HomeMy WebLinkAboutM200 BASEMENT PIPING.pdfNOTES:
SCALE:
BASEMENT PIPING PLAN
3/16" = 1'-0"
T
T
T
T 2/1 T
T
CHR CHS 3/4" HWS/R UP TO .
CHR
CHS
RADIANT
ZONE #3B
RADIANT
ZONE #2B
RADIANT
ZONE #1B
RADIANT
ZONE #2A
RADIANT
ZONE #3A
RADIANT
ZONE #1A
3/4" HWS/R UP TO
.
3/4" HWS/R UP
TO .
3/4" HWS/R UP
TO
3/4" HWS/R UP TO
FLOOR ABOVE.
3/4" HWS/R TO
.
3/4" HWS/R TO
.
3/4" HWS/R TO .
1"HWS/R VALVED AND CAPPED FOR
FUTURE BASEMENT LOOPS.
3/4" HWS/R UP
TO
3/4" HWS/R UP
TO
1-1/2" HWS/R, 2" CHS/R
UP TO FLOOR ABOVE.
3/4" HWS/R, 3/4" CHS/R TO
CAP CHS/R LINES FOR FUTURE USE.
3/4" HWS/R UP TO
1" HWS/R TO
3/4"HWS/R UP TO
2" HWS/R, 2" CHS/R CAPPED, 1" SMS/R,
1-1/2" CW, 1-1/4" HW, 3/4" HWC TO BOILER
PLANT, DOMESTIC WATER ENTRY, AND
DOMESTIC HOT WATER PLANT.
1-1/4" HWS/R, 1-1/2" CHS/R
TO CAP CHS/R
LINES FOR FUTURE USE.
CHR
CHS 3/4" HWS/R TO .
3/4" HWS/R TO .
3/4" HWS/R TO
3/4" HWS/R UP TO .
3/4" HWS/R UP TO .
1"SMS/R TO SNOWMELT
MANIFOLD #6B.
3/4"SMS/R TO
SNOWMELT
MANIFOLD #4B.
3/4"SMS/R UP TO SNOWMELT
MANIFOLD #5B.
3/4"SMS/R UP TO
SNOWMELT
MANIFOLD #5A.
3/4"SMS/R UP TO SNOWMELT
MANIFOLD #4A.
3/4" SMS/R UP TO SNOWMELT
MANIFOLD #3A.
4"W TO MAIN.
I.E. = 8139.00'
2" COMBINED F/CW
FROM MAIN.
I.E. = 8139.50'
4"W TO MAIN.
3/4" SMS/R TO SNOWMELT
MANIFOLDS #3B.
2" COMBINED F/CW
FROM MAIN.
4"G UP.
1-1/4" CW, 1-1/4" HW, 3/4" HWC
UP TO FLOOR ABOVE.
1-1/4" CW, 1-1/4"HW, 3/4" HWC TO BATH
AND LAUNDRY GROUPS, CDBBC.
1-1/4" CW, 1-1/4" HW, 3/4"
HWC TO FLOOR ABOVE.
1" CW, 3/4" HW, 3/4" HWC
TO KITCHEN FIXTURE
GROUP, CDBBC.
1. RE: M4 SERIES FOR PIPING DIAGRAMS.
2. COORDINATE ROUTING OF CONDENSATE DRAIN LINES
WITH ARCHITECT PRIOR TO INSTALLATION.
3. PIPING ON EXTERIOR WALLS TO BE ROUTED IN
FRAMED WALL ON INTERIOR SIDE OF INSULATION.
4. AVOID ROUTING PIPING OVER ELECTRICAL ROOMS OR
ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTINGS WITH DIV. 16 CONTRACTOR.
5. PROVIDE FLEXIBLE PIPE CONNECTIONS TO ALL
MOTORIZED EQUIPMENT.
6. VERIFY ALL EQUIPMENT ACCESS PANELS WITH
MANUFACTURER AND ARCHITECT.
