. Valve all heating water piping with 3/4" hose end valve to permit drainage of the system. Vent all high points in equipment rooms as necessary with automatic air vents. All high points in system outside of equipment rooms with manual air vents as required to relieve air in the system. 2. All buried pipe to be insulated as per Insulation Section 15250. All buried pipe shall be surrounded by 4" clean sand or clean on site tailings. 3. Heating water piping shall be Type “M” copper in the mechanical room. All other piping can be cross-linked polyethylene (PEX) tubing with oxygen diffusion barrier manufactured to ASTM 876 and F877 standards, for Heating Water Piping. Tubing shall be manufactured by Wirsbo or equal and installed per manufacturer’s installation instruction. 4. Refrigeration Piping: Type "L", ACR grade copper, cleaned, dehydrated and capped at the factory. Use wrought copper fittings and hard solder having a minimum melting point of 1100 degrees for buried lines, 95-5 solder for non-buried lines. Valves and specialties shall be standard brass or bronze valves for refrigeration service. Buried pipe shall be surrounded by 4" clean sand or clean on site tailings. B. Valves and Specialities 1. Globe valves or plug valves may be used as balancing valves. 2. Dielectric unions are to be used at all connections where ferrous material is connected to buried non-ferrous material and where non-ferrous material is connected to domestic water piping. Gate Valves: Bronze screwed, Class 125 or iron body, bronze mounted, flanged, Class 125. Plug Valves: 175 lb. W.O.G. for 250 degrees F @ 150 psi W.P. Eccentric, tight shut-off with permanently lubricated stem bearing surfaces in upper and lower journals. DeZurik figure 435 or Homestead Series 1500. Flo-Control Valves: Bell & Gossett Flo Control, Taco Flo-Check or Hoffman Flo Control Valve. 5/7/14 Elk Meadows 15600-2 Balancing Valves: 125 psi W.P. for 250 degrees F service, tight shutoff, Illinois Dual Purpose Balancing/Shutoff Valve, Hoffman, Sarco, or equivalent. Unions: 300 psi W.O.G. malleable iron screwed or 125 lb. cast iron flanged unions. Strainers: 250 lb. semi-steel or cast iron "Y" type screwed, monel screen, 125 lb. semi-steel "Y" type flanged, brass screen. Pressure Temperature Taps: Universal Controls Corporation #45PT-N. Sisco ENO-500 1/2" NPT, Nordel Core. or 3. Copper Pipe Valves and Specialties. Ball valves, bronze, class 125, 200 lb. W.O.G. Gate Valves: Bronze, Class 125, 200 lb. W.O.G. Globe Valves: Bronze, Class 125, 200 lb. W.O.G. Check Valves: Bronze, Class 125, 200 lb. W.O.G. Balancing Valves: 125 psi W.P. for 250 degrees F service, tight shutoff, Illinois Dual Purpose Balancing/Shutoff Valve, Hoffman, Sarco or equivalent. 1.02 RADIANT FLOOR AND SNOWMELT PIPING A. General 1. Piping to be crosslinked polyethylene with an oxygen diffusion barrier as manufactured by Wirsbo, Roth, Rehau, Stadler, Heat link, Watts Radiant or Zurn. Piping shall have a minimum of 30 day UV light protection. 2. Piping shall be installed in continuous loops, no splices allowed. The maximum loop length allowable for radiant floor shall be 250' for 1/2" tubing and snowmelt shall be 300' for 5/8" tubing or larger. Longer lengths or different diameters of tubing are not allowable unless reviewed by the Engineer for each specific installation. 3. The Contractor shall install the tubing as recommended by the manufacturer and spaced to provide the required heat output. Tubing loops off each manifold shall be installed in equivalent lengths (5%). 4. The contractor shall install manifolds as provided by the tubing manufacturer. The manifolds shall consist of a return header (including: balancing valve for each loop and compression fitting to receive tubes) 5/7/14 Elk Meadows 15600-3 and supply header (including: manual shutoff valve for each loop and compression fitting to receive tubes). 5. Tube shall carry a twenty-five (25) year non-prorated warranty against failure due to defects in material and workmanship. 6. Snowmelt tubing which is not located in the snowmelt zone shall be insulated. END OF SECTION 5/7/14 Elk Meadows 15800-1 SECTION 15800--AIR DISTRIBUTION 1.01 MATERIALS AND EQUIPMENT A. General 1. Sizes shown on the drawings shall be outside (sheet metal) duct dimensions. Ductwork shall be sheetmetal furnished and installed in accordance with SMACNA Low Velocity Duct Manual AIA File No. 30- D4. 2. All ductwork to be galvanized steel. 3. All return paths shall be ducted. Panning of the structure is not allowable. 4. All ductwork seams and joints shall be sealed with mastic. Duct tape is not allowable. 5. All ductwork which is visible behind a grille, register or diffuser shall be painted flat black. B. Acceptable Manufacturer 1. Low velocity flexible ducts: acoustically insulated consisting of inner core of perforated one ply corrugated duct, 1" thick insulation, and vapor barrier cover. The flexible duct must be approved by the code authority for the specific application. 2. Round duct connectors: Factory fabricated galvanized for insulated ducts, steel adaptor plate on glass fiber ducts. Butterfly damper and quadrant operator on all applications except VAV systems upstream of VAV boxes. 3. Flexible connections. 24 oz. per yard, U.L. approved material. 4. Turning Vanes (Provide in all rectangular elbows). 5. Opposed Blade Dampers (for duct split and where specified). a. Steel or aluminum construction with work driver operator. Screwdriver slotted shaft, factory assembled. b. Sizes up through 36" x 12": Barber Colman AOOG, T & B 7s, Titus AG-35B, Krueger OBD-DM, Anemostat OB4, Carnes 800, Agitair OB, J & J OBD-DM, or equivalent. 5/7/14 Elk Meadows 15800-2 c. Sizes larger than 36" x 12": Multi-damper with external handle and quadrant type locking device Quadrant Regulator. Blades not to exceed 6" in width. 6. Volume Extractors. a. Steel or aluminum construction with vanes on 2" centers, gauge operated. Manual operator attached to branch duct. Carnes 1250, Titus AG-ss5, T & B VLR, Anemostat DT2M, Krueger EX-88A, Agitair, Branchtrol S-2, J & J EX 9, Millaire Ex-1 or equivalent. 7. Duct Liner (Inside the Duct for Rectangular Ducts). a. Insulate all supply ducts and return ducts with 1/2" thick AP Armaflex SA Black Duct Liner. Liner shall be non-fibrous, closed cell foam, made with Microban antimicrobial protection. Outside air intake ducts shall have 1” thick insulation with an R-value of 4.2 minimum. 8. Duct Wrap (Round Rigid Ducts and Unlined Rectangular Ducts). a. Insulate with 2" thick, 0.75 pcf density, thermal insulation blanket. Knauf or equivalent. END OF SECTION 5/7/14 Lot 1 Elk Meadows 15900-1 SECTION 15900--CONTROLS AND INSTRUMENTATION 1.01 DESCRIPTION A. The Temperature Control System: Electric and electronic to comprise a complete system, furnished and supervised by the Temperature Control Manufacturer. The control system shall be able to be remotely changed from an occupied to an unoccupied state. B. Wiring - General 1. Comply with the National Electric Code, and the Electrical Division of these specifications. 2. Run wiring in metallic conduit, tubing or raceways. Exceptions: a. NEC class 2 low voltage wiring where not exposed to view such as above suspended ceiling in shafts, etc., may be run in cable. (Not allowable above ceilings used as return air plenums). b. Wiring enclosed in Temperature Control panels. 