HomeMy WebLinkAboutM0.0.pdf'*' ISSUED FOR INFORMATION ONLY
' ' NOT PART OF SET
' ' ISSUED AS PART OF A SET
ISSUE LOG KEY:
# DATE
ISSUE LOG
MECH/ELEC SHEET INDEX
TITLE
MECHANICAL COVER SHEET
M0.0
P ERMIT
09/24/2014
MECHANICAL SPECIFICATIONS
M0.1
MECHANICAL DIAGRAMS
M0.2
MECHANICAL PARTIAL FLOOR PLAN
M0.3
REFERENCE SAMPLE
FFI = FOR FURTHER INFORMATION
FCT = FOR CONTINUATION
SHEET NUMBER
DRAWING NUMBER OR DIAGRAM
LETTER
REFER TO:
RE: B/M400 FFI
DUCT/PIPE RISER
DESIGNATION KEY
CH - CHILLED WATER
DW - DOMESTIC WATER
HW - HEATING WATER
G - GAS PIPING
WV - WASTE AND/OR VENT
PR - PIPING RISER (MISC TYPES)
ST - STORM DRAIN
S2 - SECONDARY STORM DRAIN
OA - OUTSIDE AIR
EX - EXHAUST AIR
RA - RETURN AIR
RISER NUMBER
PR
203
PLAN SYMBOLS
CONTROL PANEL/RADIANT MANIFOLD
T
-
-
-
-
P
-
--
S
H
CO
P
EPO
CO2
SP
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
FIRE RISER
DIAGRAM CONTINUATION REFERENCE
PLUMBING RISER
HEATING WATER RISER
THERMOSTAT
HVAC RISER
POINT OF NEW CONNECTION
DUCT STATIC PRESSURE SENSOR
ROOM PRESSURE SENSOR
HUMIDISTAT
REMOTE TEMPERATURE SENSOR
EMERGENCY POWER OFF SWITCH
ACCESS PANEL
SNOWMELT MANIFOLD
SECTION CUT LETTER/SHEET SHOWN ON
POINT OF DISCONNECTION
NOTES
1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS
ON LEGEND SHEET ARE NOT NECESSARILY USED ON
THIS PROJECT.
2. THIS DRAWING SET CONSISTS OF DATA GENERATED, IN
PART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES
AND NOTATION CONVENTIONS OCCURRING IN THIS
DRAWING SET ARE NECESSARILY DEFINED ON THESE
LEGENDS. CONSULT THE ENGINEER IN THE EVENT
SYMBOLOGY OR NOTATION INTERPRETATION IS
REQUIRED.
DUCTWORK LEGEND
SINGLE LINE DOUBLE LINE
DESCRIPTION
90° ELBOW DOWN (ROUND DUCT ONLY)
ROUND 90° ELBOW UP (ROUND DUCT ONLY)
ROUND RADIUS ELBOW
90° STRAIGHT TEE
90° CONICAL TEE
45° BRANCH
45° CONICAL TEE
SIZE OR SHAPE TRANSITION
ROUND FLEXIBLE DUCT
90° ELBOW DN (NEGATIVE PRESSURE)
90° ELBOW DN (POSITIVE PRESSURE)
90° ELBOW UP (NEGATIVE PRESSURE)
90° ELBOW UP (POSITIVE PRESSURE)
90° RADIUS ELBOW
90° RADIUS ELBOW W/TURNING VANES
SQUARE DUCT SPLIT
ROUND DUCT SPLIT
COMBINATION FIRE AND SMOKE DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTOR OPERATED DAMPER (MOD)
BACKDRAFT DAMPER
SMOKE DETECTOR
OFFSET TO CHANGE ELEVATION
(AT 30° WHEN POSSIBLE)
D = DROP R = RISE
D
F/S
BDD
SD
24x36
D
SPLIT BRANCH TAKE-OFF WITH SQUARE
ELBOW & SPLITTER DAMPER
SPLIT BRANCH TAKE-OFF WITH RADIUS
ELBOW & SPLITTER DAMPER
POSITIVE PRESSURE RISER, TYPICALLY
SUPPLY.
NEGATIVE PRESSURE RISER, TYPICALLY
RETURN, EXHAUST OR OUTSIDE AIR.
MAN VOLUME DAMPER, SINGLE BLADE
DAMPER(SBD) FOR ROUND OR <10" TALL,
OPPOSED BLADE DAMPER(OBD) >10" TALL.
DUCT SIZE: FIRST NUMBER IS PLAN WIDTH,
SECOND NUMBER IS DEPTH.
24x36
SD
F/S
BDD
PLAN ABBREVIATIONS
ABOVE FINISHED FLOOR
AIR ADMITTANCE VALVE
ABOVE FINISHED GRADE
AUTOMATIC
BUILDING CONTROL SYSTEM
BACK DRAFT DAMPER
BUILDING
AAV
AFF
AFG
AUTO
BCS
BDD
BLDG
BOTTOM OF PIPE FROM FINISHED FLOOR
BETWEEN
COMMON
COMBUSTION AIR
CONTROLS CONTRACTOR
CONTINUATION DESIGN BUILD
BOP
B/N
C
CA
CC
CDBBC
CUBIC FEET PER MINUTE (AIR FLOW RATE)
CAST IN PLACE
CEILING (OR COOLING)
CONCRETE
CONDENSATE
CONNECT
CONTRACTOR
CFM
CIP
CLG
CONC
COND
CONN
CONTR'R
CLEANOUT
CO
CLEANOUT TO GRADE
COTG
DOMESTIC HOT WATER RECIRC
EXISTING
DWR
(E)
EXHAUST AIR
EA
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
ENTERING WATER TEMPERATURE
EAT
EC
EXH EXHAUST
EWT
GENERAL CONTRACTOR
GROUND HEAT EXCHANGER
GC
GHX
GALLONS PER MINUTE (WATER FLOW RATE)
GPM
HORSEPOWER
HOT WATER
IN LIEU OF
HP
HW
ILO
KILOWATTS
KW
LEAVING AIR TEMPERATURE
LINEAR FOOT
LEAVING WATER TEMPERATURE
LAT
LF
LWT
MECHANICAL CONTRACTOR
MC
MANUFACTURER
MOTOR OPERATED DAMPER
NEW
MFG
MOD
(N)
NORMALLY CLOSED
NC
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NORMALLY OPEN
NEC
NIC
N0
OUTSIDE AIR
OA
OPPOSED BLADE VOLUME DAMPER
ON CENTER
OBD
OC
OUTSIDE AIR
OSA
RETURN AIR
REQUIRED
RA
REQ'D
REQUIREMENTS
REQ'MTS
SUPPLY AIR
SQUARE FOOT (FEET)
SA
SF
STATIC PRESSURE
SP
STAINLESS STEEL
THROW-AWAY
TYPICAL
SS
T.A.
