HomeMy WebLinkAboutM501 CONTROLS.pdfHEATING WATER SUPPLY TEMPERATURE SETPOINT SHALL BE RESET FROM 140°F @ 30°F OSA TO 100°F @ 60°F OSA. PROVIDE AN OUTDOOR AIR SENSOR LOCATED ON THE NORTH EXPOSURE. CONTROL SHALL ABANDON THE ABOVE OSA RESET CURVE DURING DEMAND FOR DHW PRODUCTION TO PROVIDE 180°F HWS SETPOINT. HWS SETPOINT SHALL BE MAINTAINED BY MODULATING AND STAGING ON BOILERS IN SEQUENCE. BOILER CONTROL VALVE SHALL BE OPEN AND ASSOCIATED BOILER CIRC PUMP SHALL BE ENABLED WHEN ASSOCIATED BOILER IS ENABLED AND CLOSED/OFF WHEN ASSOCIATED BOILER IS DISABLED. ALL BOILERS SHALL OPERATE VIA FACTORY MOUNTED CONTROLS TO PROVIDE HWS SETPOINT. UPON A CALL FOR HEAT FROM ANY SPACE LOAD, THE LOAD'S ASSOCIATED HEATING WATER CIRCULATION PUMP(S) SHALL RUN. THE PUMPS SHALL STOP WHEN A CALL FOR HEAT IS NO LONGER PRESENT. BOILER INTERNAL CONTROLS SHALL BE INTERLOCKED WITH ASSOCIATED BOILER CIRCULATING PUMP. WHEN BOILER IS ENABLED DUE TO CALL FOR HEAT FROM SPACE LOAD, CIRCULATING PUMP SHALL START. CONVERSELY, WHEN BOILER IS DISABLED, CIRCULATING PUMP SHALL STOP. UPON A CALL FOR HEAT FROM A TANK MOUNTED AQUASTAT SET AT 120°F(ADJ.) ON THE DOMESTIC HOT WATER STORAGE TANK, THE DHW INJECTION PUMP AND ASSOCIATED BOILER SHALL RUN AND BOILER CIRCULATING PUMP SHALL BE DISABLED. DOMESTIC INJECTION PUMP AND BOILER SHALL STOP AND BOILER CIRCULATION PUMP SHALL RESUME NORMAL OPERATION WHEN A CALL FOR HEAT IS NO LONGER PRESENT. PROVIDE BOILER SHUTDOWN SWITCH LOCATED AT BOILER ROOM EXIT DOORS. SHUTDOWN SYSTEM SHALL COMPLY WITH ASME-CDS-1. DIVISION 23 CONTRACTOR SHALL PROVIDE THE SWITCH AND ALL REQUIRED CONTROL WIRING. ALL WIRING SHALL BE IN CONDUIT. A CLEAR POLYCARBONATE HINGED COVER SHALL BE PROVIDED TO PREVENT ACCIDENTAL OPERATION OF SWITCH. SWITCH SHALL HAVE ENGRAVED NAMEPLATES TO IDENTITY SWITCH AS "BOILER EMERGENCY SHUTDOWN". DIVISION 23 CONTROLS CONTRACTOR SHALL COORDINATE WITH DIVISION 26 FOR SAFE SHUTDOWN OF BOILERS. UPON A CALL FOR FIRST STAGE HEAT FROM A ROOM SPACE TEMPERATURE SENSOR SET AT 68°F (ADJ.), TELESTAT(S) OR CONTROL VALVES IN ASSOCIATED RADIANT FLOOR MANIFOLD SHALL OPEN TO ALLOW WATER TO FLOW THROUGH THE RESPECTIVE ZONE. TELESTATS AND CONTROL VALVES SHALL BE CLOSED WHEN A CALL FOR HEAT IS NO LONGER PRESENT. FOR A RADIANT ZONE WITHIN A FORCED AIR ZONE, RADIANT FLOOR HEATING SHALL BE LOCKED OUT WHEN A ZONE IS IN COOLING MODE. FOR A RADIANT ZONE WITH WOOD FLOORING, AN IN-FLOOR TEMPERATURE SENSOR IN EACH ZONE SHALL CLOSE THE CONTROL VALVE WHEN WOOD FLOORING TEMPERATURE EXCEEDS 80°F (ADJ). UPON A CALL FROM AN IN-SLAB TEMPERATURE/MOISTURE SENSOR (TEKMAR 090 OR EQUIVALENT), SNOWMELT CIRCULATION PUMP SHALL RUN IN ACCORDANCE WITH MANUFACTURER'S INTERNAL CONTROLS TO MAINTAIN CONSTANT PRESSURE AND SNOWMELT INJECTION PUMP SHALL CYCLE TO MAINTAIN A SNOWMELT SUPPLY TEMPERATURE OF 120°F (ADJ.); CONTROL VALVES FOR ASSOCIATED ZONES MATCHED WITH THE SENSOR SHALL OPEN. PUMPS SHALL BE OFF AND CONTROL VALVES CLOSED WHEN A CALL FOR HEAT IS NO LONGER PRESENT. BO BI AO BO AI BI TE BO BI AO BO BI BO BI AO BO BI BO BI AI AI AI BO BI BO BI P-1 P-1 