HomeMy WebLinkAboutNORTHSIDE GRAB N GO Test & Balance Report.pdf TEST, ADJUST AND BALANCE REPORT
PROJECT
NORTHSIDE GRAB-N-GO
#1112
PREPARED FOR
SKYLINE MECHANICAL
REPORT ISSUE DATE
11/11/2014
PREPARED BY
HVAC TAB llc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB llc
DATE: 11/11/2014
INSTRUMENT
CALIBRATION REPORT
PROJECT : NORTHSIDE GRAB N GO PROJECT ALTITUDE: 22.2 “HG
INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE
SHORTRIDGE ADM-870C / #M09211 AIR FLOW READINGS 11/11/2014 06/12/2014 06/012/2015
ANEMOMETER #RVA501416001 AIR FLOW READINGS 11/11/2014 04/14/2014 04/14/2015
SHORTRIDGE FLOW HOOD AIF FLOW READINGS 11/11/2014 * *
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/04/2014 06/04/2015
PITOT TUBE 18” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 48” PRES. READINGS NOT USED NA NA
SHIMPO TACHOMETER / #C105B0010 RPM READINGS 11/11/2014 06/18/2014 06/18/2015
FLUKE 375 / #21290229 VOLT / AMP 11/11/2014 06/04/2014 06/04/2015
SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS NOT USED 06/12/2014 06/12/2015
ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * *
FLUKE 52-II #99780167 TEMP. READINGS NOT USED 02/3/2014 02/3/2015
REFRACTOMETER RHA-100 / #RHA-
100
GLYCOL % READINGS NOT USED N/A N/A
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE:
NOTES:
HVAC TAB llc
DATE: 11/11/2014
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER CAPTIVE AIRE
MODEL A1-D-250-G10
SERIAL JOB#2070017
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1825CFM@0.55"ESP
MIN OSA CFM 100%
MOTOR NAMEPLATE DATA
MANUFACTURER WEG
HP R.P.M. 1.50 1745
PHASE FRAME 3 58 H
S.F. TYPE 1.15 -
VOLTS AMPS 208/230/460 5.09/4.60/2.30
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VL 40
MOTOR BORE 5/8"
FAN DRIVE 1 AK 46
FAN BORE 3/4"
NO. BELTS & SIZE 1 / AX 37
ROTATION CORRECT
CENTERLINE 13 3/8" MOTOR ADJ + 1 1/2 - 2
PULLEY
SPEED + 2 1/2 TURNS
STARTER DATA
MANUFACTURER ABB
MODEL 193 K
SIZE/THERMAL NO. -
RANGE (AMPS) 3.5 - 4.8
SET AT (AMPS) 4.8
REQ. THERMAL -
RATING (AMPS) -
TEST DATA INITIAL FINAL
FAN R.P.M. 1262 1262
VOLTAGE 214/214/212 214/214/212
AMPERAGE 3.8/3.4/3.4 3.8/3.4/3.4
PAGE:
AIRFLOW DATA
SUPPLY CFM 1953
OSA CFM 1953
PROJECT: NORTHSIDE GRAB N GO SYSTEM: MUA-1
F I
L T
E R
-0.27" 0.00" -0.88"
H
X
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
MUA-1 1 PF 87/12 1000 1140 1160 NO DAMPER
FOUND
2 SR 17/5 400 544 415
3 CD 24/24 213 128 191 NO DAMPER FOUND
4 CD 24/24 213 114 187 NO DAMPER
FOUND
1826 1926 1953 TOTAL
FC-1 1 CD 22/22 - 865 865
2 CD 22/22 - 595 595
- 1460 1460 TOTAL
FC-2 1 CD 22/22 - 810 810
2 CD 22/22 - 362 362
- 1172 1172 TOTAL
EF-1 1 ER 9/9 100 138 138 TOTAL
EF-2 1 ER 10/10 290 390 390 TOTAL
NOTES:
HVAC TAB llc
DATE: 11/11/2014
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: NORTHSIDE GRAB N GO SYSTEM: MUA-1 / FC-1 / FC-2 / EF-1 / EF-2
HVAC TAB llc
DATE: 11/11/2014
FAN NUMBER KEF-1 NOT USED
UNIT DATA UNIT DATA UNIT DATA
MANUFACTURER CAPTIVE AIRE
MODEL NCA14HPFA
SERIAL JOB# 2070017
SCHEDULE RATING/OUTLET TOTAL 1625CFM
MOTOR DATA MOTOR DATA MOTOR DATA
MANUFACTURER WEG -
MOTOR HP RPM 3/4 1735
PHASE FRAME 3 E 56
S.F. TYPE 1.15 -
VOLTS AMPS 208/230/460 2.65/2.66/1.33
DRIVE DATA DRIVE DATA DRIVE DATA
MOTOR DRIVE BORE 1 AK 39 3/4"
FAN DRIVE BORE 1 VL 40 5/8"
NO. BELTS SIZE 1 AX 20
DRIVE CHANGE ROTATION +0 TURNS/+1
1/2-1 1/2 CORRECT
STARTER DATA STARTER DATA STARTER DATA
MFG. MODEL ABB 193 K
RANGE SET AT (AMPS) 2.3 - 3.2 2.8 AMPS
SET AT HERTZ REQ. THERM - -
THERMAL PROTECTION - -
TEST DATA TEST DATA TEST DATA
CFM VOLTS 1615 215/214/213
FAN RPM AMPS 1714 2.6/2.8/2.6
FAN TEST REPORT
PROJECT: NORTHSIDE GRAB N GO SYSTEM: KEF-1
PAGE:
NOTES: