HomeMy WebLinkAboutB14-0266 conductor sizing.pdf Page 5 of 6 7/7/2014 Conductor Sizing From Inverters to Inverter PV Combining Panel (for a 16 panel circuit): Nameplate maximum continuous output current: 1A 1A x 125% x 16 inverters = 20A #10 THWN-2 Table 310.16 40A (75ºC column, see note 240.4(D)) For 8 current carrying conductors use .70 40A x .70 = 28A Temperature correction factor Table 310.16 28A x .77 = 21.56A From PV Combining Panel to AC Disconnect/Backfeed Breaker: Nameplate maximum continuous output current: 1A 1A x 125% x 50 inverters = 62.5A #6 THWN-2 Table 310.16 65A (75ºC column) No Conduit fill adjustment Table 310.15 (B)(2)(a) No Temperature correction factor Table 310.16 Overcurrent Protection Devices 4 - 20A two pole breaker Inverter Output Combining Panel 1 - 70A two pole breaker Backfeed Breaker