TYP
UNLESS NOTED OTHERWISE
UNO
VENT THRU ROOF
VTR
WALL CLEANOUT
WCO
WITH REGARD TO
WATER COOLED
TRANSFER
WRT
W/C
XFR
DIAMETER
Ø
BY CONTRACTOR
COLD WATER
CW
HOT WATER RECIRC
HWC
ABOVE ABV
BELOW FINISHED GRADE
BFG
DOMESTIC WATER
DOMESTIC HOT WATER
DW
DHW
DOWN
DN
DOMESTIC HOT WATER RECIRC
DHR
COMBINATION FIRE/SMOKE DAMPER
FURNISHED BY OWNER
FSD
FBO
FLOOR CLEANOUT
FCO
FOR CONTINUATION
FCT
FD FIRE DAMPER
REFER TO:
RE:
WITH
W/
EQUIPMENT ABBREVIATIONS
AIR HANDLING UNIT
AHU
AIR SEPARATOR
AS
BOILER (HOT WATER)
B
BASE BOARD
BB
BUFFER TANK
BT
CONSTANT VOLUME BOX CV
DISHWASHER EXHAUST FAN
DEF
ELECTRIC BASEBOARD HEATER
EBH
FURNACE
F
FAN COIL
FC
FAN POWERED BOX
FP
GLYCOL FEEDER
GF
HUMIDIFIER
HC HEATING COIL
HP HEAT PUMP
HX HEAT EXCHANGER
KITCHEN EXHAUST FAN
KEF
MAKE-UP AIR UNIT
MAU
MOTOR CONTROL CENTER
MCC
MIXING VALVE
MV
PUMP (SEE PIPING LEGEND FOR DETAILS)
P
RETURN (OR RELIEF) AIR FAN
RF
RADIANT ZONE
RZ
SNOWMELT AREA
SA
SUMP BASIN
SB
SUPPLY FAN
SF
STORAGE TANK
ST
THERMOSTATIC MIXING VALVE
TMV
UNIT HEATER
UH
VARIABLE VOLUME BOX
VV
WATER HEATER
WH
H
CHILLER
CH
COILING COIL CC
CIRC PUMP
CP
CABINET UNIT HEATER CUH
COOLING TOWER
CT
DUCT COIL
DC
ELECTRIC WATER HEATER
EWH
EVAPORATIVE COOLING UNIT
ECU
ENERGY RECOVERY UNIT
ERU
EXHAUST FAN
EF
EXPANSION TANK
ET
VARIABLE VOLUME BOX W/ REHEAT
VR
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO
COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS
FOR ALL DIMENSIONS.
2. ALL SUBCONTRACTORS SHALL BE LICENSED, EXPERIENCED, AND
THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF
THE CONSTRUCTION INDUSTRY AND SHALL PERFORM IN A
RESPONSIBLE MANNER WITH ESTABLISHED CONSTRUCTION
SEQUENCE, SHALL RECOGNIZE THE PRIORITY OF THE CONSTRUCTION
DOCUMENTS, AND SHALL INFORM THE PRIME CONTRACTOR OF
POTENTIAL PROBLEMS WHEN THE CONSTRUCTION DOCUMENTS ARE
UNCLEAR OR INCONSISTENT.
3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME
CONTRACTOR OF DISCREPANCIES OR CONFLICTS IN THE
CONSTRUCTION DOCUMENTS FOUND DURING BIDDING AND/OR PRIOR
TO PERFORMING THE WORK.
4. SUBCONTRACTOR SHALL VERIFY EXISTENCE AND LOCATION OF ALL
UTILITY SERVICES AND COORDINATE AS REQUIRED BY THEIR
RESPECTIVE AREA OF THE CONSTRUCTION, NOTIFYING THE PRIME
CONTRACTOR OF VARIATIONS OR CONFLICTS.
5. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION
DOCUMENTS, MATERIALS AND/OR EQUIPMENT SHALL BE IDENTIFIED
BY THE SUBCONTRACTOR WITH SUFFICIENT TIME TO ALLOW
SELECTION, PURCHASE, AND DELIVERY TO MAINTAIN CONSTRUCTION
SCHEDULE.
6. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE
STRUCTURE, BEAMS, AND COLUMNS.
7. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE
SATISFACTION OF THE ARCHITECT, OWNER, AND ENGINEER.
8. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS/HER
WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES
AND LIFE SAFETY FEATURES AS REQUIRED BY LOCAL, STATE, OR
NATIONAL AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE
ARCHITECT IF MODIFICATION OF HIS/HER WORK IS REQUIRED FOR
COMPLIANCE.
9. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR
EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF
THE 2012 INTERNATIONAL BUILDING, MECHANICAL, PLUMBING, FUEL
GAS, FIRE, 2012 INTERNATIONAL ENERGY CONSERVATION CODE AND
2011 NATIONAL ELECTRICAL CODES, MOST CURRENT NFPA, ALL
LOCAL ORDINANCES AND AMENDMENTS AND MANUFACTURER'S
INSTALLATION RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE
PUBLICATIONS EXISTS, THE MOST STRINGENT REQUIREMENT SHALL
APPLY.
10. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS.
PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL
CERTIFICATES OF COMPLETION.
11. WARRANTY THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND
WORKMANSHIP. THE WARRANTY SHALL BE FOR A PERIOD OF ONE
YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY
REMEDIED WITHOUT COST TO THE OWNER.
12. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR
CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY THE OWNER.
13. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT
A MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF
WORK ARE DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS
NECESSARY AT NO ADDITIONAL COST TO OWNER.
14. ALL MATERIALS AND/OR EQUIPMENT SHALL BE HANDLED AND
INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND
RECOMMENDATIONS.
15. TEMPORARY HEAT SHALL BE FURNISHED BY THE GENERAL
CONTRACTOR. USE OF THE PERMANENT HEATING SYSTEM WILL NOT
BE ALLOWED.
16. PROVIDE 4” HIGH CONCRETE EQUIPMENT PADS BENEATH FLOOR
MOUNTED MECHANICAL EQUIPMENT, IN ADDITION TO ANY BASE
ASSEMBLIES REQUIRED OR RECOMMENDED BY THE MANUFACTURER.
17. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE
AVAILABLE.
18. PROVIDE ¼” GALVANIZED MESH SCREEN ON ALL COMBUSTION AIR
DUCTS OR OPENINGS, AND ALL OPEN END RETURN AND EXHAUST
DUCTS.
19. PROVIDE EXPANSION JOINTS OR LOOPS ON ALL HEATING WATER
PIPING RUNS IN EXCESS OF 50 FEET AND IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
20. GRADE AND VALVE ALL HEATING WATER PIPING WITH 3/4" HOSE END
VALVES TO PERMIT COMPLETE DRAINAGE OF THE SYSTEM. VENT ALL
HIGH POINTS IN THE EQUIPMENT ROOMS AS NECESSARY WITH
AUTOMATIC AIR VENTS PIPED TO A CONVENIENT DRAIN. PROVIDE ALL
HIGH POINTS IN SYSTEM OUTSIDE OF EQUIPMENT ROOMS WITH
COMBINATION AUTOMATIC/MANUAL AIR VENTS AS REQUIRED TO
RELIEVE AIR IN THE SYSTEM.
21. EQUIPMENT LABELS: LABEL ALL PIPING AND EQUIPMENT. PROVIDE
FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING.
PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND
ATTACH WITH STANDARD CHAIN OR S-HOOKS. PROVIDE ENGRAVED
PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT.
22. INSULATE ALL EXHAUST DUCTS PENETRATING THE ENVELOPE 10'
INBOARD OF ENVELOPE PENETRATION, UNLESS NOTED OTHERWISE.
23. IN AS MUCH AS DESIGN FOR REMODEL AND/OR REHABILITATION
REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING
EXISTING CONDITIONS, AND BECAUSE SOME OF THESE ASSUMPTIONS
CANNOT BE VERIFIED WITHOUT DESTROYING OTHERWISE ADEQUATE
OR SERVICEABLE PORTIONS OF THE BUILDING, THE ENGINEER
CANNOT ASSURE THE OWNER OR THE CONTRACTOR THAT THE
PROFESSIONAL CONSULTING SERVICES HEREIN ENCOMPASS ALL
CONTINGENCIES. FIELD COORDINATION DURING CONSTRUCTION IS
IMPERATIVE. MAKE REASONABLE ALLOWANCES FOR UNSEEN
CONDITIONS.
GENERAL NOTES:
SNOWMELT SUPPLY
SNOWMELT RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER SUPPLY
CONDENSER RETURN
NATURAL GAS
MEDIUM PRESSURE GAS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. SHOWN)
HOT WATER CIRCULATION
FIRE LINE
PRESSURIZED WASTE
PLUMBING VENT PIPE
WASTE PIPE
STORM DRAIN PIPE
STORM DRAIN OVERFLOW
GREASE WASTE PIPE
PRESSURE REDUCING VALVE
SOLENOID VALVE
FLOW SWITCH
SHOCK ABSORBER
HOSE BIBB
STRAINER W/ BLOW-OFF VALVE
ROOF DRAIN
SAFETY RELIEF VALVE
FLOOR DRAIN
FLOOR SINK
HORIZONTAL CLEANOUT
VACUUM BREAKER
VERTICAL CLEANOUT
PRESSURE GAUGE W/ PIG TAIL & COCK
THERMOMETER
PRESSURE - TEMP. TAP
AIR VENT
PIPE ANCHOR
FLEXIBLE CONNECTOR
PIPE EXPANSION JOINT
PIPE UNION
DOUBLE CHECK BACKFLOW PREVENTER
PUMP & EQUIPMENT CONNECTOR
PIPING SYMBOLS
WALL HYDRANT
SHUT OFF VALVE (BALL, GATE, BUTTERFLY)
TEMPERATURE CONTROL VALVE
DRAIN VALVE W/ HOSE END
PLUG VALVE IN RISER
FLOW BALANCING VALVE
GATE OR GLOBE VALVE IN RISER
FLOW CONTROL VALVE
BALL VALVE
PLUG OR BALANCING VALVE
CHECK VALVE
GLOBE VALVE
BUTTERFLY VALVE
S
VENTURI/FLOW INDICATOR
SECONDARY DRAIN
SAND AND OIL WASTE
NON-SOFTENED DOMESTIC COLD WATER
NS
SO
SD
FS
W H
H B
ST(OF)
ST
GW
V
W
PW
F
140°
MG
G
CR
CS
CHR
CHS
HWR
HWS
SMR
SMS
ELECTRICAL SYSTEMS PLAN
E0.1 VAIL, COLORADO 81657
09.24.14
SHEET TITLE:
NO. Job no.:
REVISION Drawn by:
Date:
Designed by:
DATE
BY 846 FOREST ROAD
EAUDIN
ANZE
COPYRIGHT 2014
B
G
S:\BGProjects\9538.00 ERWSD - Vail Administration Building Boiler Replacement\Drawings\BGCE\953800M00.dwg Printed By: cadd-drp September 24, 2014 - 1:26pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
9538.00
M0.0
MECHANICAL
COVER SHEET
10/20/14
MECHANICAL SPECIFICATIONS:
DIVISION 15--MECHANICAL SPECIFICATIONS
SECTION 15010--MECHANICAL GENERAL PROVISIONS
PART 1 - GENERAL
1.1 DESCRIPTION
A. Work Included
1. Furnish all labor and materials and perform all operations necessary for the installation of complete and
operating mechanical systems subject to the conditions of the contract. The work also includes the
completion of such mechanical and electrical details not mentioned or shown which are necessary for the
successful operation of all systems; this includes the furnishing of all materials for filling systems to make
them operable, including water, refrigerant, oil, grease, antifreeze and brine. Prove satisfactory operation of
all equipment and controls to the MECHANICAL ENGINEER on request.
1.2 CODES AND STANDARDS
A. Comply with all applicable codes, laws, industry standards and utility company regulations.
1.3 PERMITS, FEES AND NOTICES
A. Apply for and pay for all permits, fees, licenses and inspections for this Division of work. Do not include the
cost of any "Plant Investment Fee" or "System Development Charge" for sewer and/or water or any "Gas
Application Fee" charged by the Utility Company. This will be arranged for and paid for by the Owner
B. Notify proper authorities when work is ready for inspections required by applicable codes, rules and regulations,
allowing sufficient time for inspections to be made without hindering progress of the work. Furnish to the Owner
copies of inspection certificates of acceptance.
1.4 PROJECT/SITE CONDITIONS
A. Install Work in locations shown on Drawings, unless prevented by Project conditions.
B. Prepare drawings showing proposed rearrangement of Work to meet Project conditions, including changes to
Work specified in other sections. Obtain permission of Architect and engineer before proceeding.
