HomeMy WebLinkAboutE0.1.pdf1. DO NOT SCALE DRAWINGS. VERIFY DIMENSION IN
FIELD PRIOR TO COMMENCEMENT OF WORK. REFER
TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS.
2. SUBCONTRACTOR SHALL BE RESPONSIBLE TO NOTIFY
PRIME CONTRACTOR OF DISCREPANCIES PRIOR TO
STARTING ANY WORK.
3. PROVIDE DEMOLITION AS SHOWN. IF AFFECTED,
RESTORE CONTINUITY TO DEVICES TO REMAIN.
4. DEVICES ONLY SHOWN IF AFFECTED BY SCOPE OF
WORK. ALL OTHER ELECTRICAL SYSTEMS (NOT
SHOWN) EXISTING TO REMAIN.
NOTES:
PROVIDE ELECTRICAL CONNECTION TO NEW BOILER.
HOMERUN CIRCUIT TO PANELBOARD SERVING
EXISTING BOILER ELECTRICAL. FIELD-COORDINATE.
REMOVE ELECTRICAL CONNECTION TO EXISTING
BOILER FOR DEMOLITION.
EXISTING CIRCULATION PUMPS, TO REMAIN. TYPICAL
2. RESTORE CONTINUITY OF CIRCUIT TO PUMPS IF
AFFECTED BY BOILER DEMOLITION.
1
FLAG NOTES:
3
2
P
-
S
T
P
-
S
T
B
1
S
T
111
B
-
333
222
1. ELECTRICAL WIRING SHALL BE 75C RATED MC-TYPE
CABLE (2)#12AWG+#12AWG GRD. FINAL CONNECTION
TO BOILER MAY BE 75C RATED THWN IN LIQUIDTIGHT
FLEXIBLE PATHWAY. CONDUIT OR PATHWAY MAY NOT
BE USED AS EQUIPMENT GROUND.
2. EQUIPMENT DISCONNECT SHALL BE 20A/240v/1P
TOGGLE SWITCH WITH THERMAL PROTECTION, RATED
FOR MOTOR USE. MOUNT IN ACCESSIBLE LOCATION
ON WALL ADJACENT TO BOILER. PROVIDE ADHESIVE
TYPEWRITTEN LABEL INDICATING CIRCUIT, VOLTAGE,
PHASE AND EQUIPMENT DESIGNATION. MOUNT AT
+48"AFF.
3. BRANCH CIRCUIT BREAKERS SHALL BE OF PANEL
MANUFACTURER, 20A/1P, 10kAIC, HACR-RATED.
PROVIDE UPDATED TYPEWRITTEN PANEL SCHEDULE.
4. DEMOLITION: REMOVE ALL ELECTRICAL
COMPONENTS (PATHWAYS, JUNCTION BOXES,
WIRING, DEVICES, ETC.) ASSOCIATED WITH
EQUIPMENT TO BE REMOVED. DISPOSE OF
DEMOLISHED COMPONENTS PER INDUSTRY
STANDARDS AND ENVIRONMENTAL REGULATIONS.
5. NEW WORK: COORDINATE ALL WORK WITH OWNER.
FIELD-COORDINATE ELECTRICAL CONNECTION TO
EQUIPMENT WITH MECHANICAL CONTRACTOR. WORK
SHALL BE PERFORMED IN A WORKMANLIKE MANNER
TO THE SATISFACTION OF THE OWNER. PROVIDE ALL
NECESSARY ACCESSORIES OR APPURTENANCES
REQUIRED FOR A COMPLETE INSTALLATION, EVEN IF
NOT DIRECTLY INDICATED ON THIS DRAWING.
COMPLY WITH MANUFACTURER'S REQUIREMENTS
FOR INSTALLATION; REPLACE ANYTHING DAMAGED BY
INCORRECT FIELD WIRING OR ELECTRICAL
INSTALLATION. VERIFY OPERATION OF NEW
ELECTRICAL WORK PRIOR TO TURNOVER.
6. LOAD JUSTIFICATION:
REMOVED LOAD: LESS THAN 12A (EXISTING BOILER
NAMEPLATE)
ADDED LOAD: 5.3A (NEW BOILER AND INTEGRAL
INJECTION PUMP NAMEPLATE)
EXPECTED LOAD CHANGE: NEGLIGIBLE TO PANEL
CAPACITY
ELECTRICAL SPECS:
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE; HALF SWITCHED
WALL MOUNTED SPECIAL OUTLET AS NOTED
SPECIAL OUTLET AS NOTED
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUCTION BOX
DUPLEX RECEPTACLE MOUNTED ABOVE CONTER
C
DIVISION 15 EQUIPMENT POWER CONNECTION
FUSED DISCONNECT
NON FUSED DISCONNECT
MOTOR STARTER
TRANSFORMER
PANELBOARD OR LOADCENTER
CONTACTOR
ELECTRIC MOTOR
CIRCUIT HOMERUN
CONDUIT RUN
CONDUIT RUN BELOW GRADE
CONDUIT UP
CONDUIT DOWN
TIMER SWITCH
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
DOOR JAMB SWITCH
KEY SWITCH
VARIABLE SPEED SWITCH
THERMAL OVERLOAD SWITCH
INDICATES DEMOLITION.
NOTE: LIGHT LINEWEIGHT INDICATES EXISTING.
NOTE: ALL SYMBOLS SHOWN ON LEGEND
ARE NOT NECESSARILY USED.
ABBREVIATIONS
AVC - ABOVE FINISHED CEILING
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AL - ALUMINUM
BFG - BELOW FINISH GRADE
C - CONDUIT
CKT - CIRCUIT
CT - CURRENT TRANSFORMER
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
(E) - EXISTING
FBO - FURNISHED BY OWNER
GRD - GROUND
GFI - GROUND FAULT CIRCUIT INTERRUPTER
IG - ISOLATED GROUND
IAW - IN ACCORDANCE WITH
NIC - NOT IN CONTRACT
DW - DISHWASHER
DISP - GARBAGE DISPOSAL
NL - NIGHT LIGHT
NTS - NOT TO SCALE
REF - REFRIGERATOR
TVSS - TRANSIENT VOLTAGE SURGE SUPPRESSOR
UG - UNDERGROUND
UNO - UNLESS NOTED OTHERWISE
WP - WEATHER PROOF
XP - EXPLOSION PROOF
+18" - MOUNTING HEIGHT TO CENTERLINE OF
DEVICE ABOVE FINISH FLOOR
S
T
S
V
S
K
S
J
S
4
S
3
S
TS
C
T
N
-
-
J
J
J
ELECTRICAL LEGEND
POWER SYMBOLS
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SCALE:
ELECTRICAL FLOOR PLAN
1/8" = 1'-0"
VAIL, COLORADO 81657
09.24.14
SHEET TITLE:
NO. Job no.: REVISION Drawn by:
Date:
Designed by:
DATE
BY 846 FOREST ROAD EAUDIN
ANZE
COPYRIGHT 2014
B
G
C:\Users\cadd-txc\local settings\temp\AcPublish_7968\953800E01.dwg Printed By: cadd-txc September 24, 2014 - 1:09pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
9538.00
E0.1
ELECTRICAL SYSTEMS
PLAN
ELR
ELR
10/20/14