ISSUE LOG KEY:
#
DATE
ISSUE LOG
ELECTRICAL SHEET INDEX
TITLE
ELECTRICAL COVER SHEET
E1.0
P ERMIT SET
07/30/14
UNIT 301 ELECTRICAL PLAN
E1.1
ABBREVIATIONS
AFC - ABOVE FINISHED CEILING
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AL - ALUMINUM
BFG - BELOW FINISH GRADE
C - CONDUIT
CKT - CIRCUIT
CT - CURRENT TRANSFORMER
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
(E) - EXISTING
FBO - FURNISHED BY OTHERS
GFI - GROUND FAULT CIRCUIT INTERRUPTER
IC - INTERMEDIATE CROSS-CONNECT
IAW - IN ACCORDANCE WITH
NIC - NOT IN CONTRACT
DW - DISHWASHER
DISP - GARBAGE DISPOSAL
NL - NIGHT LIGHT
UNO - UNLESS NOTED OTHERWISE
WP - WEATHER PROOF
XP - EXPLOSION PROOF
+18" - MOUNTING HEIGHT TO CENTERLINE OF
DEVICE ABOVE FINISH FLOOR
POWER SYMBOLS
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE; HALF SWITCHED
ISOLATED GROUND DUPLEX RECEPTACLE
WALL MOUNTED SPECIAL OUTLET AS NOTED
SPECIAL OUTLET AS NOTED
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
C
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM
ONE-LINE DIAGRAM SYMBOLS
MULTI-OUTLET PLUG STRIP
LIGHTING FIXTURE SYMBOLS
RECESSED LIGHTING FIXTURE
WALL MOUNTED LIGHT
WALL MOUNTED UP-LIGHT
PENDANT MOUNTED LIGHT
SURFACE MOUNTED LIGHT
DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE
MONO-POINT LIGHTING FIXTURE
RECESSED STEP LIGHT
FLUORESCENT STRIP LIGHT
WALL MOUNTED LINEAR FLUORESCENT LIGHT
RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER
FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT
WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
EMERGENCY LIGHTS
CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
LIGHTING CONTROL SYMBOLS
AWG - AMERICAN WIRE GAUGE
AP - ACCESS POINT
AHJ - AUTHORITY HAVING JURISDICTION
BMS - BUILDING MANAGEMENT SYSTEM
CATV - COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM
CCTV - CLOSED CIRCUIT TELEVISION
CPU - CENTRAL PROCESSING UNIT
FA - FIRE ALARM
GRD - GROUND
GC - GENERAL CONTRACTOR
OC - ON CENTER
WAN - WIDE AREA NETWORK
WLAN- WIRELESS LOCAL AREA NETWORK
W - WATT
V - VOLT
EXTERIOR POLE MOUNTED LIGHT
EXTERIOR POST (BOLLARD) MOUNTED LIGHT
DAYLIGHT PHOTO SENSOR
DL
SMALL ROOM OCCUPANCY SENSOR
LARGE ROOM OCCUPANCY SENSOR
CORRIDOR OCCUPANCY SENSOR
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
DIVISION 15 EQUIPMENT POWER CONNECTION
FUSED DISCONNECT
NON FUSED DISCONNECT
MOTOR STARTER
PUSH BUTTON
TRANSFORMER
PANELBOARD OR LOADCENTER
CONTACTOR
ELECTRIC MOTOR
METER
THERMOSTAT
ATS
AUTOMATIC TRANSFER SWITCH
CIRCUIT HOMERUN
CONDUIT RUN
CONDUIT RUN BELOW GRADE
CONDUIT UP
CONDUIT DOWN
TIMER SWITCH
TIME CLOCK
PHOTO-CELL
SWITCH
VARIABLE SPEED SWITCH
KEY SWITCH
S
K
SV
S
PC
TC
TS
T
C
T
N
--
J
J
J
DISCONNECT SWITCH
CIRCUIT BREAKER
CURRENT TRANSFORMER
GROUND
COLD WATER GROUND CONNECTION
BUILDING STEEL GROUND CONNECTION
OC
OC
OC
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
DOOR JAMB SWITCH
KEY SWITCH
LV
VARIABLE SPEED SWITCH
DIMMER
THREE-WAY DIMMER
LOW VOLTAGE SWITCH
WALL OCCUPANCY SENSOR/SWITCH
THERMAL OVERLOAD SWITCH
ST
O
D
3
D
SV
S
K
SJ
S4
S
3
S
S
1. . VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR
TO COMMENCEMENT OF WORK.
2. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER - IN WRITING. WORK
WHICH COULD RESULT IN AN ACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED
WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK.
3. REVIEW ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND OTHER DRAWINGS.
4. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.
5. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE OF
COLORADO, AND NATIONAL CODES AND ORDINANCES.
6. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS,
SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE.
7. PANEL DIRECTORIES SHALL BE REMOVABLE. SUBMIT PROPOSED SCHEDULE OF DIRECTORIES TO
OWNER FOR APPROVAL. DIRECTORIES SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC
COVERS.
8. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS
FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED. CONTRACTOR SHALL VISIT SITE PRIOR TO BID
TO DETERMINE EXTENT OF WORK INVOLVED. PROVIDE LABOR AND MATERIALS AS REQUIRED TO
MAINTAIN AND/OR RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS.
9. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING UTILIZED
FOR COMPLETION OF PROJECT.
10. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
11. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED
WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED.
12. INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY
DEVIATIONS SHALL BE BROUGHT TO THE ARCHITECT/ENGINEER'S ATTENTION PRIOR TO INSTALLATION.
13. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE,
CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST TO OWNER.
14. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER
RECOGNIZED TESTING FACILITY.
15. WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL
OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS SUITABLE FOR 75 DEGREE CELSIUS.
16. TYPE 'NM' OR 'NMC' CABLE MAY BE USED AS PERMITTED BY THE N.E.C. AND LOCAL ORDINANCE.
17. MECHANICAL DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO, AND
CONNECT EQUIPMENT AS REQUIRED.
18. NON-METALLIC AND FLEXIBLE METAL CONDUITS SHALL HAVE A CODE- SIZED COPPER GROUNDING
CONDUCTOR. INCREASE CONDUIT SIZE AS REQUIRED.
19. RECESSED LIGHITNG FIXTURES SHALL BE AIR TIGHT.
20. BOXES FOR TELEPHONE, TV, COMPUTER, WIRING DEVICES, ETC. SHALL BE MINIMUM 4" SQUARE.
GENERAL NOTES:
UNIT 301 LIGHTING PLAN
E1.2
FIRE ALARM SYMBOLS
FIRE ALARM CONTROL PANEL
REMOTE ANNUNCIATOR PANEL
SMOKE DETECTOR
HEAT DETECTOR
COMBO SMOKE/HEAT DETECTOR
FIRE ALARM HORN
FIRE ALARM STROBE
FIRE ALARM COMBO HORN/STROBE
FIRE ALARM PULL STATION
F
FIRE ALARM SPEAKER
F
FIRE ALARM COMBO SPEAKER/STROBE
FIREMAN'S PHONE JACK
DUCT SMOKE DETECTOR
SPRINKLER SYSTEM FLOW SWITCH
SPRINKLER SYSTEM TAMPER SWITCH
FIRE/SMOKE DAMPER
FSD
FT
FF
DD
F
F
H
H
SH
HD
SD
ANN
FACP
UNIT 302 ELECTRICAL PLAN
E2.1
UNIT 302 LIGHTING PLAN
E2.2
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING
RECESS
DEPTH
LAMPS
INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER
SPECIFIC
NOTES
QTY TYPE
F1 52" CEILING FAN WITH LIGHT KIT DOWNROD - 2
60W
INCANDESCENT
CANDELABRA
193 120
THE MODERN FAN
COMPANY
#CLD-TN-52-NK-IN-NC
F2
44" FLUSH MOUNT CEILING FAN, AS SPECIFIED BY
ARCHITECT
SURFACE - TBD TBD
P1 7 1/2" DIAMETER BRUSHED NICKEL PENDANT LIGHT PENDANT - 1 MR16 HALOGEN 50 12 TECHLIGHTING 700FJPPRZZ
P2
26" BRUSHED NICKEL PENDANT, AS SPECIFIED BY
ARCHITECT
PENDANT - TBD TBD
R1 5" RECESSED CAN LIGHT WITH DIMMING BALLAST RECESSED 7 1/2" 1
CFQ13W/G24Q
3000K
26 120 HALO H573ICAT1D ERT513WHT
R2 5" RECESSED CAN LIGHT RECESSED 7 1/2" 1
CFQ26W/G24Q
3000K
13 120 HALO H570ICAT ERT513WHT
R3 5" WET LOCATION RECESSED CAN LIGHT RECESSED 7 1/2" 1
CFQ26W/G24Q
3000K
13 120 HALO H570ICAT 5051PS
U1
UNDER CABINET WAC FLOURESCENT, AS SPECIFIED BY
ARCHITECT
SURFACE - TBD TBD
V1 LED VANITY LIGHT WALL - 1
T5 LINEAR
FLOURESCENT
24 120 TECHLIGHTING 700BCMETYS-CF
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE
PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND
SPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.
B. REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.
C. ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE
SPECIFIC NOTES:
(1)
(2)
(3)
(4)
2012 IECC COMPLIANCE (RESIDENTIAL)
UNIT 301
FIXTURE
TYPE
QUAN LAMP
TYPE
PERCENTAGE
R1 10 CFL 29%
R2 4 CFL 12%
R3 2 CFL 6%
U1 9 FL 26%
P1 * LV HAL
P2 3 INC 9%
V1 2 FL 6%
F1 2 INC 6%
F2 2 INC 6%
TOTAL 34 100%
High efficacy 79%
PER 2012 IECC R404 AT LEAST 75% OF
PERMANENTLY INSTALLED LAMPS SHALL
BE HIGH EFFICACY. ALL RECESSED
DOWNLIGHTS ARE SPECIFIED TO BE
AIR‐TIGHT
* NOTE‐PER 2012 IECC R404 LOW
VOLTAGE LIGHTING IS EXEMPT
2012 IECC COMPLIANCE (RESIDENTIAL)
UNIT 302
FIXTURE
TYPE
QUAN LAMP
TYPE PERCENTAGE
R1 10 CFL 29%
R2 6 CFL 18%
R3 2 CFL 6%
U1 7 FL 21%
P1 * LV HAL
P2 3 INC 9%
V1 2 FL 6%
F1 2 INC 6%
F2 2 INC 6%
TOTAL 34 100%
High efficacy 79%
PER 2012 IECC R404 AT LEAST 75% OF
PERMANENTLY INSTALLED LAMPS SHALL
BE HIGH EFFICACY. ALL RECESSED
DOWNLIGHTS ARE SPECIFIED TO BE
AIR‐TIGHT
* NOTE‐PER 2012 IECC R404 LOW
VOLTAGE LIGHTING IS EXEMPT
1 1
E1.0
MAS
MAS
SUITE 301 AND 302
ELECTRICAL COVER SHEET
VAIL, COLORADO
2465.06
07-31-14
SHEET TITLE:
NO. Job no.:
REVISION Drawn by:
Date:
Designed by:
DATE
BY BUILDING IMPROVMENTS
VAIL 21
EAUDIN
ANZE
COPYRIGHT 2014
B
G
C:\Users\cadd-txc\local settings\temp\AcPublish_9040\246506E10.dwg Printed By: cadd-txc September 18, 2014 - 4:28pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
REVISION 1
1 MAS
9-18-14
10/07/14