HomeMy WebLinkAboutM500 CONTROLS.pdfGENERAL CONTROLS NOTES: SCALE: 3 CONTROL SYSTEM ARCHITECTURE (BACNET) NONE BACNET WEB SERVER SUPERVISORY NETWORK CONTROLLER (TYP.) UNITARY EQUIPMENT CONTROLLER (TYP.) BACNET COMM BUS (TYP.) GENERIC I/O CONTROLLER (TYP.) INTERNET (BY OTHERS) LAN (BY OTHERS) DESCRIPTION: THE BUILDING CONTROL SYSTEM (BCS) SHALL CONSIST OF AN ASHRAE STANDARD 134 COMPLIANT (BACNET COMPATIBLE) FOR CONTROL OF HVAC & PLUMBING SYSTEMS WITH ALL STATUS FEEDBACK AND OCCUPANT CONTROL AVAILABLE THROUGH THE WEB INTERFACE. MAJOR COMPONENTS INCLUDING THE BOILERS AND ERV SHALL BE PROVIDED BY MANUFACTURER WITH BCS COMPATIBLE CONTROLLERS WITH ALL AVAILABLE INFORMATION WITHIN COMMUNICATED TO AND GRAPHICALLY REPRESENTED IN THE BCS. CONTROLS CONTRACTOR TO COORDINATE WITH LOW-VOLTAGE CONTRACTOR. COMMUNICATION PROTOCOLS BETWEEN LOW-VOLTAGE CONTROL SYSTEM AND HVAC CONTROL SYSTEM TO BE EITHER RS-232 FOR STANDALONE OR MODBUS FOR DDC. REMOTE ACCESS: PROVIDE REMOTE ACCESS VIA WEB BASED INTERFACE. REMOTE ACCESS SHALL HAVE, AT A MINIMUM, THE FOLLOWING VARIOUS LEVELS OF CONTROL CAPABILITY BASED ON CREDENTIALS PROVIDED DURING LOG-IN: 1. VIEW ONLY - NO ADJUSTMENT CAPABILITIES. PROVIDE 'VIEW ONLY' REMOTE ACCESS LOCATION AND CREDENTIALS TO ENGINEER AND COMMISSIONING AGENT UPON STARTUP OF SYSTEM. CREDENTIALS PROVIDED TO ENGINEER AND COMMISSIONING AGENT SHALL NOT EXPIRE DURING THE PERIOD OF THE WARRANTY. 2. OCCUPANT LEVEL - SIMILAR LEVEL OF CONTROL TO THAT AVAILABLE VIA HOME AUTOMATION TOUCH SCREENS. 3. TECHNICIAN LEVEL - FULL CONTROL, TROUBLESHOOTING, ADJUSTMENT, AND PROGRAMMING CAPABILITIES. BCS SHALL UTILIZE REMOTE ACCESS TO THE WEB TO AUTOMATICALLY CALIBRATE ITS INTERNAL TIME-OF-YEAR CLOCK ON A MONTHLY BASIS WITH THE OFFICIAL WORLD TIME. GRAPHICS: AS INDICATED IN THE POINTS LISTS, ALL BCS POINTS SHALL BE REPRESENTED BY GRAPHIC DISPLAY ON THE WEB BASED INTERFACE. ITEMS SUCH AS PUMPS, FANS, CONTROL VALVES, AND DAMPER MOTORS SHALL BE REPRESENTED BY ANIMATED GRAPHIC DISPLAYS. GRAPHICAL FLOOR PLANS SHALL INDICATE AIRSIDE ZONE DESIGNATIONS AS WELL AS THEIR SPACE TEMPERATURE SETPOINT, SPACE TEMPERATURE. BACKGROUND COLOR OF ZONES SHALL BE CHANGED AS FOLLOWS: 1. NONE - SPACE TEMPERATURE WITHIN 3°F OF SETPOINT. 2. RED - SPACE TEMPERATURE GREATER THAN 3°F ABOVE SETPOINT. 3. BLUE -SPACE TEMPERATURE LOWER THAN 3°F BELOW SETPOINT. GRAPHICAL FLOOR PLANS SHALL ALSO INDICATE DE-CENTRALIZED EQUIPMENT BY LOCATION AND DESIGNATION. ANIMATED GRAPHICS ARE NOT REQUIRED ON THE GRAPHICAL FLOOR PLAN SCREEN. ADDITIONAL INFORMATION FOR A GIVEN ZONE OR PIECE OF EQUIPMENT SHALL BE EASILY ACCESSED BY DOUBLE-CLICKING ITS ASSOCIATED FLOOR PLAN GRAPHIC. LINE VOLTAGE POWER REQUIREMENTS FOR CONTROLS SYSTEM HAVE BEEN ESTIMATED ON PLAN; CONTROLS CONTRACTOR TO FIELD COORDINATE WITH DIV. 26 CONTRACTOR FOR REQUIREMENTS. DIV. 26 CONTRACTOR TO INCLUDE CONTROLS POWER IN BASE BID. DDC SYSTEM SHALL ALSO BE EXPANDABLE TO ACCOMMODATE FUTURE COOLING HVAC SYSTEMS INSTALLATION. EXHAUST FANS SERVING THE MECHANICAL, ELECTRICAL, AND