PART 2 - PRODUCTS
2.1 INDOOR PIPING INSULATION
INSULATE ALL HEATING WATER, WITH U.L. APPROVED, WHITE, ALL SERVICE, FIBERGLASS, SNAP-ON,
PIPE INSULATION. ALL MATERIALS SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A
FLAME SPREAD RATING OF 25 OR LESS. PROVIDE POLYISOCYANURATE THERMAL INSERT AT
HANGERS AND SUPPORTS. INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS. VAPOR
BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH “NON-BREATHING” VAPOR BARRIER MASTIC ON
PIPING OPERATING AT TEMPERATURES BELOW AMBIENT. ALL RAW EDGES OF INSULATION SHALL BE
NEATLY TRIMMED AND SEALED WITH MASTIC.
A. INSULATION THICKNESS BELOW BASED ON INSULATION CONDUCTIVITY VALUE NOT EXCEEDING
0.27 BTU*IN/(HR*FT^2*°F):
1) HEATING WATER - ALL PIPE SIZES, 1.5” THICK.
2.2 WATER TREATMENT: CLOSED HYDRONIC SYSTEMS INCLUDING CHILLED WATER SHALL HAVE THE
FOLLOWING WATER QUALITIES:
A. PH: MAINTAIN A VALUE WITHIN 7.0 TO 9.0
B. AMMONIA: MAINTAIN A MAXIMUM VALUE OF 2.0 mg/L
C. CaCO3 ALKALINITY: MAINTAIN A VALUE WITHIN 30-500 mg/L
D. CaCO3 HARDNESS: MAINTAIN A VALUE WITHIN 30-500 mg/L
E. CHLORIDES: MAINTAIN A MAXIMUM VALUE OF 200 mg/L
F. DISSOLVED SOLIDS: MAINTAIN A MAXIMUM VALUE OF 1000 mg/L
G. IRON: MAINTAIN A MAXIMUM VALUE OF 5.0 mg/L
H. MANGANESE: MAINTAIN A MAXIMUM VALUE OF 0.4 mg/L
I. NITRATE: MAINTAIN A MAXIMUM VALUE OF 100 mg/L
SULPHATE: MAINTAIN A MAXIMUM VALUE OF 200 mg/L
PART 3 - EXECUTION
3.1 STORAGE
A. Provide for proper storage of all materials and equipment and assume responsibility for losses due to any
cause. All storage shall be within the contact limit lines of the building site. Cover and store all equipment and
materials out of elements; any rusted or weather damaged item shall not be used.
3.2 PRODUCT INSTALLATION
A. Manufacturer's Instructions
30.Except where more stringent requirements are indicated, comply with the product manufacturer's
instructions and recommendations.
31.Consult with manufacturer's technical representatives, who are recognized as technical experts, for specific
instructions on special project conditions.
32.If a conflict exists, notify the Architect/Engineer in writing and obtain his instruction before proceeding with
the work in question.
B. Movement of Equipment
1. Wherever possible, arrange for the movement and positioning of equipment so that enclosing partitions,
walls and roofs will not be delayed or need to be removed.
2. Otherwise, advise Contractor of opening requirements to be maintained for the subsequent entry of
equipment.
C. Heavy Equipment
1. Coordinate the movement of heavy items with shoring and bracing so that the building structure will not be
overloaded during the movement and installation.
2. Where mechanical products to be installed on the existing roof are too heavy to be hand-carried, do not
transport across the existing roof deck; position by crane or other device so as to avoid overloading the roof
deck.
3.3 Clearances
1. Except as otherwise indicated, arrange mechanical services and overhead equipment with a minimum of:
a. 7'0” headroom in storage spaces.
b. 8'6” headroom in other spaces.
2. Do not obstruct windows, doors or other openings.
3. Give the right-of way to piping systems required to slope for drainage (over other service lines and
ductwork).
4. Offsets, transitions and changes in direction in pipes and ducts shall be made as required to maintain
proper head room and pitch of sloping pipes whether or not indicated on the drawings. Furnish and install
all traps, air vents, sanitary vents, etc., as required to affect these offsets, transitions and changes in
direction.
3.1 Access
1. Install all work to permit removal (without damage to other parts) of coils, heat exchanger bundles, boiler
tubes, fan shafts and wheels, filters, belt guards, sheaves and drives, and all other parts which might require
periodic replacement or maintenance. Arrange pipes, ducts, and equipment to permit ready access to
valves, traps, starters, motors, control components and to clear the openings of doors and of access panels.
3.2 PROTECTION OF POTABLE WATER SYSTEMS
A. All temporary water connections shall be made with an approved back flow preventer.
B. All hose bibbs shall have, as a minimum, a vacuum breaker to prevent back flow.
C. Direct connections to hydronic systems shall only be made through a reduced pressure back flow preventer.
3.3 PROTECTION OF SYSTEMS SERVING OCCUPIED SPACES
A. Where work is being performed in occupied spaces, or occupancy is to be phased in with ongoing construction
contractor shall prevent contamination of all systems serving the occupants including but not limited to:
1. Supply or return air
a. Systems shall be capped or provided with adequate particulate and gas phase filtration to prevent
dust, chemical, or biological contamination. Particulate filters shall be as a minimum equivalent to
those specified for the completed system.
2. Domestic Water
a.Isolate sterilized portions from non-sterilized portions.
3.4 ELECTRICAL EQUIPMENT AND WIRING FOR MECHANICAL DIVISION
A. Unless otherwise indicated, all motors and controls shall be furnished, set in place and wired in accordance
with the following schedule. (MD is Mechanical Division - ED is Electrical Division).
Connections to all controls directly attached to ducts, piping and mechanical equipment shall be made with
flexible connectors.
3.5 FLUSHING, CLEANING & STERILIZING
A. Before final connections are made in the piping systems, blow out all piping with air and then wash out with
cleaning compounds. Then flush the system to remove of all foreign materials. Furnish all temporary
connections, valves, etc, required for this purpose. Clean the boiler and chiller by the same procedure.
B. After flushing, sterilize the domestic water system.
3.6 BALANCING
A. The balancing of the system shall be part of this contract, include in bid the cost of balancing and adjusting.
The balancing and balance report shall be in acceptance with Associated Air Balance Council (AABC)
requirements or National Environmental Balancing Bureau (NEBB) requirements.
B. At the completion of the installation, the mechanical systems shall be adjusted and balanced by an independent
balancing firm specializing in this work, accepted by the Engineer before bidding.
C. Provide such items as thermometer wells, pressure test cocks, access doors, etc., as required to allow tests
and adjustments to be made.
D. Adjust and balance all air and water systems. Check, adjust and balance all systems to meet the design
conditions and tabulate all information on acceptable forms. All systems shall be checked for proper
performance during design conditions, both heating and cooling.
VAIL, COLORADO 81657
09.24.14
SHEET TITLE:
NO. Job no.:
REVISION Drawn by:
Date:
Designed by:
DATE
BY 846 FOREST ROAD
EAUDIN
ANZE
COPYRIGHT 2014
B
G
C:\Users\cadd-drp\local settings\temp\AcPublish_9340\953800M01.dwg Printed By: cadd-drp September 24, 2014 - 1:26pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
9538.00
M0.1
MECHANICAL
SPECIFICATIONS
10/20/14
BOILER SCHEDULE
MARK SERVICE
BOILER
TYPE
FUEL
TYPE
HEATING CAPACITY
WATER
∆ T (°F)
BURNER PUMP
VENT
TYPE
MANUFACTURER*
& MODEL #
ACCESSORIES REMARKS
INPUT
@ S.L.
(MBH)
OUTPUT
@ ALT.
MINIMUM
A.F.U.E.