S S P-1 S P-3 TO WATER HEATERS. TO FAN COIL UNITS & RADIANT ZONES TE P-2 P-2 CP CP CP TE TE AIR VENTS AT ALL HIGH POINTS, TYP. ROUTE INDIRECTLY TO CONDENSATE NEUTRALIZER AND ROUTE OUTLET DRAIN LINE FROM CONDENSATE NEUTRALIZER TO MECHANICAL ROOM FLOOR DRAIN, TYP. 4. DOWNWARD GAS FLOW DIRECTION INTO DIRTLEG TEE, TYP. 2"G TO BOILER, TYP. AIR SEPARATOR, SPIROVENT. EXPANSION TANK, TACO CA-215. TO GLYCOL FEEDER. TO SNOWMELT HEAT EXCHANGER P-5 BO BI G G G 2" 2" 2" 2" 2" 2" 2" 2" 2" 2" 3" 3" SCALE: BOILER SYSTEM PIPING DIAGRAM AND CONTROL SCHEMATIC NO SCALE 1. COALESCING TYPE AIR SEPARATOR WITH WITH AUTOMATIC RELIEF FLOAT. 1 PIPE AND SMALLER: SPIROTHERM SPIROVENT JR, B&G EASB JR, OR TACO VORTEC. 2" PIPE AND LARGER: SPIROTHERM SPIROVENT SR, B&G CRS, OR TACO 4900 OR EQUIVALENT. 2. EXTEND DRAIN TO NEAREST FLOOR SINK FOR INDIRECT CONNECTION. DO NOT COMBINE DRAIN WITH OTHERS. 3. EXTEND ALL SAFETY RELIEF VALVES TO DRAIN PER VALVE MFG's RECOMMENDATIONS WITHOUT PIPE BELLIES OR UPWARD SLOPE. DO NOT COMBINE WITH OTHERS. 4. INDICATES UNION OR FLANGE CONNECTION FOR SERVICE PURPOSES. DIELECTRIC UNIONS NOT PERMITTED EXCEPT AT DOMESTIC WATER CONNECTIONS TO WATER HEATERS. PROVIDE DIELECTRIC NIPPLES OR FLANGES AT FERROUS TO NON-FERROUS PIPING MATERIAL TRANSITIONS. 5. THREE-WAY VALVE WITH PORTS IDENTIFIED: C = COMMON NC = NORMALLY CLOSED NO = NORMALLY OPEN 6. DIAGRAM IS SCHEMATIC IN NATURE. NOT ALL APPURTENANCES REQ'D ARE NECESSARILY SHOWN. PROVIDE SYSTEM ACCESS, VALVING, AND DRAINAGE AS REQ'D FOR PROPER SYSTEM MAINTENANCE AND PURGE/FILL PROCEDURES. 7. PROVIDE MANUAL AIR VENT AT ALL HIGH POINTS AND MANUAL DRAIN VALVES AT ALL LOW POINTS. PIPE DRAIN VALVES TO A SUITABLE LOCATION WHEN DRAINS ARE IN A LOCATION IN WHICH THEIR DRAINAGE WILL BE A NUISANCE OR CAUSE DAMAGE. 8. PROVIDE 4" HIGH CONCRETE SHOP KEEPING PAD IN ADDITION TO MFG's BASE FOR ALL FLOOR MOUNTED EQUIPMENT. COORDINATE EXACT PAD SIZES AND LOCATIONS WITH PIPING SHOP DRAWINGS AND CONCRETE CONTRACTOR. 9. ALL ISOLATION VALVES SHALL BE FULL PORT VALVES EQUIVALENT TO PIPE SIZE SHOWN. 10. ROUTE COMBUSTION EQUIPMENT CONDENSATE DRAIN LINES AND INDIRECT CONNECT TO CONDENSATE NEUTRALIZATION BASIN SIZED PER COMBUSTION EQUIPMENT MFG's RECOMMENDATIONS. INDIRECT CONNECT BASIN OUTLET TO NEAREST WASTE RECEPTOR. 11. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL DEVICE REQUIREMENTS SUCH AS PRESSURE AND TEMPERATURE PICKUP LOCATIONS. 12. PROVIDE DOWNWARD GAS FLOW INTO SEDIMENT/DRIP LEG TEES. PLANT PIPING NOTES: S:\BGProjects\9511.00 182 West Meadow Drive Duplex\Cad\BGCE CAD\951100M501.dwg Printed By: cadd-txc January 06, 2015 - 10:26am LC-XXX COPYRIGHT 2014 B ANZE G EAUDIN (970) 949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 (307) 739-3944 Vail: Denver: Fort Collins: Albuquerque: Jackson: www.bgce.com MERIBEL CORP. RESIDENCE Project Number - 1428 1650 Fallridge Road, Suite C-1 Vail, Colorado 81657 f.(970) 476-4901 p.(970)476-6342 182 WEST MEADOW DRIVE VAIL, CO 81657 11/10/14 90% CD SET 09/05/14 PERMIT SET 7/30/14 DESIGN REVIEW 01/06/15 CD SET M5.01 MECHANICAL CONTROLS 04/15/15