HomeMy WebLinkAboutM030 SPECIFICATIONS.pdfMECHANICAL SPECIFICATIONS: 1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS. 2. ALL SUBCONTRACTORS SHALL BE LICENSED, EXPERIENCED, AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE CONSTRUCTION INDUSTRY AND SHALL PERFORM IN A RESPONSIBLE MANNER WITH ESTABLISHED CONSTRUCTION SEQUENCE, SHALL RECOGNIZE THE PRIORITY OF THE CONSTRUCTION DOCUMENTS, AND SHALL INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN THE CONSTRUCTION DOCUMENTS ARE UNCLEAR OR INCONSISTENT. 3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME CONTRACTOR OF DISCREPANCIES OR CONFLICTS IN THE CONSTRUCTION DOCUMENTS FOUND DURING BIDDING AND/OR PRIOR TO PERFORMING THE WORK. 4. EXAMINATION OF BIDDING DOCUMENTS. A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN (7) DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE CONSTRUCTION CONTRACT DRAWINGS AND SPECIFICATIONS. 5. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS FOR THE LISTED EQUIPMENT SHALL BE ALLOWED IN THE BASE BID. A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS LISTED ARE CONSIDERED GENERAL EQUIVALENTS ONLY. B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS: WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERAL EQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED, COORDINATE CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL AND OTHER WORK. 1) PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND PROPERLY FITS IN THE AVAILABLE SPACE ALLOCATED FOR THE BASIS OF DESIGN. 2) PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF DESIGN PLUS ANY SPECIFIED OPTIONS. 3) BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT, FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL EQUIVALENTS OR SUBSTITUTIONS DO NOT CAUSE ACCESS, SERVICE, OR OPERATIONAL DIFFICULTIES ANY GREATER THAT WOULD BE ENCOUNTERED WITH THE BASE DESIGN. 6. SUBCONTRACTOR SHALL VERIFY EXISTENCE AND LOCATION OF ALL UTILITY SERVICES AND COORDINATE AS REQUIRED BY THEIR RESPECTIVE AREA OF THE CONSTRUCTION, NOTIFYING THE PRIME CONTRACTOR OF VARIATIONS OR CONFLICTS. 7. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS, MATERIALS AND/OR EQUIPMENT SHALL BE IDENTIFIED BY THE SUBCONTRACTOR WITH SUFFICIENT TIME TO ALLOW SELECTION, PURCHASE, AND DELIVERY TO MAINTAIN CONSTRUCTION SCHEDULE. 8. VERIFY EXACT LOCATIONS OF NEW UNDERGROUND UTILITIES, PIPING, AND RACEWAY SYSTEMS PRIOR TO TRENCHING. CONTRACTOR SHALL OBTAIN AND VERIFY EXACT UTILITY COMPANY DRAWINGS AND REQUIREMENTS. 9. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE STRUCTURE, BEAMS, AND COLUMNS. 10. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT, OWNER, AND ENGINEER. 11. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS/HER WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND LIFE SAFETY FEATURES AS REQUIRED BY LOCAL, STATE, OR NATIONAL AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF MODIFICATION OF HIS/HER WORK IS REQUIRED FOR COMPLIANCE. 12. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE 2012 VERSION OF THE INTERNATIONAL RESIDENTIAL, MECHANICAL, PLUMBING, ENERGY CONSERVATION, FUEL GAS, AND FIRE CODES AND THE 2011 NATIONAL ELECTRICAL CODE, MOST CURRENT NFPA, ALL LOCAL ORDINANCES AND AMENDMENTS AND MANUFACTURER'S INSTALLATION RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE PUBLICATIONS EXISTS, THE MOST STRINGENT REQUIREMENT SHALL APPLY. 13. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS. PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES OF COMPLETION. 14. WARRANTY THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP. THE WARRANTY SHALL BE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER. 15. SUBMIT RECORD DOCUMENTS TO ARCHITECT. DOCUMENTS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC. 16. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY THE OWNER. 17. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK ARE DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO ADDITIONAL COST TO OWNER. 18. ALL MATERIALS AND/OR EQUIPMENT SHALL BE HANDLED AND INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS. 19. SUBMIT ALL MECHANICAL DIVISION SHOP DRAWING AND PRODUCT DATA AT ONE TIME. PARTIAL SUBMITTALS WILL BE REJECTED. 20. SHOP DRAWING SUBMITTALS SHALL STATE CAPACITIES, SIZES, ETC., OF ALL EQUIPMENT AND SHALL BE CERTIFIED AND INCLUDE COMPUTER BASED PROJECT SPECIFIC SELECTIONS WHERE APPLICABLE. CLEARLY MARK EACH SHOP DRAWING, CATALOG CUT AND/OR SPECIFICATION SHEET TO INDICATE THOSE PRODUCTS AND FEATURES WHICH ARE INTENDED TO BE FURNISHED. SPECIFICALLY INDICATE ANY DEVIATIONS FROM THE DESIGN INTENT. ENGINEER RESERVES THE RIGHT TO REQUIRE CORRECTION AT NO COST TO OWNER FOR DEVIATIONS NOT SPECIFICALLY INDICATED IN THE SUBMITTALS. REVIEW AND APPROVAL OF SHOP DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR FROM THE RESPONSIBILITY OF FURNISHING EQUIPMENT AND MATERIALS OF PROPER DIMENSION, SIZE, QUANTITY, QUALITY AND ALL PERFORMANCE CHARACTERISTICS TO EFFICIENTLY PERFORM THE REQUIREMENTS AND INTENT OF THE CONTRACT DOCUMENTS. SUBMITTAL SHALL BE BOUND AND INDEXED IN A NEAT AND ORDERLY MANNER. 21. [SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO: EQUIPMENT, FIXTURES, INSULATION, DIFFUSERS, PUMPS, FANS, PIPING, VALVES, BOILERS, AND CONTROLS. 22. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 23. TEMPORARY HEAT SHALL BE FURNISHED BY THE GENERAL CONTRACTOR. USE OF THE PERMANENT HEATING SYSTEM WILL NOT BE ALLOWED. 24. PROVIDE 4” HIGH CONCRETE EQUIPMENT PADS BENEATH FLOOR MOUNTED MECHANICAL EQUIPMENT, IN ADDITION TO ANY BASE ASSEMBLIES REQUIRED OR RECOMMENDED BY THE MANUFACTURER. 25. FIRE STOPPING REQUIREMENT. PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ACCEPTABLE MATERIALS INCLUDE: DOW CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 150 CAULK FOR BARE PIPE, METAL CONDUIT, AND BUILDING CONSTRUCTION GAPS; 3M CP-25 CAULK AND FS-195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, AND ELECTRICAL CABLE. SUBMIT UL LISTED APPLICATION DATA FOR EACH TYPE OF PENETRATION ENCOUNTERED. 26. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE ARCHITECTURAL DRAWINGS. IN THE ABSENCE OF ANY OTHER REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING VENTS IN BUILT-UP ROOFS, TALL CONE WITH EPDM BOOT FOR PIPE AND CONDUIT IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF PENETRATIONS IN ALL TYPES OF ROOF. INSTALLATION SHALL BE WATERTIGHT. 