Loading...
HomeMy WebLinkAbout07 E10 Legend, Spec & Detail .pdfPROJECT: ANTLERS CORRIDOR LIGHTING ENGINEER: SOH PROJECT #: 14017 VOLTAGE: 120V, 1P, 2W MOUNTING: EXISTING MAINS: 40A MLO TYPE: EXISTING AIC: 10K PHASE PHASE DESCRIPTION A B BKR P CIR CIR P BKR A B DESCRIPTION EAST BREEZEWAY LTGS 500 20 1 1 2 1 20 500 LOBBY SCONCES WEST BREEZEWAY LTGS 500 20 1 3 4 1 20 500 4TH LEVEL BREEZEWAY LTG LOWER LEVEL DOWNLIGHTS 476 20 1 5 6 1 20 500 5TH LEVEL BREEZEWAY LTG SPARE 0 20 1 7 8 1 20 500 6TH LEVEL BREEZEWAY LTG SPARE 0 20 1 9 10 0 SPACE SPARE 0 20 1 11 12 0 SPACE SPARE 0 20 1 13 14 0 SPACE SPACE 0 15 16 0 SPACE SPACE 0 17 18 0 SPACE SPACE 0 19 20 0 SPACE SPACE 0 21 22 0 SPACE SPACE 0 23 24 0 SPACE SPACE 0 25 26 0 SPACE SPACE 0 27 28 0 SPACE SPACE 0 29 30 0 SPACE SPACE 0 31 32 0 SPACE SPACE 0 33 34 0 SPACE SPACE 0 35 36 0 SPACE SPACE 0 37 38 0 SPACE SPACE 0 39 40 0 SPACE SPACE 0 41 42 0 SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR: 1.00 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING/CONTINUOUS 3476 29 4345 36 RECEPTACLES 0 0 0 0 MECHANICAL 0 0 0 0 KITCHEN 0 0 0 0 TOTAL 3476 29 4345 36 PANEL EP PROJECT: ANTLERS CORRIDOR LIGHTING ENGINEER: SOH PROJECT #: 14017 VOLTAGE: 120/208V, 3P, 4W MOUNTING: EXISTING MAINS: 125A MLO TYPE: EXISTING AIC: 10K PHASE PHASE DESCRIPTION A B C BKR P CIR CIR P BKR A B C DESCRIPTION NE BREEZWAY LTG/ENTRY 1000 20 1 1 2 1 20 1000 NORTH ENTRY LTG LOBBY RAMP LTG 1000 20 1 3 4 1 20 1000 FOUNTAIN LTG NW BREEZWAY LTG 1000 20 1 5 6 1 20 0 SPACE LOWER LEVEL STRIP LTS 1053 20 1 7 8 1 20 0 SPACE SPARE 0 20 1 9 10 1 20 0 SPACE COIL VOLTAGE 100 20 1 11 12 1 20 1000 STREET LIGHT SPARE 0 20 1 13 14 1 20 1000 STREET LIGHT SPACE 0 15 16 1 20 0 SPACE SPACE 0 17 18 0 SPACE SPACE 0 19 20 0 SPACE SPACE 0 21 22 0 SPACE SPACE 0 23 24 0 SPACE SPACE 0 25 26 0 SPACE SPACE 0 27 28 0 SPACE SPACE 0 29 30 0 SPACE SPACE 0 31 32 0 SPACE SPACE 0 33 34 0 SPACE SPACE 0 35 36 0 SPACE SPACE 0 37 38 0 SPACE SPACE 0 39 40 0 SPACE 0 41 42 1 40 3476 PANEL EP LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR: 1.00 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING/CONTINUOUS 11529 32 14411 40 RECEPTACLES 100 0 100 0 MECHANICAL 0 0 0 0 KITCHEN 0 0 0 0 TOTAL 11629 32 14511 40 PANEL SA 2011 and State Code Special Inspection shall not be required but building department inspection of penetrations is required 09/22/14