HomeMy WebLinkAboutBP14-0254 Firetex FX5120 Revised 091514.pdf09/24/14
Revised: April 29, 2014
FIRETEX FX5120
WATERBASED INTUMESCENT
COATING
B59W5120 WhITE
Protective
&
Marine
Coatings
www.sherwin-williams.com/protective
Product descriPtion
Firetex Fx5120 is a waterbased thin-film intumescent fire protec-
tion coating for use on interior exposed structural steel substrates.
Its smooth paint-like finish allows architects to design using exposed
steel for a decorative and aesthetic final appearance.
• Provides up to 2 hours fire protection in accordance with UL
263 (ASTM E-119) and CAN/ULC-S101
• Single component
• Aesthetic finish
• Impact resistant
• Low odor, low VOC
• Outstanding application characteristics
Product characteristics
Finish: Flat
Color: White
Volume Solids: 69%
Weight Solids: 71%
VOC: <4 g/L ; 0.03 lb/gal
Note: Product is designed for spray and brush application
recommended Spreading rate per coat:
Airless Spray Brush
Wet mils (microns) 56.0 (1400) 18.0 (441)
Dry mils (microns) 40.0 (1000) 12.0 (300)
~Coverage sq ft/gal (m2/L) 28 (0.7) 92 (2.3)
Theoretical coverage sq ft/gal
(m2/L) @ 1 mil / 25 microns dft 1104 (27.1)
Maximum sag tolerance typically 72.0 mils (1800 microns) wet by
airless spray.
Drying Schedule:
@ 60°F/15°C @ 73°F/23°C
to touch: 5 hours 3 hours
to handle*:
to recoat: 24 hours 6 hours
*This will depend on the total thickness of FIRETEX FX5120 to be
applied. No more than 2 coats by airless spray should be applied
within any 24 hour period.
Drying time is temperature, humidity, and film thickness dependent.
Shelf Life: 10 months, unopened
Store indoors at 40°F (4.5°C) to
100°F (38°C).
reducer/Clean Up: Water
continued on back
recommended uses
• For use on exposed structural steel that requires an aesthetic
finish
• Commercial buildings
• Healthcare / Hospitals
• Hotels
• Educational buildings
• Stadiums
• Iconic structures
• Public buildings
• Airports
• Atriums
• Warehouses
• School gymnasiums
• Convention centers
aPProvals
• Provides Up To 2 Hours Fire Protection in Accordance With UL
263 (ASTM E-119) and CAN/ULC-S101
• UL D981 Beam Design
• UL N636 Beam Design
• UL Y623 Column Design
• UL Y624 Tube Column Design
Performance characteristics
test Name test Method results
Abrasion resistance ASTM D4060 290 mg loss
Adhesion ASTM D4541-09 540 psi
Durometer Hardness ASTM D2240-05 Shore D - 70
impact resistance ASTM D2794-93 104 in. lbs.
Surface Burning ASTM E84
Class A
Flame Spread - 0
Smoke Developed - 5
aPPlication equiPment
The following is a guide. Changes in pressures and tip sizes may
be needed for proper spray characteristics. Always purge spray
equipment before use with listed reducer. Any reduction must be
compliant with existing VOC regulations and compatible with the
existing environmental and application conditions.
Airless Spray
Nozzle Size: ......................19-23 (depending on application
requirements)
Operating Pressure: ..........2500 psi (175 kg/cm²)
Use 3/8” ID fluid line where lengths in excess of 10 feet are
required. In-line gun or pump filters should not normally be used.
Brush
The material is suitable for brush application but due to the
nature of the material a ribbed appearance will result.
Application of more than one coat may be necessary to give
equivalent dry film thickness to a single spray applied coat.
09/24/14
Revised: April 29, 2014
FIRETEX FX5120
WATERBASED INTUMESCENT
COATING
B59W5120 WhITE
Protective
&
Marine
Coatings
www.sherwin-williams.com/protective
surface PreParation
Surface must be clean, dry, and in sound condition. Remove all oil,
dust, grease, dirt, loose rust, and other foreign material to ensure
adequate adhesion.
aPPlication conditions
Firetex Fx5120 must be applied in a dry internal environ-
ment. it must not be exposed to condensation, damp or wet
conditions during or after application.
In conditions of high relative humidity good ventilation conditions
are essential. Substrate temperature should be at least 5°F (3°C)
above the dew point.
At application temperatures below 50°F (10°C), drying times
will be significantly extended, and spraying characteristics
may be impaired.
A minimum air and substrate temperature of 40°F (5°C) is
required to ensure proper film formation.
relative humidity should not exceed 80% to ensure proper
film formation.
extended overcoating times may be required at low tempera-
tures and/or high film thicknesses.
Occasionally cracking may occur on edges of flanges and external
or internal angles of structural steel, depending on geometry, over-
application and ambient conditions. This does not detrimentally
affect the fire performance properties of the product.
ordering information
Packaging: 5 gallon (20L) containers
Weight: 11.6 lb/gal ; 1.39 Kg/L
disclaimer
The information and recommendations set forth in this Product Data Sheet
are based upon tests conducted by or on behalf of The Sherwin-Williams
Company. Such information and recommendations set forth herein are subject
to change and pertain to the product offered at the time of publication. Consult
your Sherwin-Williams representative to obtain the most recent Product Data
Information and Application Bulletin.
Warranty
The Sherwin-Williams Company warrants our products to be free of manufactur-
ing defects in accord with applicable Sherwin-Williams quality control procedures.
Liability for products proven defective, if any, is limited to replacement of the defec-
tive product or the refund of the purchase price paid for the defective product as
determined by Sherwin-Williams. NO OTHER WARRANTY OR GUARANTEE
OF ANY KIND IS MADE BY SHERWIN-WILLIAMS, EXPRESSED OR IMPLIED,
STATUTORY, BY OPERATION OF LAW OR OTHERWISE, INCLUDING MER-
CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
PRODUCT INFORMATION
recommended Primers
Must be primed with approved primer.
Approved Primers:
Kem Bond HS
Kem Kromik Universal Primer
Macropoxy 646
Pro Industrial ProCryl Universal Primer
Recoatable Epoxy Primer
Contact your Sherwin-Williams Representative for specific
products.
recommended toPcoats
Approved Topcoats:
DTM Acrylic
Duration Home
EcoSelect
Emerald
Harmony
Hi-Solids Polyurethane
Macropoxy 646
Metalatex
Pro Industrial Precatalyzed Epoxy
Pro Industrial Zero VOC Acrylic
Pro Mar 200 Zero VOC
Pro Mar 400 Zero VOC
ProIndustrial HB WB Epoxy
Solo
Superpaint Interior
Waterbased Acrolon 100
Waterbased Catalyzed Epoxy
Contact your Sherwin-Williams Representative for specific
products.
A topcoat is not UL/ULC required for Interior Conditioned Space
(ICS) areas.
additional notes
The dry time of this material is retarded by high humidity condi-
tions. Lack of air movement also slows down the drying process,
and under such conditions it is advisable to introduce some
method of circulating air over the coated surface in order to
speed up the drying. A ventilated air speed of 6 feet per second
is recommended.
clean uP instructions
Clean spills and spatters immediately with Water. Clean tools
immediately after use with Water. Follow manufacturer's safety
recommendations when using any solvent.
safety Precautions
Refer to the MSDS sheet before use.
Published technical data and instructions are subject to change without notice.
Contact your Sherwin-Williams representative for additional technical data and
instructions.
09/24/14