HomeMy WebLinkAboutB14-0254 REV4 balance report.PDFENGINEERING,INC.1833 MTN.VIEW RD.,SEDALIA CO (303)688-9044 GENERAL INFORMATION PROJECT VAIL VILLAGE WELCOME CENTER LOCATION VAIL, COLORADO ELEVATION 9200' ARCHITECT GPSL MECH. ENG.M-TECH GROUP CONTRACTOR M-TECH GROUP BAL. CREW JP GRIFFITH DATE NOVEMBER 2014 JPG JOB #3301 INSTRUMENTS USED CALIBRATION DATE: Jan 28, 2014 AMPMETER/VOLTMETER FLuke 324 4152637 ANEMOMETER Davis A/2 Ball Brg. JPG-17 PRESSURE GAGE-DIFFER FLO-DESIGN 12C1386 0-300" JPG-1 SPEED INDICATOR Biddle 9920 786293 VELOMETER Shortridge ADM-860 M89784 METHOD OF BALANCE Supply Diffusers are read with a capture hood using a Shortridge Air Data Meter. Exhaust and return inlet registers read with Shortridge Air Data Meter and Flow Hood. Zone ductwork was pitoted for total flow using a Shortridge Airdata Meter with pitot tube. Item Sheet Number Cover Page..................................................................................................................................................1 Table of Contents........................................................................................................................................2 Equipment(Air) - MZ-1..............................................................................................................................3 Air Balance - MZ-1 / MZ-1........................................................................................................................4 Air Balance - MZ-1 / ZONE 1....................................................................................................................4 Air Balance - MZ-1 / ZONE 5....................................................................................................................4 Air Balance - MZ-1 / ZONE 6....................................................................................................................5 Equipment(Air) - EF-1................................................................................................................................6 Equipment(Air) - EF-2................................................................................................................................7 TABLE OF CONTENTS Page 2 of 7 EQUIPMENT INFORMATION UNIT #MZ-1 MAKE McQUAY MODEL #LML111EH SERIAL #970392-010 RATING MOTOR DATA MAKE CENTURY H.P.7.5 PF/EFF 82.5 / 88.5 TYPE SCE PH.3 RATED SPEED 1755 MEAS. VOLTS 460/460/460 SF.1.15 RATED VOLTS 230/460 MEAS. AMPS 7.5/6.8/7.2 FR.S213T RATED AMPS 19.2/9.6 STARTER DATA MAKE S&S MODEL SIZE ENCLOSURE CLASS THERMALS SET @ 10.0 AMPS (EXISTING) AMP RATING THERMALS (REQUIRED) AMP RATING OTHER DRIVE DATA DRIVEN SHEAVE 2BK52H BORE H X 1-7/16'' DRIVER SHEAVE 2VP75 BORE 1-3/8'' BELT SIZE BX75 NO. BELTS 2 TURNS TO MAX MOTOR