Loading...
HomeMy WebLinkAboutE301 ELECTRICAL DIAGRAMS.pdfMECHANICAL EQUIPMENT SCHEDULE MARK DESCRIPTION QUANTITY VOLT / PHASE HP WATTS FLA MCA MOCP DISCONNECT/ FUSE SIZE FEEDER SPECIFIC NOTES MARK DESCRIPTION QUANTITY VOLT / PHASE HP WATTS FLA MCA MOCP DISCONNECT/ FUSE SIZE FEEDER SPECIFIC NOTES FC-1A FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD EF-1 EXHAUST FAN 6 120/1 -- 12 0.1 0.1 20A 1P MOTOR RATED SWITCH 2#12,#12GRD FC-2A FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD EF-2 EXHAUST FAN 10 120/1 -- 42 0.4 0.4 20A 1P MOTOR RATED SWITCH 2#12,#12GRD FC-3A FAN COIL 1 240/1 2 2880 12.0 15.0 20A 2P MOTOR RATED SWITCH 2#10,#10GRD EF-3 EXHAUST FAN 2 120/1 -- 97 0.8 1.0 20A 1P MOTOR RATED SWITCH 2#12,#12GRD FC-4A FAN COIL 1 120/1 (2) 1/12 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD EF-4 EXHAUST FAN 2 120/1 -- 64 0.5 0.7 20A 1P MOTOR RATED SWITCH 2#12,#12GRD FC-5A FAN COIL 1 120/1 3/4 1656 13.8 17.3 20A 1P MOTOR RATED SWITCH 2#12,#12GRD CH-1 CHILLER 2 240/1 -- 14400 60.0 66.3 100A -- -- 1 FC-6A FAN COIL 1 120/1 (2) 1/12 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD B-1 BOILER 6 120/1 -- 1440 12.0 15.0 20A 1P MOTOR RATED SWITCH 2#12,#12GRD FC-7A FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD P-1 BOILER INJECTION PUMP 6 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD FC-1B FAN COIL 1 120/1 1/6 528 4.4 5.5 20A -- -- 1 P-2 HEATING WATER CIRC PUMP 4 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD FC-2B FAN COIL 1 120/1 1/6 528 4.4 5.5 20A -- -- 1 P-3 DWH INJECTION 4 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD FC-3B FAN COIL 1 240/1 2 2880 12.0 15.0 20A 2P MOTOR RATED SWITCH 2#10,#10GRD P-4 DHW RECIRC PUMP 2 120/1 1/25 120 1.0 1.3 20A 30A, 1P, NF 2#12,#12GRD FC-4B FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD P-5A SNOWMELT INJECTION PUMP 1 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD FC-5B FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD P-5B SNOWMELT INJECTION PUMP 1 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD FC-6B FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD P-6A SNOWMELT CIRC PUMP 1 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD FC-7B FAN COIL 1 120/1 1/6 528 4.4 5.5 20A 1P MOTOR RATED SWITCH 2#12,#12GRD P-6B SNOWMELT CIRC PUMP 1 120/1 3/4 1656 13.8 17.3 20A 30A, 1P, NF 2#10,#10GRD GF-1 GLYCOL FEEDER 2 120/1 -- 50 0.4 0.5 20A CORD AND PLUG 2#12,#12GRD P-8 CHILLER INJECTION PUMP 2 120/1 3/4 1656 13.8 17.3 20A -- -- 1 GF-2 GLYCOL FEEDER 2 120/1 -- 50 0.4 0.5 20A CORD AND PLUG 2#12,#12GRD P-9 CHILLED WATER CIRC PUMP 2 120/1 3/4 1656 13.8 17.3 20A -- -- 1 H-1 HUMIDIFIER 3 240/1 -- 3,800 15.8 19.8 20A -- -- 1 SP-2A SEWAGE EJECTOR 1 120/1 1/2 1176 9.8 12.3 20A CORD AND PLUG 2#12,#12GRD SG-1 STEAM GENERATOR 2 240/1 -- 24,000 100.0 125.0 20A 200A, 2P, NF 3#1,#6GRD SP-2B SEWAGE EJECTOR 1 120/1 1/2 1176 9.8 12.3 20A CORD AND PLUG 2#12,#12GRD SG-2 STEAM GENERATOR 2 240/1 -- 12,000 50.0 62.5 20A 100A, 2P, NF 3#4,#8GRD HRV-1 HEAT RECOVERY VENTILATOR 1 120/1 -- 180 1.5 1.9 20A 1P MOTOR RATED SWITCH 2#12,#12GRD SG-3 STEAM GENERATOR 2 240/1 -- 15,000 62.5 78.1 20A 100A, 2P, NF 3#2,#8GRD 20A GENERAL NOTES: GENERAL NOTES: A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION. A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION. B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP. B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP. C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING. C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING. D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C. D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C. SPECIFIC NOTES: SPECIFIC NOTES: (1) CIRCUIT BREAKER PROVIDED IN PANEL FOR FUTURE EQUIPMENT. (1) CIRCUIT BREAKER PROVIDED FOR FUTURE EQUIPMENT. (2) (2) (3) (3) (4) (4) S:\BGProjects\9511.00 182 West Meadow Drive Duplex\Cad\BGCE CAD\951100E301.dwg Printed By: cadd-drp February 06, 2015 - 10:27am LC-XXX COPYRIGHT 2014 B ANZE G EAUDIN (970) 949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 (307) 739-3944 Vail: Denver: Fort Collins: Albuquerque: Jackson: www.bgce.com MERIBEL CORP. RESIDENCE Project Number - 1428 1650 Fallridge Road, Suite C-1 Vail, Colorado 81657 f.(970) 476-4901 p.(970)476-6342 182 WEST MEADOW DRIVE VAIL, CO 81657 11/10/14 90% CD SET 09/05/14 PERMIT SET 7/30/14 DESIGN REVIEW 01/06/15 CD SET E3.01 ELECTRICAL DIAGRAMS 04/15/15