3. Low volt sensor wires to be either shielded or twisted pairs. C. Wiring: One Contractor shall be solely responsible for all temperature control wiring. All wiring and installation in connection with the automatic control system to be the responsibility of the Mechanical Division, supervised by the Control Manufacturer or his representative. Upon completion of the installation the control manufacturer or his representative shall link all valves and dampers and check out the wiring and calibrate controls furnished under this section. D. Control Settings: All control settings are tentative, equipment shall have adjustable settings. 1.02 ACCEPTABLE MANUFACTURERS A. This specification is based on Honeywell equipment. It is recognized that packaged equipment comes with other names on controls and that some functions are accomplished with other named components. This specification does not intend to prohibit this practice. 5/7/14 Lot 1 Elk Meadows 15900-2 1.03 MATERIALS AND EQUIPMENT A. Low Voltage Power 1. Control devices and panel containing low voltage power sources shall comply with NEC Class 2 requirements (current limiting), or supplied with branch circuit fusing to limit control circuit current to NEC Class 2. Control transformers; of the current limiting type, or installed with primary disconnect and overload protection. B. Thermostats 1. All thermostats shall have a temperature range suitable for the application and have adjustable set points. The thermostats shall be able to display temperature setpoint and room temperature. All thermostats shall be approved by the owner. C. Dampers: Pacific Series 210, Johnson "Proportion-Air", Honeywell "Moduflow Low Leakage", Ruskin"CD250 Low Leakage Penn Air Control Damper PBD or OBD or equivalent. D. Valves 1. Valves in water and antifreeze system shall be sized for not more than 3 feet of pressure drop. E. Freeze Detection Thermostats. Each supply system with water coils taking outside air shall have a freeze detection thermostat located on the downstream side of the coil. Thermostats shall be of adjustable electric contact type, silver plated, manual reset with 20' flexible sensing bulb of increment type with any section capable of actuating mechanism on temperature drop below set point, thermostat shall stop fan(s) and closed outside air damper. They shall have an isolated set of contacts for alarm system. END OF SECTION END OF DIVISION HEAT LOSS / HEAT GAIN SUMMARYJOB NAME: Elk MeadowsJOB NUMBER: 14037DATE: 5/7/2014CALCS BY: DRC(USER SHALL INPUT YELLOW CELLS)SITE ELEVATION = 8150 Wall Insulation (avg) R- 23.5TRANSFER FACTOR = 0.79 Roof Insulation (avg) R- 58.6COOLING AIRFLOW ΔT =20 Infiltration (nach) 0.3WINDOW VALUES (U, S.C.) 0.32, 0.46 Winter Design Temp (indoor/ outdoor) 70 / -20LIGHTING LOAD (W/S.F.) 1, 3 Summer Design Temp (indoor/ outdoor) 75 / 90ROOM FLOOR AREA EFFECTIVE(SF) AREA (SF) SENS LATENT TOTAL BTU/H BTU/SF101-Garage 648 600 3700 0 3700 11300 19103-Mud 201 176 800 0 800 2800 16105-Entry 248 206 5300 0 5300 6200 30109-Bed 1 233 221 2900 100 3000 3900 18110-Bath 1 55 31 600 0 600 200 6112-Family 275 275 5500 700 6200 5800 21113-Bed 2 236 224 2600 102 2702 3800 17115-Bath 2 69 39 800 0 800 1100 28116-Laundry 46 28 1200 0 1200 200 7202-Powder 38 29 500 0 500 200 7203-Bath 3 59 32 800 0 800 700 22205-Bed 3 224 208 2400 150 2550 3100 15206-Master Bath 154 70 2700 0 2700 2000 29207-Master Bed 270 270 4800 250 5050 5700 21209-Master Closet 92 53 700 0 700 1400 26212-Kitchen, Living 662 562 18900 350 19250 13500 24215-Dining 228 228 6200 800 7000 5600 25217-Den 188 180 3300 100 3400 3900 22TOTALS / AVG'S.3926 63700 2552 66252 71400 18LOT 3COOLING HEATING