HomeMy WebLinkAboutM401 DIAGRAMS.pdfREQUIRED.
CABLE OR AS
24" STANDARD
SUPPLY DIFFUSER BALANCE DAMPERS
ADJUSTS WITH 1/4" NUTDRIVER
SPECIFY OPTIONAL SCREWDRIVER
TIP IF LESS THAN 3/8" CLEAR
ACCESS.
NO SCALE
ROUND
DAMPER
PLENUM
ADJUSTABLE
MOUNTING CLAMP
DIFFUSER
TAKE-OFF
AS REQ.
INSULATED SUPPLY
AIR PLENUM.
2-WAY COIL PIPING DIAGRAM
NO SCALE
COIL
:
1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT CONTAINING
FANS OR COMPRESSORS, NOT REQ'D FOR EQUIPMENT SUCH AS
DUCT COILS.
2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER ENTERS
MOST DOWNSTREAM COIL, LEAVES MOST UPSTREAM COIL).
3. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION.
4. 2-WAY VALVE NORMALLY OPEN FOR HEATING AND NORMALLY
CLOSED FOR COOLING.
STRAINER WITH
BLOWDOWN
AND CAP.
MANUAL AIR VENT
AT HIGHEST POINT
IN PIPING.
RETURN
SUPPLY
THRU ROOF DIAGRAM
DRYER VENT
NO SCALE
STORM COLLAR/
COUNTER
FLASHING. SEAL
TO DUCT.
MEMBRANE,
INSULATION,
FLASHING,
ETC.
LONG RADIUS ELBOW.
FULLY WELDED CURB CAP,
SIMILAR TO TRANSITION.
TIGHT TO, BUT NOT
FASTENED TO DUCT.
PREFAB, INSULATED
ROOF CURB WITH
TREATED WOOD
NAILER.
SUPPORT DUCT FROM
STRUCTURE.
DRYER VENT CAP W/
BACKDRAFT DAMPER.
COIL PIPING DIAGRAM
NO SCALE
:
1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT CONTAINING
FANS OR COMPRESSORS, NOT REQ'D FOR EQUIPMENT SUCH AS
DUCT COILS.
2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER ENTERS
MOST DOWNSTREAM COIL, LEAVES MOST UPSTREAM COIL).
3. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION.
4. 3-WAY VALVE WITH COIL RETURN PIPED TO NORMALLY OPEN PORT
FOR HEATING AND NORMALLY CLOSED PORT FOR COOLING.
MANUAL AIR VENT
AT HIGHEST POINT
IN PIPING.
STRAINER WITH
BLOWDOWN
VALVE AND CAP.
SUPPLY
RETURN
3-WAY (DIVERTING VALVE)
SNOWMELT HEAT EXCHANGER AND PUMP PIPING DIAGRAM
NO SCALE
SMS
SMS
SMR
SMR
HWR
TO HEATING
WATER SYSTEM.
HEAT EXCHANGER
SNOWMELT PUMP, P-6, SUPPORT FROM WALL
OR FLOOR AS REQUIRED.
ROUTE PIPE INDIRECT TO
FLOOR DRAIN.
EXPANSION TANK.
HOSE END VALVE FOR GLYCOL
FILL.
AIR PURGER ASSEMBLY.
SMS/SMR
HWS
SNOWMELT CONNECTION: STAIR TO WALK DIAGRAM
NO SCALE
9" O.C. TYP. FOR ALL
LANDINGS & WALKS.
HYDRONIC SNOWMELT
TUBING.
6" O.C. TYP. FOR ALL
STAIRS.
D
DOMESTIC WATER HEATER PIPING DIAGRAM
NO SCALE
A
HWR
HWS
S
(SIDEARM)
HW TO FIXTURES.
COLD WATER SUPPLY.
HWC FROM FIXTURES.
DIAPHRAGM TYP.
EXPANSION TANK.
AMTROL OR EQUIV.
RELIEF VALVE, PIPE
INDIRECT TO FLOOR
DRAIN.
DOMESTIC HOT
WATER RECIRC
PUMP, P-4.
WATER HEATER.
2" HWS/R, TYP.
D
A
HWR
HWS
S 3/4"
E
F
B
J
G A D
GOOSENECK DIAGRAM
NO SCALE
135°
SPOT WELD REINFORCING
ANGLE.
NUT & BOLT.
BIRD
SCREEN
FRAME.
DUCT SIZE
PLUS 25%.
1/4" SCREEN.
20" MIN.
FLASHING AND
COUNTER
FLASHING.
12" MIN.
14" MIN.
COOR'D ROOF PENETRATION
WITH ROOF MANUFACTURER.
H
GAS PIPING ONE-LINE DIAGRAM
NO SCALE C
M
0.5 PSI
DISCHARGE.
1-1/4"
1-1/4"
3/4"
1,973 CFH,
205 FT, 4"
BOILER ,
399 MBH/493 CFH
BOILER ,
399 MBH/493 CFH
BOILER ,
399 MBH/493 CFH
85 FT, 1,479
CFH, 2-1/2"
1-1/2" TO
EACH
BOILER
KITCHEN RANGE
90 MBH/112 CFH
BBQ
90 MBH/112 CFH
494 CFH, 2"
140 FT, 1"
382 CFH, 2"
160 FT,
1-1/4"
270 CFH
LIVING RM FP
115 MBH/145 CFH
OUTDOOR
FP
100 MBH/125 CFH
205 FT,
3/4"
170 FT,
1-1/4"
PROVIDE AUTOMATIC
SHUT-OFF CONTROL
WITH MAX. 30 MIN.
TIMER.
:
1. SCH. 40 METALLIC PIPE.
2. 0.3 IN. W.C. AP.
3. RESIDENCES A AND B HAVE SAME GAS
ROUTING; WORST CASE PIPE LENGTHS
TO EACH FIXTURE USED.
SINGLE BLADE
DAMPER IF H<8"
OPPOSED BLADE
DAMPER IF H>=8"
NOTE:
CEILING DIFFUSER
SHOWN. FLOOR
DIFFUSER SIMILAR.
END BEARING
GAS UTILITY
METER/PRV
ASSEMBLY.
S:\BGProjects\9511.00 182 West Meadow Drive Duplex\Cad\BGCE CAD\951100M401.dwg Printed By: cadd-drp February 06, 2015 - 11:35am LC-XXX
COPYRIGHT 2014
B
ANZE
G
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
MERIBEL CORP. RESIDENCE
Project Number - 1428
1650 Fallridge Road, Suite C-1
Vail, Colorado 81657
f.(970) 476-4901 p.(970)476-6342
182 WEST MEADOW DRIVE
VAIL, CO 81657
11/10/14
90% CD SET
09/05/14
PERMIT SET
7/30/14
DESIGN REVIEW
01/06/15
CD SET
M4.01
MECHANICAL
DIAGRAMS
04/15/15