HomeMy WebLinkAboutB14-0366 Balance Report.pdfTEST, ADJUST AND BALANCE REPORT
\3 -I~ -03 "~
PROJECT
SMARTWOOL VAIL
#1115
PREPARED FOR
AMERICAN PLUMBING,
HEATING, & SOLAR INC.
REPORT ISSUE DATE
11/17/2014
PREPARED BY
HVAC TAB lie
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB lie
TEST, ADJUST AND BALANCE REPORT
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF
SYSTEM PERFORMANCE AND WAS OBTAINED IN COMPLIANCE WITH
NBC PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN
REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS
REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TO THE
EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED THROUGH-
OUT THIS SURVEY.
THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN
COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING,
ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE
PROJECT SPECIFICATIONS.
CERTIFIEDBY:M~ DATE:
THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEA&LREMENTS
ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR
TESTING, ADUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY: DATE: -----------------
HVAC TAB lie WARRANTS IHA T THE AIR AND HYDRONIC SYSTEM
EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFIED LEVELS
AS SHOWN WITHIN THIS REPORT, AT AND ONLY AT THIS TIME. HVAC TAB lie
MAKES NO OTHER WARRANTIES, ST A TED OR IMPLIED, CONCERNING THE
CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS
EQUIPMENT PASS THIS TIME.
CERTIFIED
Michael T. Richardson
HVAC TAB, lie Page: 1
#13--084-03 Expires: 2/2212015
NATIONAL BA!ANCING COUNCIL
HVAC TAB lie
DATE: 11/17/2014
PROJECT : SMARTWOOL VAIL
PROJECT ALTITUDE: "HG
INSTRUMENT/ SERIAL# APPLICATION DATE OF USE
SHORTRIDGE ADM-870C I #M0921 l AIR FLOW READINGS 11/17/2014
ANEMOMETER#RVA501416001 AIR FLOW READINGS 11/17/2014
SHORTRIDGE FLOW HOOD Alf FLOW READINGS NOT USED
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP I HUMIDITY NOT USED
PITOT TUBE 18" PRES. READINGS NOT USED
PITOT TUBE 24" PRES. READINGS NOT USED
PITOT TUBE 36" PRES. READINGS NOT USED
PITOT TUBE 48" PRES. READINGS NOT USED
SHIMPO TACHOMETER I #CI05B0010 RPM READINGS 11/15/2014
FLUKE 375 I #21290229 VOLT I AMP 11/15/2014
SHORTRIDGE HDM-2501 #W08162 WATER PRES. READINGS NOT USED
ASCROFT I 0-100 PSI I #D068332-06 WATER PRES. READINGS NOT USED
FLUKE 52-11 #99780167 TEMP. READINGS NOT USED
REFRACTOMETER RHA-100 I #RHA-GLYCOL% READINGS NOT USED
100
INSTRUMENT
CAl1IBRATION REPORT
CALIBRATION CALIBRATION
DATE DUE DATE
06/1212014 06101212015
04/1412014 0411412015
* *
0610412014 0610412015
NIA NIA
NIA NIA
NIA NIA
NA NA
0611812014 0611812015
0610412014 0610412015
0611212014 0611212015
* *
021312014 021312015
NIA NIA
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR
TEMPERATURE AND ALTITUDE. PAGE:
HVAC TAB lie
DATE: 11/15/2014
PROJECT: SMARTWOOL VAIL
AIR HANDLER UNIT DATA
MANUFACTURER INTERNATIONAL
ENVIROMENTAL CORP
MODEL HBC1200051645
SERIAL 96-1451-10-1
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1000CFM@0.6"ESP
MIN OSACFM 168 CFM
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
AIRFLOW DATA
SUPPLY CFM 971
OSACFM 169
RETURN CFM 802
F
-0.05" L
T
E
R
NOTES:
AIR APPARATUS
TEST REPORT
SYSTEM: FCU-C2-14
MOTOR NAMEPLATE DATA
MANUFACTURER BALDOR
HP R.P.M. 1/2 1725
PHASE FRAME 1 56
S.F. TYPE 1.25 -
VOLTS AMPS 115/230 8.4/4.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP 3 5/8"
MOTOR BORE 5/8"
FAN DRIVE 1AK54
FAN BORE 3/4"
NO. BEL TS & SIZE 1 I A 25
ROTATION CORRECT
CENTERLINE MOTOR ADJ PULLEY
SPEED+ 2 6 3/4" + 1/2 -1/2 TURNS
TEST DATA INITIAL FINAL
FAN R.P.M. 994 994
VOLTAGE 120 120
AMPERAGE 7.8 7.8
0.02"
PAGE:
HVACTAB lie
DATE: 11/17/2014
PROJECT: SMARTWOOL VAIL
SYSTEM TERMINAL DESIGN
NO TYPE SIZE AK VEL CFM
FCU-C2-14 1 SR 46/2 115
2 SR 46/2 188
3 SR 46/2 188
4 SR 46/2 188
5 SR 46/2 188
6 ---
7 SR 11/11 110
8 SR 11 /11 25
1002
NOTES:
NF DENOTES NOT FOUND
AIR TERMINAL
TEST REPORT
SYSTEM: FCU-C2-14
INITIAL FINAL NOTES
VEL CFM VEL CFM
152 109
246 179
108 185
176 177
196 174
NF NF NOT FOUND
165 113
40 34 DAMPER
r1 ns:Pn
1083 971 TOTAL
PAGE: