Loading...
HomeMy WebLinkAboutBegin_Workflow - Review Comments - 09-15-2014_13-25-15.pdfBegin_Workflow ­ Review Comments ­ 09­15­2014_13­25­15 Review Cycle Department Markup Snapshot 1 Building File: B14­0246 REV1 gas schematic.pdf ChangeMark: mhaeberle Description: B001 Comment: provide a complete gas piping plan showing compliance with section 402.3 IFGC 2012 edition 1 Building File: B14­0246 REV1 gas schematic.pdf ChangeMark: mhaeberle Description: B002 Comment: How is this protected? See CSST manufactures installtion requirements.