HomeMy WebLinkAboutM104.pdfSF-4 REPLACEMENT FAN SCHEDULE
TOT. CFM S.P.
OUTLET
DESIG. MFR. MODEL FAN TYPE SERVICE AT IN. W.C.
VELOCITY
REMARKS
8120' AT 8120'
(FPM)
SF-4 TEMTROL
22,200 4.0 HUNTAIR FANWALL SWSI SWSI
NOTES (ALL APPLY):
1. WEIGH EXISTING FAN AND ACCESSORIES WHEN REMOVING. WEIGHT OF NEW FANWALL SHALL NOT EXCEED EXISTING WEIGHT. WEIGHT OF EXISTING FAN AND CONCRETE BASE ESTIMATED TO BE 3,300 LBS.
INDIVIDUAL FAN INFO
NO.
FANS
6
WHEEL
DIA.(IN)
16
B.H.P.
EACH
3.3
TOT.
B.H.P.
20
CELL
SIZE (IN)
32x30x23
FAN
RPM
3,427
2. ARRAY SHALL BE CAPABLE OF MINIMUM 21,000 CFM WITH ONE FAN DISABLED.
TOT.
F.L.A.
27.0A
3. PROVIDE BACKDRAFT DAMPERS, COPLANER INSULATION, BALDOR PREMIUM EFFICIENCY MOTORS, ABB VFD
4. INTEGRATE INTO EXISTING CONTROL SYSTEM
5. CONTRACTOR TO PRECISELY COORDINATE NEW FAN WALL SIZE WITH EXISTING CASING SIZE
DIRECT 90x70x24
FAN
DRIVE
TYPE
ARRAY
SIZE(IN)
WxHxD
6. PROVIDE SINGLE POINT POWER CONNECTION 460V/3PH/60HZ
7. FIELD WIRING FURNISHED AND INSTALLED BY CONTRACTOR. VFD AND MOTOR OVERLOAD PANEL FURNISHED BY AHU VENDOR AND INSTALLED BY CONTRACTOR.
8. VFD SHALL INCLUDE HAND/AUTO/OFF FUNCTIONALITY
9. AIRFLOW MEASURING STATION AND TUBING TO BE FURNISHED BY TEMTROL INSTALLED BY CONTRACTOR. STATIC AND TOTAL PRESSURE TAPS TO BE FACTORY INSTALLED.
CONTROL
VFD 510
10. PROVIDE SHAFT GROUNDING KIT
ALL
TOTAL
WEIGHT
(LBS)
2,300
08/28/14