27. ALL FLOOR DRAINS AND FLOOR SINKS CONNECTED TO THE SEWER SYSTEM SHALL BE EQUIPPED WITH TRAP PRIMERS. PROVIDE TRAP PRIMERS WITH BACKFLOW PREVENTERS AND CONNECT TO THE NEAREST COLD WATER PIPING ADJACENT TO A FLUSHING FIXTURE. PROVIDE ELECTRONIC TRAP PRIMERS FOR ANY AREAS WHERE THE NEAREST ADJACENT FLUSHING FIXTURES ARE NOT WITHIN A REASONABLE DISTANCE OR STRUCTURAL OBSTRUCTIONS PREVENT GRAVITY SLOPING OF TRAP PRIMER LINES. ADDED COST OF ELECTRIC POWER FOR ELECTRONIC TRAP PRIMERS SHALL BE BORNE BY PLUMBING CONTRACTOR. INSTALL ALL TRAP PRIMER VALVES AND ASSOCIATED SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. 28. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL CEILING PENETRATIONS AND AIR DEVICE LOCATIONS. 29. COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, ELECTRICAL, LANDSCAPING, AND INTERIOR DESIGN DRAWINGS PRIOR TO INSTALLATION. 30. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE AVAILABLE. 31. MOUNT ALL STATS AT 48” AFF IN “ACCESSIBLE” AREAS, 4'6” AFF IN OTHER AREAS, UNLESS NOTED OTHERWISE. COORDINATE LOCATION WITH WALL FINISH, AND TO AVOID CASEWORK, FURNITURE, DOOR SWINGS, HEAT SOURCES, AND EXTERIOR WALLS. NOTIFY ENGINEER OF ANY CONFLICTS PRIOR TO BEGINNING THERMOSTAT INSTALLATION. 32. SUBMIT A WRITTEN BALANCE REPORT BY A NEBB OR AABC CERTIFIED BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE IN ACCORDANCE WITH NEBB OR AABC GUIDELINES FOR PROPORTIONAL BALANCE. SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS FOR REVIEW PRIOR TO BALANCING. MEASUREMENTS SHALL INCLUDE ALL MOTOR AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS; STATIC PRESSURE AT INLET AND OUTLET OF ALL PACKAGED EQUIPMENT, FANS, COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY, EXHAUST, RETURN, AND OUTSIDE AIR MAIN DUCTS; AIR INLET AND OUTLETS; WATER FLOW AT ALL FLOW MEASUREMENT STATIONS; INLET AND OUTLET PRESSURE AT PUMPS WITH FLOW CALCULATED FROM THE PUMP CURVE; WATER FLOW, TEMPERATURE DROP, AND PRESSURE DROP AT ALL COILS. A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO ADJUST FAN SPEED. B. ADJUST FLOWS TO WITHIN 10% OF REQUIRED QUANTITY. WHERE ROOM AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE MAINTAINED AS SHOWN BY A DIFFERENTIAL OF SUPPLY AND EXHAUST/RETURN OR BY NOTE, ADJUST SUPPLY TO WITHIN 10% AND THEN ADJUST EXHAUST/RETURN TO PROVIDE THE INDICATED ROOM PRESSURE. IF ACTUAL QUANTITY IS LESS THAN 90%, INVESTIGATE CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER. SUBMITTAL OF BALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT EXPLANATION IS CAUSE FOR REJECTION OF REPORT. C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES SHALL BE RETAINED BY THE OWNER, ARCHITECT, AND ENGINEER. 33. DUCTWORK: (LOW VELOCITY) A. DUCTS SHALL BE INSULATED TO A MINIMUM R-6. B. FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE RETARDANT POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM LAYER OF FIBERGLASS INSULATION, HIGH-STRENGTH GALVANIZED STEEL HELIX ENCAPSULATED IN REINFORCED “RIP STOP” ALUMINUM LAMINATE INTERIOR CORE, UL LISTED AND LABELED, CLASS 1 AIR DUCT. WORKING PRESSURE RATING: POSITIVE 6”, NEGATIVE 4”. FLEXMASTER TYPE 5 OR EQUIVALENT. SUBMIT SAMPLES TO DETERMINE EQUIVALENCE. C. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS CLOTH, 10” W.C. RATED. D. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR 5 GORE ELBOWS. “SNAP-LOCK”, LONGITUDINAL SEAM DUCT, OR ADJUSTABLE FITTINGS ARE ACCEPTABLE ON INDIVIDUAL GRILLE/DIFFUSER RUNOUTS ONLY. E. LINER: 1) LINE ALL SUPPLY, OUTSIDE AIR, RETURN AIR DUCTS, EXHAUST AIR RISERS, AND MAKE UP AIR RISERS WITH 1”, 1.5 LB/CF, BLACK MATTE COATED INSULATING DUCT LINER. 2) LINER SHALL BE COATED AND SEALED AND SHALL MEET ASTM C1071. 3) MATERIAL SHALL MEET ALL REQUIREMENTS OF NFPA-90. 4) INSTALL WITH ADHESIVE AND WELDED PINS IN ACCORDANCE WITH SMACNA “HVAC DUCT CONSTRUCTION STANDARDS”. 5) EXTERNALLY WRAP ALL ROUND SUPPLY AIR DUCTS WITH FLEXIBLE GLASS FIBER, ANSI/ASTM C612; 0.002 INCH FOIL SCRIM FACING. F. DUCTWORK: G60 GALVANIZED SHEET STEEL; LOCK FORMING QUALITY; CONSTRUCTED TO AND GAUGE PER THE LATEST EDITION OF SMACNA “HVAC DUCT CONSTRUCTION STANDARDS”; +/- 1” WC PRESSURE CLASSIFICATION, SEAL CLASS “C”; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES, STRAPS, ETC. G. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH UNITED MCGILL “UNI-GRIP” UL LISTED, WATER BASED, NON-HARDENING, ELASTIC SEALANT OR EQUIVALENT. TAPE NOT ALLOWED. 34. PROVIDE ¼” GALVANIZED MESH SCREEN ON ALL COMBUSTION AIR DUCTS OR OPENINGS, AND ALL OPEN END RETURN AND EXHAUST DUCTS. 35. ALL DUCTWORK DIMENSIONS ARE OUTSIDE SHEET METAL DIMENSIONS. DUCT LINER HAS BEEN ACCOUNTED FOR WITHIN RECTANGULAR DUCTWORK. 36. DUCTWORK NOTES: A. DIFFUSER NECK SIZE IS SAME AS FLEXIBLE DUCT SIZE. B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 DUCT WIDTH. 1) WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE THROAT ELBOWS WITH SINGLE WIDTH (NON-AIRFOIL) TURNING VANES. 2) FOR DUCT DEPTHS OF 36” OR LESS, PROVIDE MANUFACTURED SINGLE WIDTH (NON-AIRFOIL) TURNING VANES, WITH SPACING IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS FOR “STANDARD SPACING”. USE DOUBLE THICKNESS BLADES FOR DUCT DEPTHS GREATER THAN 36”. USE NO TRAILING EDGES. C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED EIGHT FEET IN LENGTH. 37. SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR CLAMPS. NO PIPE TAPE OR STRAPPING ALLOWED. ALL HANGERS SHALL BE SIZED FOR OD OF INSULATION, IF ANY. PROTECT INSULATED LINES WITH 20 GA SHEET METAL SHIELDS AND PROVIDE CALCIUM SILICATE INSULATION INSERTS FOR ALL INSULATED PIPING. MAINTAIN VAPOR BARRIER ON ALL COLD LINES. ISOLATE BARE COPPER LINES FROM HANGERS WITH VIBRASORB OR EQUIVALENT, COPPER COATED HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT ACCEPTABLE. 38. REFER TO PLUMBING FIXTURE CONNECTIONS SCHEDULE FOR PIPE SIZES TO INDIVIDUAL PLUMBING FIXTURES. 39. PROVIDE SHOCK ARRESTERS AT ALL DOMESTIC HOT AND COLD WATER BRANCHES SERVING FIXTURES AND EQUIPMENT WITH QUICK CLOSING VALVES. SUCH FIXTURES AND EQUIPMENT INCLUDES DISHWASHERS AND CLOTHES WASHERS. SHOCK ARRESTERS SHALL BE CONSTRUCTED WITH A PISTON IN A SEALED COPPER TUBE CHAMBER, AND APPROVED FOR INSTALLATION WITHIN WALLS WITHOUT ACCESS PANELS. SIOUX CHIEF OR EQUIVALENT. BELLOWS TYPE NOT ACCEPTABLE. 