HomeMy WebLinkAboutB14-0320 load calcs.pdf963 Lions Ridge LP #524
Proposed Load Calculation 8/26/14:
1039 sq. ft. @ 3VA 3,117 VA
Kitchen appliance X 2 3,000 VA
Dishwasher 1,200 VA
Disposal 1,200 VA
Refrigerator 1,200 VA
Microwave 1,200 VA
Range 8,500 VA
Washer 1,500 VA
Dryer 5,000 VA
Water Heater 5,000 VA
General Load SubāTotal 30,917 VA
1st 10kVA @ 100% 10,000 VA
Remainder @ 40% 8,367 VA
Total Net General Load 18,367 VA
Boiler and pumps @ 100% 3,000 VA
Total 21,367 VA
Calculated Load for Service 21,367 VA / 240 volts = 89 Amps
Existing service size 100Amps