Loading...
HomeMy WebLinkAboutNORTHSIDE GRAB N GO Test & Balance Report.pdf TEST, ADJUST AND BALANCE REPORT PROJECT NORTHSIDE GRAB-N-GO #1112 PREPARED FOR SKYLINE MECHANICAL REPORT ISSUE DATE 11/11/2014 PREPARED BY HVAC TAB llc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB llc DATE: 11/11/2014 INSTRUMENT CALIBRATION REPORT PROJECT : NORTHSIDE GRAB N GO PROJECT ALTITUDE: 22.2 “HG INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE SHORTRIDGE ADM-870C / #M09211 AIR FLOW READINGS 11/11/2014 06/12/2014 06/012/2015 ANEMOMETER #RVA501416001 AIR FLOW READINGS 11/11/2014 04/14/2014 04/14/2015 SHORTRIDGE FLOW HOOD AIF FLOW READINGS 11/11/2014 * * TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/04/2014 06/04/2015 PITOT TUBE 18” PRES. READINGS NOT USED N/A N/A PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A PITOT TUBE 48” PRES. READINGS NOT USED NA NA SHIMPO TACHOMETER / #C105B0010 RPM READINGS 11/11/2014 06/18/2014 06/18/2015 FLUKE 375 / #21290229 VOLT / AMP 11/11/2014 06/04/2014 06/04/2015 SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS NOT USED 06/12/2014 06/12/2015 ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * * FLUKE 52-II #99780167 TEMP. READINGS NOT USED 02/3/2014 02/3/2015 REFRACTOMETER RHA-100 / #RHA- 100 GLYCOL % READINGS NOT USED N/A N/A * CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: NOTES: HVAC TAB llc DATE: 11/11/2014 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER CAPTIVE AIRE MODEL A1-D-250-G10 SERIAL JOB#2070017 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1825CFM@0.55"ESP MIN OSA CFM 100% MOTOR NAMEPLATE DATA MANUFACTURER WEG HP R.P.M. 1.50 1745 PHASE FRAME 3 58 H S.F. TYPE 1.15 - VOLTS AMPS 208/230/460 5.09/4.60/2.30 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VL 40 MOTOR BORE 5/8" FAN DRIVE 1 AK 46 FAN BORE 3/4" NO. BELTS & SIZE 1 / AX 37 ROTATION CORRECT CENTERLINE 13 3/8" MOTOR ADJ + 1 1/2 - 2 PULLEY SPEED + 2 1/2 TURNS STARTER DATA MANUFACTURER ABB MODEL 193 K SIZE/THERMAL NO. - RANGE (AMPS) 3.5 - 4.8 SET AT (AMPS) 4.8 REQ. THERMAL - RATING (AMPS) - TEST DATA INITIAL FINAL FAN R.P.M. 1262 1262 VOLTAGE 214/214/212 214/214/212 AMPERAGE 3.8/3.4/3.4 3.8/3.4/3.4 PAGE: AIRFLOW DATA SUPPLY CFM 1953 OSA CFM 1953 PROJECT: NORTHSIDE GRAB N GO SYSTEM: MUA-1 F I L T E R -0.27" 0.00" -0.88" H X SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM MUA-1 1 PF 87/12 1000 1140 1160 NO DAMPER FOUND 2 SR 17/5 400 544 415 3 CD 24/24 213 128 191 NO DAMPER FOUND 4 CD 24/24 213 114 187 NO DAMPER FOUND 1826 1926 1953 TOTAL FC-1 1 CD 22/22 - 865 865 2 CD 22/22 - 595 595 - 1460 1460 TOTAL FC-2 1 CD 22/22 - 810 810 2 CD 22/22 - 362 362 - 1172 1172 TOTAL EF-1 1 ER 9/9 100 138 138 TOTAL EF-2 1 ER 10/10 290 390 390 TOTAL NOTES: HVAC TAB llc DATE: 11/11/2014 AIR TERMINAL TEST REPORT PAGE: PROJECT: NORTHSIDE GRAB N GO SYSTEM: MUA-1 / FC-1 / FC-2 / EF-1 / EF-2 HVAC TAB llc DATE: 11/11/2014 FAN NUMBER KEF-1 NOT USED UNIT DATA UNIT DATA UNIT DATA MANUFACTURER CAPTIVE AIRE MODEL NCA14HPFA SERIAL JOB# 2070017 SCHEDULE RATING/OUTLET TOTAL 1625CFM MOTOR DATA MOTOR DATA MOTOR DATA MANUFACTURER WEG - MOTOR HP RPM 3/4 1735 PHASE FRAME 3 E 56 S.F. TYPE 1.15 - VOLTS AMPS 208/230/460 2.65/2.66/1.33 DRIVE DATA DRIVE DATA DRIVE DATA MOTOR DRIVE BORE 1 AK 39 3/4" FAN DRIVE BORE 1 VL 40 5/8" NO. BELTS SIZE 1 AX 20 DRIVE CHANGE ROTATION +0 TURNS/+1 1/2-1 1/2 CORRECT STARTER DATA STARTER DATA STARTER DATA MFG. MODEL ABB 193 K RANGE SET AT (AMPS) 2.3 - 3.2 2.8 AMPS SET AT HERTZ REQ. THERM - - THERMAL PROTECTION - - TEST DATA TEST DATA TEST DATA CFM VOLTS 1615 215/214/213 FAN RPM AMPS 1714 2.6/2.8/2.6 FAN TEST REPORT PROJECT: NORTHSIDE GRAB N GO SYSTEM: KEF-1 PAGE: NOTES: