HomeMy WebLinkAboutE002.pdfLIGHTING FIXTURE SCHEDULE
PREPARED BY KAZIN & ASSOCIATES
DESCRIPTION OF LUMINAIRE LUMINAIRE SPECIFICATION
ID DESCRIPTION FINISH MOUNTING INFO MANUFACTURER CATALOG NUMBER LAMP(S) VOLTAGE
A
EXISTING RECESSED
DOWNLIGHT TO BE
RELAMPED
EXISTING RECESSED EXISTING RELAMP EXISTING FIXTURE
PHILIPS
19PAR38/F25
3000 DIM RO AF
120
B DECORATIVE PENDANT WHITE
~7' AFF - COORDINATE
MOUNTING HEIGHT WITH
ARCHITECT
TMS LIGHTING HYD0010-B-1-F05 (1) 26W PL-T 120
C RECESSED DOWNLIGHT WHITE RECESSED PRESCOLITE LF6CFH226EBMW26-6CFH-B6 (2) 26W QUAD 120
D 4' FLUORESCENT WRAP WHITE SURFACE COLUMBIA WC4-232-EP120 (2) F32T8 120
G WALL SCONCE WHITE/SATIN
CHROME
6' AFF TO TOP OF FIXTURE EUREKA 3530-SC-WH F.T5.24 120
T1 TRACK LIGHTING WHITE SURFACE CON-TECH
TRACK: LT2 (LENGTH PER PLAN)
+ PENDANT MOUNTING
ACCESSORIES-P (WHITE)
HEADS: CTL603A-P (WHITE)
WRL20 ***PROVIDE QUANTITY OF
HEADS SHOWN ON LIGHTING
PLAN*** PROVIDE (1) 600W,2P
TRACK BREAKER
PHILIPS
19PAR38/F25
3000 DIM RO AF
120
T2 TRACK LIGHTING WHITE WALL - HEIGHT PER ARCHITECT CON-TECH
TRACK: LT2 (LENGTH PER PLAN)
+ PENDANT MOUNTING
ACCESSORIES-P (WHITE)
HEADS: CTL603A-P (WHITE)
WRL20 ***PROVIDE QUANTITY OF
HEADS SHOWN ON LIGHTING
PLAN***
PHILIPS
19PAR38/F25
3000 DIM RO AF
120
NOTES:
1. PROVIDE FLUORESCENT LAMPS RATED 3500K, 85CRI, AND ALL MADE BY THE SAME MANUFACTURER.
2. PROVIDE INTEGRAL DISCONNECT FOR EACH DOUBLE-ENDED FLUORESCENT FIXTURE TO DISCONNECT THE BALLAST FROM THE LAMP SOCKET.
3. PROVIDED HANGERS, ADAPTERS, INSTALLATION KITS, PARTS AND PIECES TO INSTALL THE SPECIFIED FIXTURE IN THE LOCATIONS SHOWN ON THE PLAN.
EXIT AND EMERGENCY LIGHTING FIXTURE SCHEDULE
DESCRIPTION OF LUMINAIRE LUMINAIRE SPECIFICATION
SYMBOL DESCRIPTION FINISH
MOUNTING
INFO
MANUFACTURER CATALOG NUMBER LAMP(S) VOLTAGE
EXTERIOR EMERGENCY
EGRESS LIGHT
WHITE OR
BRONZE
SEE PLAN EXITRONIX
NF3-WB-15L-(WHITE OR BRONZE
- PER ARCHITECT)-G2-CL
15W LED 120/277 INPUT
TO (E)
METER
CENTER
TO (E)
METER
CENTER
P/B
(4 #3/0, 1 #6G) IN EXISTING CONDUIT
(4 #3/0, 1 #6G)2"C
PANEL
NW5
NEW UTILITY
METER
PANEL
NW4
2000A MDP
208Y/120V, 3Ø, 4W
65,000AIC
UTILITY COMPANY
PAD MOUNTED
TRANSFORMER
3[4-300kcmil, 1 #1/0G] (800A) OR EQUAL
800A METER CENTER
208Y/120V, 3Ø, 4W
FAULT CURRENT CALCULATIONS (END OF CONDUCTOR)
LOCATION DESCRIPTION
(@ ISC END)
STARTING ISC
MINIMUM
CONDUCTOR
LENGTH
PHASE
MULTIPLIER
VOLTAGE
# OF
CONDUCTOR
SETS
C VALUE ISC END
@ 2000A MDP 57,400 50 1.73 208 6 24,297 49,324
@ 800A METER CENTER 49,324 30 1.73 208 3 20,868 41,220
@ PANEL NW5 41,220 150 1.73 208 1 12,844 8,238
6[4-400kcmil] (2000A) OR EQUAL
1
PARTIAL ONE-LINE DIAGRAM
NOT TO SCALE
NOTES:
1. EQUIPMENT, WIRING, AND DEVICES SHOWN LIGHT ARE EXISTING
AND SHOWN DARK ARE NEW UNLESS OTHERWISE NOTED.
2. NEW WIRING SHALL BE THHN/THWN-2 INSULATED COPPER
UNLESS OTHERWISE NOTED.
LIGHTING RELAY PANEL
RELAY FED
FROM
CIRCUIT
NUMBER
LOAD
(VA)
LOCATION LOCAL
CONTROL
CONTROL DESCRIPTION
1 NW5 6 300 TRACK LIGHTING PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
2 NW5 6 300 TRACK LIGHTING PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
3 NW5 4 304 RECESSED
DOWNLIGHTS
PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
4 NW5 4 52 PENDANT LIGHTING PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
5 NW5 2 1200 EXTERIOR SIGN PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
6
7
8
4
LIGHTING CONTROL PANEL WITH INTEGRAL
CLOCK. REFERENCE ELECTRICAL
SPECIFICATIONS AND RELAY SCHEDULE
FOR ADDITIONAL REQUIREMENTS.
DIGITAL SWITCH - REFERENCE
LIGHTING PLAN FOR QUANTITY,
LOCATIONS AND NUMBER OF
BUTTONS PER SWITCH.
INCOMING CIRCUIT
PER RELAY SCHEDULE
SWITCHED CIRCUIT
OUT TO LOAD PER
RELAY SCHEDULE
REFERENCE RELAY
SCHEDULE FOR
QUANTITY OF RELAYS
120/277V
N
G
2
LIGHTING RELAY PANEL CONCEPTUAL ONE-LINE DIAGRAM
NOT TO SCALE
Scale
Project Number
Date
Drawn by
Checked by
675 Lionshead Place, Vail, CO 81657
AS NOTED
E002
22414
ARRABELLE SMARTWOOL
CONVERSION
TENANT
8 AUGUST 2014
BEK
BEK
No. Description Date
9364 Teddy Lane Suite 101, Lone Tree, CO 80124-2873
Project Number:
Village Square at Lone Tree
(720) 489-1609 Fax (720) 489-1611
· ·
2014
C
Est. 1984
Consulting Electrical Engineers
14292
NOT ISSUED FOR CONSTRUCTION UNLESS
SIGNED THROUGH THE SEAL IN BLUE INK OR
DIGITALLY SIGNED BY BRYAN KAZIN.
LIMITED TO ELECTRICAL.
36628
8/14/14
ONE-LINE
DIAGRAM &
SCHEDULES
10/17/14