40. DOMESTIC HOT AND COLD PIPING INSIDE BUILDING--BURIED LINES, TYPE “K” SOFT ANNEALED COPPER WATER TUBE, SINGLE LENGTH TO AVOID FITTINGS, (WROUGHT COPPER FITTINGS WHERE UNAVOIDABLE) AND 1100°F SOLDER. NON-BURIED LINES, TYPE “L” HARD COPPER WATER TUBE, WROUGHT COPPER FITTINGS AND NO LEAD 95-5 SOLDER OR PEX TUBE AND FITTINGS, ASTM F877, SDR 9 TUBING, ASTM F1807 FITTINGS WITH CRIMP RINGS, MULTIPLE OUTLET MANIFOLD ASSEMBLY. 41. COPPER PIPE VALVES AND SPECIALTIES A. GATE VALVES - BRONZE, CLASS 125, 200 LB. W.O.G. B. BALL VALVES - BRONZE, CLASS 125, 600 LB. W.O.G. C. CHECK VALVES - BRONZE, CLASS 125, 200 LB. W.O.G. D. BALANCING VALVES - 125 PSI W.P. FOR 250 DEGREE FARENHEIGHT SERVICE TIGHT SHUTOFF, TOUR AND ANDERSON STA, ARMSTRONG CBV, GERAND, OR FLOWSET, B&G CIRCUIT SETTER. E. DIRECT UNIONS: FURNISH AND INSTALL A DIELECTRIC UNION AT EACH CONNECTION BETWEEN DISSIMILAR METALS. 42. MATERIALS; SOIL, WASTE, AND VENT PIPING (INSIDE BUILDING) A. LINES BURIED BELOW GROUND: STANDARD WEIGHT, CAST IRON SOIL PIPE, AND FITTINGS. HUB AND SPIGOT WITH NEOPRENE GASKETS, OR NO HUB WITH HEAVY DUTY 304 STAINLESS STEEL CLAMPS, HUSKEY OR EQUIVALENT. B. LINES ABOVE GROUND: STANDARD WEIGHT, CAST IRON SOIL PIPE, AND FITTINGS. HUB AND SPIGOT WITH NEOPRENE GASKETS, OR NO HUB WITH STANDARD CLAMPS. UP THROUGH 2-1/2” MAY BE STANDARD WEIGHT, GALVANIZED STEEL PIPE WITH BLACK, WROUGHT IRON DRAIN FITTINGS, OR DWV COPPER TUBE WITH DWV FITTINGS AND 95-5 NO LEAD SOLDER. 43. GAS PIPING: SCHEDULE 40 BLACK STEEL PIPE, 150 LB. MALLEABLE IRON SCREWED FITTINGS ON ABOVE GROUND PIPE, WELDED FITTINGS WITH ALL PIPING COATED AND WRAPPED ON BURIED PIPE. 44. GAS VALVES: NON-LUBRICATED BALL STYLE VALVE WITH RESILIENT SEATS, AND ADJUSTABLE GLAND PACKING NUT, AGA AND UL LISTED FOR NATURAL GAS SERVICE. 45. PROVIDE EXPANSION JOINTS OR LOOPS ON ALL CHILLED, SNOWMELT, AND HEATING WATER PIPING RUNS IN EXCESS OF 50 FEET AND IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. 46. FILL HEATING WATER SYSTEM WITH 30% PROPYLENE GLYCOL/WATER SOLUTION AND FILL SNOWMELT SYSTEM WITH 50% PROPYLENE GLYCOL/WATER SOLUTION. 47. GRADE AND VALVE ALL HEATING, CHILLED, AND SNOWMELT WATER PIPING WITH 3/4” HOSE END VALVES TO PERMIT COMPLETE DRAINAGE OF THE SYSTEM. VENT ALL HIGH POINTS IN EQUIPMENT ROOMS AS NECESSARY WITH AUTOMATIC AIR VENTS PIPED TO CONVENIENT DRAIN. ALL HIGH POINTS IN SYSTEM OUTSIDE OF EQUIPMENT ROOMS WITH COMBINATION AUTOMATIC/MANUAL AIR VENTS AS REQUIRED TO RELIEVE AIR IN THE SYSTEM. 48. PROVIDE PLASTIC GROMMETS ON ALL HEATING WATER PIPING PASSING THROUGH WOOD JOISTS AND STUDS. 