ELEVATOR MACHINE ROOMS SHALL BE CONTROLLED BY INDIVIDUAL SPACE MOUNTED COOLING THERMOSTAT SET AT 80°F (ADJ). UPON A RISE IN SPACE TEMPERATURE ABOVE SETPOINT PLUS DIFFERENTIAL, EXHAUST FANS SHALL ENABLE. CONVERSELY, UPON A DECREASE IN SPACE TEMPERATURE BELOW SETPOINT PLUS DIFFERENTIAL, EXHAUST FANS SHALL DISABLE. THESE FANS ARE NOT INTENDED TO BE ON THE DDC SYSTEM. SCALE: 5 THERMOSTAT CONTROL SCHEMATIC NONE EXHAUST FAN UNIT MOTOR STARTER MS TSTAT ANALOG INPUT TO BCS CONTROLS LEGEND TEMP SENSOR AI AO BI BO ANALOG OUTPUT FROM BCS BINARY INPUT TO BCS BINARY OUTPUT FROM BCS CARBON MONOXIDE SENSOR CARBON DIOXIDE SENSOR CURRENT SWITCH FLOW SWITCH HUMIDITY SENSOR MOTOR STARTER DAMPER MOTOR RELAY SMOKE DETECTOR TEMPERATURE SENSOR VARIABLE FREQUENCY DRIVE CP FREEZSTAT SENSOR - THERMOSTAT SWITCH SPACE MOUNTED STAT EQUIPMENT MANUFACTURER'S CONTROL PANEL DIFFERENTIAL PRESSURE SWITCH DIFFERENTIAL PRESSURE TRANSDUCER FLOW SENSOR AIRFLOW MEASURING STATION AFMS CO CO2 CS DPS DPT FRZ FS F HE MS DM RLY S SMK TE TSTAT VFD EMERGENCY POWER OFF EPO EXHAUST FANS SERVING RESIDENTIAL POWDER ROOMS AND BATHROOMS SHALL ENABLE UPON CLOSE OF A WALL MOUNTED SWITCH. CONVERSELY, FAN SHALL DISABLE UPON OPEN OF THE SWITCH. WALL SWITCH SCALE: 4 SWITCH CONTROL SCHEMATIC NONE EXHAUST FAN WALL SCALE: 1 GLOBAL CONTROLS COMPONENTS NONE TE HE AI AI OSA TEMP OSA HUMIDITY AI OSA CO2 CONCENTRATION CO2 SCALE: 2 PUMP CONTROL SCHEMATIC NO SCALE SUMP AND SEWAGE EJECTOR PUMPS SHALL CYCLE ON WHEN PUMP ON LEVEL IS REACHED AND OFF WHEN PUMP OFF LEVEL IS REACHED. PUMPS SHALL GO INTO AUDIBLE ALARM WHEN ALARM ON/HIGH WATER LEVEL IS REACHED. PUMPS SP-1 ARE INTENDED FOR PRIMARY/STANDBY OPERATION; ONE PUMP IS TO RUN AT A TIME, THE STANDBY ONLY COMES ON IF PRIMARY FAILS. STORM VAULT SUMP PUMPS TO HAVE FLOAT SWITCHES INSTALLED AT LEVELS SHOWN IN CIVIL DOCUMENTS. PUMPS SP-4 ARE INTENDED FOR PRIMARY/STANDBY OPERATION; ONE PUMP IS TO RUN AT A TIME, THE STANDBY ONLY COMES ON IF PRIMARY FAILS. CONTROL PANEL TO HAVE OUTPUTS FOR CONNECTION TO DDC SYSTEM. IF HIGH WATER ALARM IS SIGNALED, A SIGNAL WILL BE SENT THROUGH THE CONTROLS SYSTEM TO ALERT THE BUILDING OPERATOR. SCALE: 6 VENTILATOR CONTROLS SCHEMATIC NO SCALE HEAT RECOVERY HEAT RECOVERY VENTILATOR SHALL OPERATE CONTINUOUSLY VIA 'ON' POSITION OF MANUAL WALL SWITCH. THE UNIT SHALL OPERATE VIA MANUFACTURER'SFROST CONTROLS FOR A SET AMOUNT OF TIME TO AVOID FROST CONDITIONS. R.A. O.S.A. S.A. EXH HRV CP BO S:\BGProjects\9511.00 182 West Meadow Drive Duplex\Cad\BGCE CAD\951100M500.dwg Printed By: cadd-txc January 06, 2015 - 10:25am LC-XXX COPYRIGHT 2014 B ANZE G EAUDIN (970) 949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 (307) 739-3944 Vail: Denver: Fort Collins: Albuquerque: Jackson: www.bgce.com MERIBEL CORP. RESIDENCE Project Number - 1428 1650 Fallridge Road, Suite C-1 Vail, Colorado 81657 f.(970) 476-4901 p.(970)476-6342 182 WEST MEADOW DRIVE VAIL, CO 81657 11/10/14 90% CD SET 09/05/14 PERMIT SET 7/30/14 DESIGN REVIEW 01/06/15 CD SET M5.00 MECHANICAL CONTROLS 04/15/15