HomeMy WebLinkAboutB14-0344 Special Inspection Reports.pdfWest Slope Testing & Inspection LLC
3 I 77 Glendam Dr.
Grand Junction, CO 8I504
Phone:970-434-6988
Cell: 970-260-2844
Dates: 3-20-15 & 3-26-15
Inspection Report
Client: HP Geotech (Job #HP 114 043B)
Project: I82 West Meadow Dr. Duplex
Address: I82 West Meadow Dr. Vail, CO
Building Permit No: BI 4-0344
General Contractor: GE Johnson
Inspection of shop fabrication or field work at job site: Field
Report #I
Page I of I
Report: Verified onsite welders were qualified per A WS D l. I & using the correct
welding electrodes/materials.
Visually inspected field welding at face plate connections (for anchoring steel
beams to concrete wall pockets), and inspected high strength A325 bolting at steel
beam & column connections main floor level framing both units.
Visually inspected field welding at steel frame moment connections upper level
framing grid line I at A. I & C. Also observed joint preparation for steel frame
moment welds grid line 5 at B. I & C.9 (note double bevel groove welds with back
gouging/grinding were going to be used at these connections in lieu of single
bevel welds with backing bars. Both weld joints are prequalified per A WS D 1.1
for complete joint penetration welds). Inspected high strength A325 bolting at
steel beam & column connections upper level framing grids I to 2 West unit.
The field welding & high strength A325 bolting inspected above appeared to be
in substantial conformance with the plans, and the quality requirements of the
AWS DI.I Structural Welding Code & the AISC/RCSC Specification for
A325/A490 bolting.
Further inspections will be performed as work progresses.
Inspectorffechnician: Douglas E Young
West Slope Testing & Inspection LLC
3177 Glendam Dr.
Grand Junction, CO 81504
Phone:970-434-6988
Cell: 970-260-2844
Dates: 4-2-15 & 4-14-15
Inspection Report
Client: HP Geotech (Job #HP 114 043B)
Project: 182 West Meadow Dr. Duplex
Address: 182 West Meadow Dr. Vail, CO
Building Permit No: B14-0344
General Contractor: GE Johnson
Inspection of shop fabrication or field work at job site: Field
Report#2
Page 1of1
Report: Visually inspected field welding at steel frame moment connections
upper level framing grid line 5 at B.1 & C.9, and grid line E.4 at E2 & H. Visually
inspected field welding at tube steel connection welds & column base weld main
level framing grid line A from 2 to 3. Inspected high strength A325 bolting at steel
beam & column connections upper level framing grids 2 to 5 West unit, and 1.8 to
4 East Unit.
The field welding & high strength A325 bolting inspected above appeared to be
in substantial conformance with the plans, and the quality requirements of the
A WS D 1.1 Structural Welding Code & the AISC/RCSC Specification for
A325/ A490 bolting.
Further inspections will be performed on remainder of project.
Inspectorffechnician: Douglas E Young
+ Douglas E Young
CWI 96070131
QC1 EXP. 7/1/2017
West Slope Testing & Inspection LLC
3177 Glendam Dr.
Grand Junction, CO 81504
Phone:970-434-6988
Cell: 970-260-2844
Date: 5-5-15
Inspection Report
Client: HP Geotech (Job #HP 114 043B)
Project: 182 West Meadow Dr. Duplex
Address: 182 West Meadow Dr. Vail, CO
Building Permit No: Bl4-0344
General Contractor: GE Johnson
Inspection of shop fabrication or field work at job site: Field
Report#3
Page 1of1
Report: Received/reviewed certificates of compliance for high strength A325
bolts, nuts, and washers used on the project. Inspected high strength A325 bolting
at steel beam & column connections upper level framing grids D to E between 5 &
6.
The high strength A325 bolting inspected above appeared to be in substantial
conformance with the plans, and the requirements of the AISC/RCSC
Specification for A325/A490 bolting.
Further inspections will be performed on remainder of project.
West Slope Testing & Inspection LLC Report#4
3177 Glendam Dr.
Grand Junction, CO 81504
Phone:970-434-6988
Cell: 970-260-2844
Page 1of1
Final Inspection Report
Date: 7-9-15
Client: HP Geotech (Job #HP 114 043B)
Project: 182 West Meadow Dr. Duplex
Address: 182 West Meadow Dr. Vail, CO
Building Permit No: B 14-0344
General Contractor: GE Johnson
Inspection of shop fabrication or field work at job site: Field
Report: Visually inspected field welding at shear plates to W12x35 steel beam
unit B upper level framing grid line A.1 between grids 1 & 1.1 frame RF 4. Also
visually inspected field welding at tube steel connections South screen wall to unit
B, and field welding at steel stair stringer connection top of stairs Unit B.
The field welding inspected above appeared to be in substantial conformance
with the latest plans, and the quality requirements of the A WS D 1.1 Structural
Welding Code.
To the best of my knowledge this completes the special inspections of the
structural steel onsite welding & high strength A325 bolting on the project, as
outlined in reports #1 thru #4.
Douglas Young cwt 96010131
OC1 EXP. 71112017