HomeMy WebLinkAboutE200.pdfBREAKER WILL BE INSTALLED IN PLACE OF
RELOCATED CIRCUITS TO THE MAIN FLOOR AREA.
30-DAY METER SHALL BE PROGRAMMED TO COMPLY
WITH NEC 220.87.
1
FLAG NOTES:
1. EXISTING CONDITIONS ARE SHOWN FOR
INFORMATION ONLY. VERIFY ALL EXISTING
CONDITIONS PRIOR TO PERFORMING ANY
WORK.
NOTES:
MAIN LEVEL
LOWER LEVEL
(E) PANEL 'LP4'
480Y/277V,
3-PHASE, 225A
T
(E) TRANSFORMER
75KVA, 480Y/277V
PRIMARY, 208Y/120V
SECONDARY
(E) PANEL 'SP5-LEFT'
208Y/120V, 3-PHASE,
225A
(E) PANEL
'SP5-RIGHT'
208Y/120V,
3-PHASE, 150A
M
TEMPORARY 30 DAY
METER
(N) PANEL 'SP6'
208Y/120V,
3-PHASE, 125A
125/3
1
2
2 (3#1 & 1#6G) 1 1/4"C
SCALE: 1 ONE-LINE DIAGRAM
NOT TO SCALE
PANEL: SP6
VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 125
LOCATION: FOURTH FLOOR STORAGE MAIN: MLO
MOUNTING: RECESSED MINIMUM AIC: 10,000
NO.
LOAD
TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD
NO.
A B C POLE TRIP A B C TRIP POLE A B C
1 225 L NEW ADD. LIGHTING 20 1 + 20 1 M EF-1 WOMENS 121 2
3 1260 R NORTH ADD. RECEP. 20 1 + 20 1 M RHP-1 WOMENS 750 4
5 1080 R SOUTH ADD. RECEP. 20 1 + 20 1 M EF-1 MENS 121 6
7 1400 E MENS HAND DRYER 20 1 + 20 1 M RHP-1 MENS 750 8
9 1400 E WOMENS HAND DRYER 20 1 + 20 1 LM EWH-1 2000 10
11 1000 E EAST EXT DOORS 20 1 + 12
13 1000 E EAST INT DOORS 20 1 + 14
15 1000 E NORTH DOORS 20 1 + 16
17 1000 E SOUTH DOORS 20 1 + 18
19 540 R WEST RECEP. 20 1 + 20
21 144 L EXTERIOR LCP 20 1 + 22
23 810 L NEW EXIST. LIGHTING 20 1 + 24
25 + 26
27 + 28
29 + 30
31 + 32
33 + 34
35 + 36
37 + 38
39 + 40
41 + 42
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL
DEMAND FEEDER TOTAL
GENERAL NOTES:
A. VERIFY AIC RATING WITH EXISITNG CONDITIOJNS
(L) LIGHTING 1179 1179 125% 1474 B.
(R) RECEPTACLES 2880 2880 NEC 220 2880 C.
(LM) LARGEST MOTOR 2000 2000 25% 500 D.
(M) MOTORS (ALL) 3742 3742 100% 3742 E.
(E) EQUIPMENT 6800 6800 100% 6800 SPECIFIC NOTES:
(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 15.4
(2)
(3)
PANEL TOTAL (A): 43
(4)
(5)
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING
RECESS
DEPTH
LAMPS
INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER
SPECIFIC
NOTES
QTY TYPE
F1
4' SURFACE MOUNTED LINEAR FLOURESCENT
WRAPAROUND.
SURFACE - 2 F32T8 64 120
CREATIVE
ILLUMINATION
402-32 XV
F2
4' LINEAR LED VANITY LIGHT, BRUSHED ALUMINUM
FINISH.
WALL - -LED AS SUPPLIED,
3500K
14.9 120 PHILIPS TAB4L-ASY-120-BA
F3
2' SURFACE MOUNTED LINEAR FLOURESCENT WRAP
AROUND.
SURFACE - 2 F17T8 32 120
CREATIVE
ILLUMINATION
402-17 XV
L1 4' LINEAR LED STRIP LIGHT SURFACE - - LED AS SUPPLIED 12 120 CROSSOVER LSL2-48-LED-NW-24-CL
M1 LED WHITE MONOPOINT AT EXISTING 18" AFF. WALL - 1
13PAR38/F25 3000
DIM AF SO 6/1
13 120 JUNO T1038E-25W-WH-T40WH
M2 MR16 SILVER MONOPOINT AT EXISTING LOCATIONS. WALL - 1 T527 50W MR16 50 120 JUNO TL116SL-TL540SL
R1 5" COMPACT LED RECESSED CAN. RECESSED 3 1/2" 1 LED WITH FIXTURE 13 120 PHILIPS
1050LRN09D1 1050LRN0927
1050LRNDLCDW
T1 4' TRACK WITH 2 LED WHITE HEADS AT 12' AFF. WALL - 2
13PAR38/F25 3000
DIM AF SO 6/1
26 120 JUNO TL1038E-25W-WH-T4WH-T21WH
T2 20' TRACK WITH 5 MR16 HEADS SILVER. SURFACE - 5 T527 50W MR16 250 120 JUNO T216SL-T8SL-T23SL
T3 16' TRACK WITH 5 MR16 HEADS SILVER. SURFACE - 5 T527 50W MR16 250 120 JUNO T216SL-T4SL-T21SL
X1 EMERGENCY LED EXIT SIGN COMBO WALL - - LED AS SUPPLIED 5.6 120 JUNO NXDC1GBA
X2 LED REMOTE HEAD WALL - - LED AS SUPPLIED 1 120 JUNO NRLWP1GY 1
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE
PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND
SPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.
B. REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.
C. ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE
SPECIFIC NOTES:
(1) WIRE REMOTE HEAD INTO BATTERY OF EMERGENCY EXIT SIGN COMBO (X1).
(2)
(3)
(4)
EXTERIOR LIGHTING CONTROL DIAGRAM - LCP
NO SCALE
120V
SYSTEM CLOCK
A
TC
DOUGLAS PROGAMMABLE LITEPAK
PANEL #WPAK-33518-S
POWER
TYPICAL
TYPICAL FOR BOTH EM & CHP
MECHANICAL EQUIPMENT SCHEDULE
MARK DESCRIPTION
VOLT /
PHASE
HP WATTS FLA MCA MOCP
DISCONNECT/
FUSE SIZE
FEEDER CIRCUIT SPECIFIC NOTES
EF-1 EXHAUST FAN 120/1 121 20 A
(2#12 & 1#12 G)
3/4"C
SP6-2, SP6-6
EWH-1 ELECTRIC WATER HEATER 120/1 2000 20 A
(2#12 & 1#12 G)
3/4"C
SP6-10
RHP-1 RADIANT HEATING CEILING
PANEL
120/1 750 20 A
(2#12 & 1#12 G)
3/4"C
SP6-4, SP6-8
UH-1 ELECTRIC UNIT HEATER 277/1 5000 20 A
(2#12 & 1#12 G)
3/4"C
LP4
GENERAL NOTES:
A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.
B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.
C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.
D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.
SPECIFIC NOTES:
(1)
(2)
(3)
(4)
VAIL, COLORADO 9491.00
07.14.14
SHEET TITLE:
NO. Job no.: REVISION Drawn by:
Date:
Designed by:
DATE
BY VAIL VILLAGE WELCOME CENTER
EAUDIN
ANZE
COPYRIGHT 2013
B
G
S:\BGProjects\9491.00 Vail Village Welcome Center - Electrical Design Build\Cad\BGCE CAD\949100E201.dwg Printed By: cadd-drp July 17, 2014 - 5:03pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
E-200
MAS
MAS
ELECTRICAL
ONE-LINE
11/19/14