ADJUST-INCHES DRIVE CHANGE BELT CHANGE INITIAL/FINAL RPM 2515 / 2515 FINAL AMPS 7.5/6.8/7.2 PRESSURE INFORMATION FILTER IN -0.22"OUT -0.24"DROP 0.02 " FAN IN -0.24"OUT 1.96"RISE 2.20 " HTG. COIL IN 1.96"OUT 1.42"DROP 0.54 " CLG COIL IN 1.96"OUT 1.96"RISE 0.00 " Remarks:FINALLED WITH ALL ZONES ON FULL HEATING MODE EQUIPMENT DATA PROJECT VAIL VILLAGE WELCOME CENTER Page 3 of 7 MZ-1 ZONE 1 18X10 18X10 0.9 778 700 1070 963 ZONE 2 18X10 18X10 0.9 833 750 1160 1044 ZONE 3 14X10 14X10 0.67 1119 750 1210 811 ZONE 4 28X8 28X8 1.08 1481 1600 1494 1614 ZONE 5 18X18 18X18 1.78 730 1300 802 1428 ZONE 6 20X10 20X10 1.0 1050 1050 1205 1205 TOTAL 6150 7065 ZONE 1 1 1.0 150 150 234 234 2 1.0 150 150 74 74 3 1.0 200 200 265 265 4 1.0 200 200 204 204 5 NOT SHOWN 1.0 NG 194 194 TOTAL 700 971 ZONE 5 1 1.0 300 300 174 174 NO ACCESS TO DAMPER AIR BALANCE DATA PROJECT VAIL VILLAGE WELCOME CENTER SYSTEM MZ-1 LOCATION OPENING SIZE REQUIRED FINAL MINIMUM HEATING PLAN ACTUAL AREA VEL CFM VEL CFM VEL CFM VEL CFM Page 4 of 7 ZONE 5 2 1.0 300 300 332 332 3 1.0 300 300 382 382 4 1.0 250 250 273 273 5 1.0 150 150 235 235 TOTAL 1300 1396 ZONE 6 1 1.0 300 300 248 248 2 1.0 300 300 272 272 3 1.0 300 300 369 369 4 1.0 150 150 308 308 TOTAL 1050 1197 AIR BALANCE DATA PROJECT VAIL VILLAGE WELCOME CENTER SYSTEM MZ-1 LOCATION OPENING SIZE REQUIRED FINAL MINIMUM HEATING PLAN ACTUAL AREA VEL CFM VEL CFM VEL CFM VEL CFM Page 5 of 7 EQUIPMENT INFORMATION UNIT #EF-1 MAKE GREENHECK MODEL #SP-A410 SERIAL # RATING 250 CFM MOTOR DATA MAKE McMILLAN H.P.1/19 PF/EFF / TYPE PH.1 RATED SPEED 1100 MEAS. VOLTS 120 SF.RATED VOLTS 115 MEAS. AMPS 1.4 FR.RATED AMPS 1.7 STARTER DATA MAKE NONE MODEL SIZE ENCLOSURE CLASS THERMALS (EXISTING) AMP RATING THERMALS (REQUIRED) AMP RATING OTHER BUILT IN OVERLOAD DRIVE DATA DRIVEN SHEAVE DIRECT DRIVE BORE DRIVER SHEAVE BORE BELT SIZE NO. BELTS TURNS TO MAX MOTOR ADJUST-INCHES DRIVE CHANGE BELT CHANGE INITIAL/FINAL RPM /FINAL AMPS 1.4 PRESSURE INFORMATION FAN IN ATM"OUT NAC"- " Remarks:REQ'D = 250 CFM FINAL = 350 CFM EQUIPMENT DATA PROJECT VAIL VILLAGE WELCOME CENTER Page 6 of 7 EQUIPMENT INFORMATION UNIT #EF-2 MAKE GREENHECK MODEL #SP-A410 SERIAL # RATING 250 CFM MOTOR DATA MAKE McMILLAN H.P.1/19 PF/EFF / TYPE PH.1 RATED SPEED 1100 MEAS. VOLTS 120 SF.RATED VOLTS 115 MEAS. AMPS 1.4 FR.RATED AMPS 1.7 STARTER DATA MAKE NONE MODEL SIZE ENCLOSURE CLASS THERMALS (EXISTING) AMP RATING THERMALS (REQUIRED) AMP RATING OTHER BUILT IN OVERLOAD DRIVE DATA DRIVEN SHEAVE DIRECT DRIVE BORE DRIVER SHEAVE BORE BELT SIZE NO. BELTS TURNS TO MAX MOTOR ADJUST-INCHES DRIVE CHANGE BELT CHANGE INITIAL/FINAL RPM /FINAL AMPS 1.4 PRESSURE INFORMATION FAN IN ATM"OUT NAC"- " Remarks:REQ'D = 250 CFM FINAL = 341 CFM EQUIPMENT DATA PROJECT VAIL VILLAGE WELCOME CENTER Page 7 of 7