49. MATERIALS; HYDRONIC PIPING A. ABOVE GRADE, UP THROUGH 2-1/2”: SCHEDULE 40 STEEL PIPE WITH MALLEABLE IRON THREADED FITTINGS, OR TYPE “L” COPPER TUBE WITH WROUGHT COPPER FITTINGS AND 95-5 NO LEAD SOLDER. B. ABOVE GRADE, 3” AND LARGER: SCHEDULE 40 STEEL PIPE WITH CAST IRON OR STEEL WELDING FITTINGS. C. BELOW GRADE, UP THROUGH 1-1/4”: TYPE “K” SOFT ANNEALED COPPER TUBE, SINGLE LENGTH TO AVOID FITTINGS, (WROUGHT COPPER FITTINGS WHERE UNAVOIDABLE) AND 1100 DEGREE FARENHEIGHT SOLDER INSULATE WITH 1” THICK CLOSED CELL ELASTOMERIC INSULATION. ALL BURIED PIPE SHALL BE SURROUNDED WITH 4” OF CLEAN SAND. D. BELOW GRADE, 1-1/2” AND LARGER: JACKETED, PRE-INSULATED PIPING, WITH FLUID CARRIER PIPE EQUAL TO ABOVE SPECIFICATION. ROVANCO, RICWELL/PERMA-PIPE OR EQUIVALENT. E. SNOWMELT/RADIANT FLOOR SERPENTINE TUBING: 1) ALL TUBING TO BE CROSS-LINKED POLYETHYLENE (PEX) WITH AN OXYGEN DIFFUSION BARRIER. TUBING TO BE RATED FOR CONTINUOUS OPERATION OF 100 PSIG AND A TEMPERATURE SUITABLE FOR THE SPECIFIC APPLICATION. FACTORY MANIFOLDS SHALL BE EQUIPPED WITH LOOP VALVES AND ZONE VALVES PER CONTROLS REQUIREMENTS. SYSTEMS SHALL BE CAPABLE OF WITHSTANDING TEMPERATURES 180 DEGREE F TO 230 DEGREE F FOR LIMITED PERIODS OF TIME. INSTALL PIPING AND MANIFOLD IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. 2) SNOWMELT PIPING: WIRSBO HEPEX OR APPROVED EQUIVALENT. 3) RADIANT FLOOR PIPING: WIRSBO HEPEX OR APPROVED EQUIVALENT. 50. DRAIN AND RECEPTOR PIPING FOR COMBUSTION CONDENSATE--NOT BURIED--TYPE: SCHEDULE 40 SOLID-WALL PVC, PVC FITTINGS, AND PVC CEMENT; BURIED--TYPE: SCHEDULE 80 SOLID-WALL PVC, PVC FITTINGS, AND PVC CEMENT. ALL BURIED PIPE SHALL BE SURROUNDED WITH 4” OF CLEAN SAND. PROVIDE NEUTRALIZATION SYSTEMS AS RECOMMENDED BY COMBUSTION APPLIANCE MANUFACTURER. 51. DRAIN PAN PIPING: NOT BURIED: TYPE “M” COPPER, WROUGHT COPPER FITTINGS, AND 95-5 SOLDER; BURIED: TYPE “L” COPPER WROUGHT COPPER FITTINGS, AND 95-5 SOLDER. ALL BURIED PIPE SHALL BE SURROUNDED WITH 4” OF CLEAN SAND. 52. REFRIGERATION PIPING--TYPE “L”, ACR GRADE COPPER, CLEANED, DEHYDRATED, AND CAPPED AT THE FACTORY. USE WROUGHT COPPER FITTINGS AND HARD SOLDER HAVING A MINIMUM MELTING POINT OF 1100 DEGREE F FOR BURIED LINES, 95-5 SOLDER FOR NON-BURIED LINES. VALVES AND SPECIALTIES SHALL BE STANDARD BRASS OR BRONZE VALVES FOR REFRIGERATION SERVICE. BURIED PIPE SHALL BE SURROUNDED BY 4” CLEAN SAND. 53. SUPPORT EACH AIR HANDLING UNIT AND FAN BY MASON INDUSTRIES OR EQUIVALENT SPRING TYPE VIBRATION ISOLATORS. 54. INDOOR PIPING INSULATION - INSULATE ALL HEATING WATER, CHILLED WATER, REFRIGERANT, DOMESTIC WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RECIRCULATION, AND HORIZONTAL STORM AND OVERFLOW PIPING WITH UL APPROVED, WHITE, ALL SERVICE, MINERAL FIBER, SNAP-ON, PIPE INSULATION. INSULATE FITTINGS WITH MINERAL FIBER BLANKET INSULATION AND PRE-MOLDED PVC COVERS. ALL MATERIALS SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25 OR LESS. PROVIDE CALCIUM SILICATE THERMAL INSERT AT HANGERS AND SUPPORTS. INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH “NON-BREATHING” VAPOR BARRIER MASTIC ON PIPING OPERATING AT TEMPERATURES BELOW AMBIENT. ALL RAW EDGES OF INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC. A. INSULATION R-VALUE OF 3; BASED ON INSULATION CONDUCTIVITY VALUE NOT EXCEEDING 0.27 BTU*IN/(HR*FT^2*°F):: 1) HEATING AND SNOWMELT WATER (LESS THAN 200°F) - NPS 1.25 AND LESS, 1.5” THICK; NPS 1.5 AND GREATER, 2” THICK. RUNOUTS WITHIN 4 FEET OF TERMINAL AND 1” PIPE DIAMETER OR LESS, 1” THICK. 2) CHILLED WATER AND REFRIGERANT (SUCTION AND LIQUID) - ALL PIPE SIZES, 1” THICK. RUNOUTS WITHIN 4 FEET OF TERMINAL AND 1” PIPE DIAMETER OR LESS - 1/2” THICK. 