Loading...
HomeMy WebLinkAboutM104.pdfSF-4 REPLACEMENT FAN SCHEDULE TOT. CFM S.P. OUTLET DESIG. MFR. MODEL FAN TYPE SERVICE AT IN. W.C. VELOCITY REMARKS 8120' AT 8120' (FPM) SF-4 TEMTROL 22,200 4.0 HUNTAIR FANWALL SWSI SWSI NOTES (ALL APPLY): 1. WEIGH EXISTING FAN AND ACCESSORIES WHEN REMOVING. WEIGHT OF NEW FANWALL SHALL NOT EXCEED EXISTING WEIGHT. WEIGHT OF EXISTING FAN AND CONCRETE BASE ESTIMATED TO BE 3,300 LBS. INDIVIDUAL FAN INFO NO. FANS 6 WHEEL DIA.(IN) 16 B.H.P. EACH 3.3 TOT. B.H.P. 20 CELL SIZE (IN) 32x30x23 FAN RPM 3,427 2. ARRAY SHALL BE CAPABLE OF MINIMUM 21,000 CFM WITH ONE FAN DISABLED. TOT. F.L.A. 27.0A 3. PROVIDE BACKDRAFT DAMPERS, COPLANER INSULATION, BALDOR PREMIUM EFFICIENCY MOTORS, ABB VFD 4. INTEGRATE INTO EXISTING CONTROL SYSTEM 5. CONTRACTOR TO PRECISELY COORDINATE NEW FAN WALL SIZE WITH EXISTING CASING SIZE DIRECT 90x70x24 FAN DRIVE TYPE ARRAY SIZE(IN) WxHxD 6. PROVIDE SINGLE POINT POWER CONNECTION 460V/3PH/60HZ 7. FIELD WIRING FURNISHED AND INSTALLED BY CONTRACTOR. VFD AND MOTOR OVERLOAD PANEL FURNISHED BY AHU VENDOR AND INSTALLED BY CONTRACTOR. 8. VFD SHALL INCLUDE HAND/AUTO/OFF FUNCTIONALITY 9. AIRFLOW MEASURING STATION AND TUBING TO BE FURNISHED BY TEMTROL INSTALLED BY CONTRACTOR. STATIC AND TOTAL PRESSURE TAPS TO BE FACTORY INSTALLED. CONTROL VFD 510 10. PROVIDE SHAFT GROUNDING KIT ALL TOTAL WEIGHT (LBS) 2,300 08/28/14