Load Calc 408 Vantage Point.pdf
Load Calc 408 Vantage Point, Vail, CO 1707 sq ft x 3W/ft = 5121W 2 small appliance x 1500W = 3000W Dishwasher 1200W Microwave 1000W Disposal 500W Refrigerator 1200W Range 8000W Laundry 1500W Dryer 5000W Water heater 5000W Sauna 1500W Total 33,021W 33,021W – 8,000W = 25,021W 25,021W x 40% =- 10,008W 10,008W + 8,000W = 18,008W Electric heat – 45ft x 250W/ft = 11,250W 18,008W + 11,250W = 29,258W 29,258W / 240V = 122A total adjusted service load Existing service is 150A