HomeMy WebLinkAbout2722 Cortina Lane - Sheet - A7-1 - FIREPLACE SHEET.pdfGENERAL NOTES:
1.) INSTALL GAS LOG SET AND BURNER PER MANUFACTURERS SPECIFICATION. CONTRACTOR TO HAVE A
COPY OF THE SPECIFICATIONS AND INSTALLATION REQUIREMENTS ON SITE SO INSPECTOR CAN VERIFY
PROPER INSTALLATION.
2.) INSTALL EXCEL MODEL RIS CHIMNEY @ LIVING ROOM, HEARTH ROOM, AND OUTDOOR FIREPLACES PER
MANUFACTURERS SPECIFICATION. CONTRACTOR TO HAVE A COPY OF THE SPECIFICATIONS AND
INSTALLATION REQUIREMENTS ON SITE SO INSPECTOR CAN VERIFY PROPER INSTALLATION.
4" STONE CHIMNEY CAP
PAINTED TO MATCH WINDOW
COLOR 4X4 TUBE STEEL POST
CANTED AT 1:12 WELDED TO 1/2" X
6" X 4" STEEL PLATE AT TOP AND
BOTTOM SET IN A BED OF SEALANT
OVER FLASHING, FASTENED WITH
LAG BOLTS INTO FRAMING BELOW
AND EXPANSION BOLTS INTO
STONE ABOVE
FLASHING OVER W.P.
MEMBRANE OVER SLOPED 1
1/8" PLYWOOD AS REQ'D
STEEL ANGLE RE:
STRUCT
LAP W.P. MEMBRANE OVER
FLASHING 1 1/2" MIN.
TYP. STONE WALL ASSEMBLY.
7 1/8"
6' - 3 1/2"
COUNTER FLASHING SET IN SEALANT
TYP.
STORM COLLAR FLASHING
SET IN SEALANT OVER COUNTER
FLASHING TYP.
4' - 0" 4"
MECHANICAL PVC VENTS
ROUTED THRU 2X8 WALL
AND DRILLED THRU
CHIMNEY CAP
2"
PROVIDE SOLID
BLOCKING UNDER STEEL
COLUMNS
FILL 2X10 CAVITY WITH INSULATION
TYPE X 5/8" DRYWALL CONT. @ INSIDE
OF CHASE FROM T.O. PLYWOOD SUB
FLOOR TO B.O. SHEATHING
2X10 JOISTS W/ TOPS CUT TO
SLOPE PLY WOOD ABOVE @ 1/8"
PER 1'-0" MAINTAIN 2"
CLEARANCE TO COMBUSTIBLES
1' - 8"
2 1/4"
1' - 4"
2" MIN
1' - 0"
TERMINATION CAP: MAINTAIN
CLEARANCES PRESCRIBED BY
CODE ABOVE ADJACENT CHIMNEY
FLUES
W.P. MEMBRANE CONT.
UP WALL
2"
10"
2"
2"
FIREPLACE FLUE INTERIOR
EXTERIOR
STONE VENEER ATTACHED PER 1/A6.1
RE: ELEVATION
LAP MIRADRAIN OVER ICE & WATER SHIELD
OVER FLASHING TO ALLOW PROPER WALL
DRAINAGE
PFSM CRICKET LAPPED OVER SOLID BLOCKING
OVER HIGH TEMP ICE & WATER SHIELD
PFSM FLASHING W/ DRIP EDGE AS SHOWN
2X FRAMING CRICKET STRUCTURE
RE: STRUCTURAL
PROVIDE BLOCKING
RE: STRUCTURAL
PROVIDE SOLID BLOCKING TO SUPPORT STONE VENEER
RE: STRUCTURAL
CONTINUE ROOF ICE & WATER SHIELD UP CHIMNEY WALL TO T.O
CHIMNEY
US Mail Only: P. O. Box 2378
Physical / Fedex: 210 Edwards
Village Blvd, Bldg A Suite A103
Edwards, Colorado 81632-2378
(970) 926 4301, Fax: 926 4364
hans@berglundarchitects.com
www . berglundarchitects.com
Scale
Date
Drawn by
Checked by
Issue Date
8/18/2014 3:11:52 PM
As indicated
2722 CORTINA LANE
VAIL RIDGE SUBDIVISION, BLOCK B,
LOT 13 , VAIL CO
A7.1
FIREPLACE
SHEET
8-18-14
AG
HB
8-18-14
BUILDING PERMIT
1 1/2" = 1'-0"
1 CHIMNEY SECTION
1 1/2" = 1'-0"
2
FIREPLACE DETAIL @ CRICKET
INTERSECTION
REVISION SCHEDULE
# DESCRIPTION DATE
09/17/14