3) DOMESTIC HOT WATER (DHW) AND DOMESTIC HOT WATER RECIRCULATION: ALL PIPE SIZES - 1” THICK; NON-RECIRCULATED DHW RUNOUTS WITHIN 8 FEET OF FIXTURES - 1/2” THICK. 4) DOMESTIC COLD WATER: ALL PIPE SIZES - 1/2” THICK. 5) HORIZONTAL STORM AND OVERFLOW PIPING: ALL SIZES - 1/2” THICK. 54. OUTDOOR PIPING INSULATION: INSULATE ALL HEATING WATER, CHILLED WATER, DOMESTIC WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RECIRCULATION, AND HORIZONTAL STORM AND OVERFLOW PIPING WITH UL APPROVED, WHITE, ALL SERVICE, CELLULAR GLASS, OR POLYISOCYANURATE, PRE-MOLDED, SNAP-ON, PIPE INSULATION; INSULATION SHALL BE PROTECTED FROM DAMAGE WITH PVS, STAINLESS STEEL, OR OTHER JACKETING. INSULATE FITTINGS WITH PRE-MOLDED INSULATING FITTINGS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH “NON-BREATHING” VAPOR BARRIER MASTIC ON PIPING OPERATING AT TEMPERATURES BELOW AMBIENT. ALL RAW EDGES SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC. BELOW GRADE PIPING SYSTEMS SHALL BE INSULATED WITH PRE-MOLDED POLYISOCYANURATE AND JACKETED WITH WATERTIGHT HPDE SYSTEM LISTED FOR DIRECT BURY. INSULATION THICKNESSES AS FOLLOWS ARE BASED ON INSULATION CONDUCTIVITY NOT EXCEEDING 0.27 BTU*IN/(HR*FT^2*°F): 1) HEATING AND SNOWMELT WATER (LESS THAN 200°F) - NPS 1.25 AND LESS, 2” THICK; NPS 1.5 AND GREATER, 3” THICK. RUNOUTS WITHIN 4 FEET OF TERMINAL AND 1” PIPE DIAMETER OR LESS, 1” THICK. 2) CHILLED WATER (NOT LESS THAN 40°F) - ALL PIPE SIZES, 2” THICK. RUNOUTS WITHIN 4 FEET OF TERMINAL AND 1” PIPE DIAMETER OR LESS - 1/2” THICK. 3) DOMESTIC HOT WATER (DHW) AND DOMESTIC HOT WATER RECIRCULATION: ALL PIPE SIZES - 2” THICK; NON-RECIRCULATED DHW RUNOUTS WITHIN 8 FEET OF FIXTURES - 1” THICK. 4) DOMESTIC COLD WATER: ALL PIPE SIZES - 2” THICK. 5) HORIZONTAL STORM AND OVERFLOW PIPING: ALL SIZES - 1” THICK. 55. IDENTIFICATION: LABEL ALL PIPING AND EQUIPMENT. PROVIDE FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND ATTACH WITH STANDARD CHAIN OR S-HOOKS. PROVIDE ENGRAVED PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT. 56. DUCTWORK SPECIALTIES A. VOLUME AND SPLITTER DAMPERS: GALVANIZED SHEET METAL WITH VENTFABRICS, INC., VENTLOCK OR EQUAL OPERATING HARDWARE. FOR ACCESSIBLE DAMPERS, PROVIDE NO. 620, 635 OR 637 DIAL REGULATORS, NO. 635 OR 637 SQUARE END BEARING, AND NO. 635 SPRING END BEARING, AS APPLICABLE. FOR INACCESSIBLE DAMPERS, PROVIDE NO. 666 CONCEALED DAMPER REGULATOR, WITH PAINTED COVER (COLOR BY ARCHITECT) AND BEARINGS AS ABOVE. FOR MEDIUM PRESSURE DUCTS, PROVIDE NO. 635 HIVEL DIAL REGULATOR AND NO. 609 HIVEL END BEARING FOR ACCESSIBLE DAMPERS. B. MULTI-LOUVER VOLUME DAMPERS: TITUS AG-35-B OPPOSED BLADE, ANEMOSTAT OR EQUAL. SEE DETAIL REGARDING REMOTE ACCESS TO VOLUME DAMPERS. A. FIRE-SMOKE DAMPERS: RUSKIN, AIR BALANCE, INC. OR EQUAL, UL LABELED AND IN CONFORMANCE WITH NFPA 90A. ALL DAMPERS TO BE OUT OF AIRSTREAM, TYPE B OR C RATED FOR A MINIMUM OF 1-1/2 HOURS (2 HOURS WHERE NOTED), UL LABEL AND AS APPROVED BY LOCAL AUTHORITIES. MOUNT DAMPERS WITHIN 16-GAGE SLEEVES HELD IN PLACE WITH RETAINING ANGLES. COORDINATE LOCATION OF