7. PEX PIPING SHALL NOT BE ALLOWED TO PENETRATE
FIRE BARRIERS WHERE FIRE CAULKING IS REQUIRED.
8. ALL BRANCH CHILLED AND HEATING WATER PIPING TO
FAN COIL UNITS SHALL BE 3/4" U.N.O.
9. ALL VALVES SHALL BE INSTALLED WITH ACCESS
PANELS IN HARD-LID CEILINGS.
10. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN
THE CEILING SPACE. UTILIZE JOIST SPACE WHEN
POSSIBLE, ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS, AND ELECTRICAL.
11. ACCESS PANELS SHALL BE 24x24, U.N.O. LOCATIONS
SHOWN ARE APPROXIMATE, EXACT LOCATIONS SHALL
BE COORDINATED WITH THE ARCHITECTS DRAWINGS
AND WITH THE LOCATIONS OF THE EQUIPMENT OR
APPARATUS THAT THEY SERVE.
12. REFER TO THE PLUMBING FIXTURE CONNECTION
SCHEDULE FOR PIPE SIZES TO INDIVIDUAL FIXTURES.
13. NOT ALL REQUIRED CLEANOUTS ARE NECESSARILY
SHOWN ON THESE PLANS. PROVIDE CLEANOUTS ON
WASTE, VENT AND STORM PIPING AS REQUIRED BY
CODE AND FOR REASONABLE MAINTENANCE BASED
ON ACTUAL FIELD INSTALLATION. COORDINATE
LOCATIONS WITH ARCHITECT/ENGINEER.
14. ST PIPING 3", U.N.O.
15. ROUTE DOMESTIC HOT WATER RECIRC TO WITHIN 10
FEET OF ALL HOT WATER FIXTURES. CONNECT WITHIN
5 FEET OF 0.5 GPM AND LOWER FAUCETS.
16. PROVIDE NECESSARY CW SUPPLY TO STEAM
GENERATOR PER MANUFACTURER'S REQUIREMENTS.
17. ROUGH-IN NECESSARY 1/2"CW SUPPLY WITH
SHUT-OFF VALVE, CAPPED FOR FUTURE
HUMIDIFICATION SYSTEMS AT "A" UNIT PER
MANUFACTURER'S REQUIREMENTS. LOCATE AT EACH
FCU LOCATION FROM NEAREST CW MAIN OF 3/4" OR
LARGER SIZE. PROVIDE 1" DRAIN PIPE WITH AIR GAP
TO SAME LOCATION AND ROUTE INDIRECTLY TO
NEAREST FLOOR DRAIN OR SINK TAILPIPE.
G UP TO RANGE.
G UP TO
FIREPLACE.
G UP TO BBQ.
G UP TO FIREPLACE.
G UP TO BBQ.
G UP TO RANGE.
1"CW, 1"HW, 3/4"HWC TO
BATHROOM GROUP, CDBBC.
G
G
G
G TO OUTDOOR FIREPLACE.
ROUTE PIPING BELOW
GRADE I.A.W. 2012 IFGC,
BREAK GRADE AS
REQUIRED.
G
SPACE RESERVED
FOR COMBINED
FIRE/DOMESTIC
WATER ENTRIES.
SPACE RESERVED FOR COMBINED
FIRE/DOMESTIC WATER ENTRIES.
G UP.
G
G
G
1"SMS/R UP TO SNOWMELT
MANIFOLD #6A.
G TO OUTDOOR
FIREPLACE.
G TO BOILERS.
3/4" SMS/R UP.
2"CHS/R CAPPED AND VALVED
FOR FUTURE CHILLER PLANT
INSTALLATION.
CHS
CHR
4"ø RADON PIPE RISER.
4"ø RADON PIPE UP. STUB
PIPING INTO SUB-SLAB
ASSEMBLY I.A.W. 2012 IRC,
APPENDIX F, AF103.6.
4"ø RADON PIPE UP. STUB PIPING
INTO SUB-SLAB ASSEMBLY I.A.W.