ACCESS PANELS TO PERMIT EASY ACCESS TO FUSIBLE LINK. D. TURNING VANES FOR LOW PRESSURE DUCTS: SMACNA SMALL DOUBLE VANE, PLATE NO. 22B OR EQUAL, WITH AIRFOIL BLADES FOR DUCTS 36" OR LESS IN WIDTH; SMACNA FIG. 3.23 FOR DUCTS GREATER THAN 36" WIDE. FOR MEDIUM PRESSURE DUCTS: SMACNA FIG. 3-23. E. ACCESS PANELS: 1) REINFORCED, GALVANIZED SHEET METAL WITH AIRTIGHT GASKETS RATED FOR PRESSURES AND SERVICE INTENDED. MILCOR OR EQUAL. PROVIDE HINGES AND VENTFABRICS, INC. VENTLOCK LATCHES. 2) DUCT ACCESS PANELS FOR HAND ENTRY ONLY: NO. 90 SASH TYPE LATCH. MINIMUM SIZE: 18" X 18". 3) DUCT AND PLENUM ACCESS DOORS FOR BODY ENTRY: NO. 310 LATCH, OPERABLE FROM BOTH SIDES OF DOOR. MINIMUM SIZE: 18" X 18". 4) REFERENCE OTHER SECTIONS FOR CEILING/ WALL ACCESS PANELS. F. BACKDRAFT DAMPERS: PROVIDE COUNTER WEIGHT TYPE BACKDRAFT DAMPERS IN ALL DUCTS OPENING TO THE OUTSIDE RUSKIN MODEL CBS-7 OR APPROVED EQUAL. 57. FIRE PROTECTION DESIGN/BUILD REQUIREMENTS: A. PROVIDE AN AUTOMATIC SPRINKLER SYSTEM. COMPLETE DRAWINGS, SPECIFICATIONS, AND DETAILS SHALL BE SUBMITTED BY THE FIRE SPRINKLER DESIGN-BUILD CONTRACTOR. B. THE FIRE SPRINKLER CONTRACTOR SHALL SERVE AS THE ENGINEER OF RECORD FOR ALL WORK PERFORMED UNDER THIS DIVISION. IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, (AHJ) SUBMIT COMPLETE FIRE SPRINKLER SYSTEM SHOP DRAWINGS AND HYDRAULIC CALCULATIONS, GENERATED BY CONTRACTOR. SHOP DRAWINGS SHALL BE A MINIMUM 1/8” SCALE, AND SHALL SHOW DEVICE AND APPLIANCE LOCATIONS, BUILDING BACKGROUND INFORMATION, ROOM OCCUPANCY DESCRIPTIONS, DOOR SWINGS, FIRE RATINGS AND FIRE PROTECTION SYSTEM LAYOUT AND DETAILS. SHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL BE SEALED BY A PROFESSIONAL ENGINEER OR NICET III LICENSED TECHNICIAN REGISTERED IN THE STATE OF COLORADO. SUBMIT SHOP DRAWINGS AND HYDRAULIC CALCULATIONS TO THE BUILDING AND FIRE DEPARTMENTS AND OBTAIN THEIR APPROVAL BEFORE SUBMISSION TO THE ARCHITECT. C. WHERE REQUIRED BY THE AHJ, ALL SPRINKLER HEADS SHOULD HAVE THE CONNECTING MAIN AND BRANCH PIPE SIZES SHOWN. 1) SHOW THE CONNECTING MAIN AND BRANCH PIPE SIZES FOR ALL SPRINKLER HEADS. 2) CONFORM TO LIGHT HAZARD OCCUPANCY REQUIREMENTS OF NFPA 13D. 3) PROVIDE FLOW TEST INDICATING STATIC AND RESIDUAL PRESSURED DEVELOPED UNDER FIRE FLOW CONDITIONS AS REQUIRED BY AHJ. D. SYSTEM SHALL BE INSTALLED COMPLETE AND OPERATIONAL, INCLUDING WATER FLOW INDICATOR, CONNECTIONS TO ALARM, DRAIN PIPING, IDENTIFICATION SIGNS, ETC. E. WORK SHALL BE PERFORMED BY A QUALIFIED FIRE SPRINKLER INSTALLER WITH A MINIMUM OF FIVE (5) YEARS EXPERIENCE IN SIMILAR INSTALLATIONS. F. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO AND DURING INSTALLATION. G. PROVIDE AN EXTRA STOCK OF SIX (6) SPRINKLER HEADS, THREE (3) OF EACH TYPE, AND A SPRINKLER WRENCH. SPRINKLER HEADS SHALL MATCH IN ADJACENT AREAS. 182 WEST MEADOW DRIVE VAIL, CO 81657 PIETRINI RESIDENCE Project Number - 1428 07/30/14 DESIGN REVIEW COPYRIGHT 2014 B ANZE G EAUDIN (970) 949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 (307) 739-3944 Vail: Denver: Fort Collins: Albuquerque: Jackson: www.bgce.com 09/05/14 PERMIT SET M0.30 MECHANICAL SPECIFICATIONS 03/04/15