2012 IRC, APPENDIX F, AF103.6.
1-1/2" SMS/R UP TO SNOWMELT
MANIFOLDS #1A & 2A
1-1/2" SMS/R UP TO SNOWMELT
MANIFOLDS #1B & 2B.
RADIANT
ZONE #4B
P1
P1
P1
2" HWS/R, 2" SMS/R TO
BOILER PLANT.
1-1/2" CW, 1-1/4"HW, 3/4"HWC TO
DOMESTIC WATER ENTRY AND
DOMESTIC HOT WATER PLANT.
G UP TO BOILERS.
1-1/2" HWS/R, 3/4"
SMS/R UP.
G UP.
3/4"
ROUTE PIPING BELOW GRADE,
I.A.W. 2012 IFGC; BREAK GRADE
AS REQUIRED.
3"V UP AND CAPPED FOR FUTURE
EXTENSION.
2/1
4"W TO BATH GROUP, CDBBC.
4"W UP.
2-1/2"V DN. ROUTE TO 3"V UP, CDBBC.
2"PW UP TO GRAVITY MAIN.
1
FLAG NOTES:
2
3
T
3"W UP TO KITCHEN
GROUP; CDBBC.
2
2
2
3
3
2"PW UP TO GRAVITY MAIN.
2
2
1
2
T V
2"V DN.
3"V CAPPED FOR
FUTURE EXTENSION.
3"V UP.
3"W UP TO KITCHEN
GROUP ABOVE.
3/4" HWS/R TO
1
3
3
1-1/4" HWS/R
UP TO
SMS
SMR
HWR
HWS
SMS SMR SMS
SMR
HWR
HWS
HWR
HWS
SMS
SMR
SMS
SMR
HWR
HWS
HWR
HWS
SMS
SMR
SMS
SMR
SMS
SMR
W
W
W
W
W W
W
3/4"
3/4"
3/4"
3/4"
1-1/4"
1"
3/4"
3/4"
3/4"
3/4"
1"
1" 3/4" 3/4" 1-1/4"
3/4"
1-1/4"
3/4"
3/4"
2"
2"
1-14"
1-1/4"
1"
1"
3/4"
1-1/2"
1-1/2"
3/4"
3/4"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/4"
4"
4" 4"
4"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
1-1/4"
1-1/4"
1
3/4"
1-1/4"
1-1/4"
4"G UP.
2"
2" RADIANT
ZONE #4A
4
4
1-1/4" HWS/R AND 1-1/4"CHS/R VALVED
AND CAPPED FOR FUTURE BASEMENT
LOADS.
1
1-1/4"
1"
P1 1-1/4"
1-1/4" CW, 1-1/4"HW, 3/4" HWC TO
BATHROOM GROUP, CDBBC.
3/4"CW, 3/4"HW, 3/4"HWC TO
LAUNDRY GROUP, CDBBC.
1"CW, 1"HW, 3/4"HWC TO BATHROOM
GROUP, CDBBC.
CHS CHR 3/4"CW UP TO HB.
3/4"CW UP
TO HB.
ST
3"
ST 3"
ST
3"
3"ST TO MAIN.
3"ST TO MAIN.
3"ST TO P9, TYP.
3"ST TO MAIN.
S:\BGProjects\9511.00 182 West Meadow Drive Duplex\Cad\BGCE CAD\951100M200.dwg Printed By: cadd-drp February 06, 2015 - 11:33am LC-XXX
COPYRIGHT 2014
B
ANZE
G
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
MERIBEL CORP. RESIDENCE
Project Number - 1428
1650 Fallridge Road, Suite C-1
Vail, Colorado 81657
f.(970) 476-4901 p.(970)476-6342
182 WEST MEADOW DRIVE
VAIL, CO 81657
11/10/14
90% CD SET
09/05/14
PERMIT SET
7/30/14
DESIGN REVIEW
01/06/15
CD SET
M2.00
BASEMENT
PIPING PLAN
04/15/15