AMPS
VOLT/
PH
AMPS
VOLT/
PH
B-1
HOT
WATER
HEATING
CONDENSING NAT GAS 399 300 92 20 4 120 /1 1.3 120 /1 IV RAYPAK H7-400 --
- - - - - - - --- - - - -
MANUFACTURERS:
* RAYPAK, LOCHINVAR, TRIANGLE TUBE, PATTERSON KELLY, VIESSMANN OR BUDERUS
GENERAL NOTES:
A:
PROVIDE UNIT WITH ON BOARD BOILER CONTROLLER AND DIAGNOSTIC CENTER WITH INTEGRATION MATCHING THE PROGRAMMING LANGUAGE OF THE BUILDING MANAGEMENT SYSTEM I.E. (LONWORKS, BACNET,
MODBUS, ECT.). REFER TO BOILER CONTROLS, THIS SHEET FOR FURTHER INFORMATION.
B: PROVIDE BOILER VENT AS STAINLESS STEEL TYPE IV OR EQUIVALENT FOR LONG TERM HIGH TEMP BOILER OPERATION. PVC SHALL NOT BE ALLOWED.
C: PROVIDE UNIT WITH INTEGRAL PRIMARY BOILER PUMP, CONDENSATE NEUTRALIZATION KIT, INDIRECT SENSOR, DIRECT VENT KIT, AND LOW WATER ALARM WITH MANUAL RESET.
PUMP SCHEDULE
MARK SERVICE TYPE GPM TDH (FT) FLUID
MOTOR
MANUFACTURER*
& MODEL #
ACCESSORIES REMARKS
HP RPM
VOLT/
PH
(N) BP-1
PRIMARY
BOILER
PUMP
- 38 18 30% PG 1.3 AMPS - 120 /1 - - PUMP INTEGRAL TO BOILER
(E) P-1
SECONDARY
HOT WATER
PUMP
INLINE - - 30% PG 1/2 - 120 /1 BELL AND GOSSET - -
(E) P-2
SECONDARY
HOT WATER
PUMP
INLINE - - 30% PG 1/3 - 120 /1 BELL AND GOSSET - -
(E) GPF GLYCOL
FEEDER
- - - - - - 120 /1 - - -
- - --- ---- - - -
MANUFACTURERS:
* B&G, GRUNDFOS, TACO OR AURORA EQUIVALENT
GENERAL NOTES:
A:
B:
SPIROTHERM SPIROVENT
VHR AIR SEPARATOR, OR
EQUIVALENT MATCH PIPE
SIZE.
HOSE END VALVE TO . 30%
PROPYLENE GLYCOL WATER
SOLUTION.
AIR VENT AT ALL HIGH
POINTS, TYPICAL.
G
60PSI RELIEF VALVE
PIPED TO FLOOR DRAIN.
Y-STRAINER
2" HWR
D
2" HWS
S
2" HWR
SCALE: 2 NEW BOILER PIPING DIAGRAM
NO SCALE
NEW TACO CA-450 EXPANSION
TANK.
G
2" HWR
D 2" HWS
S
2" HWR
2" HWS
SCALE: 2 BOILER DEMOLITION PIPING DIAGRAM
NO SCALE
DESCRIPTION - THE BOILER PLANT CONSISTS OF ONE(1) GAS
FIRED CONDENSING BOILERS, PRIMARY BOILER PUMP, AND
SECONDARY PUMPING SYSTEMS. PROVIDE NEW BOILERS WITH
CONTROLLER CAPABLE OF INPUT OUTPUT TO BUILDING
MANAGEMENT SYSTEM.
SCHEDULING - OPERATION OF THE HEATING WATER PLANT IS
NOT SCHEDULED AND SHALL BE BASED ON DEMAND FOR
HEATING WATER PRODUCTION. ANY DEVICE WITHIN THE
HEATING WATER SYSTEM SHALL BE CAPABLE OF ENABLING
HEATING WATER SERVICE.
HEATING WATER SUPPLY SETPOINT: 140°F
OUTDOOR RESET SCHEDULE: 190°F HWS @ 0°F OSA
120°F HWS @ 60°FOSA
INCLUDE LOGIC TO ABANDON HEATING WATER RESET
SCHEDULE AND INCREMENTALLY INCREASE SUPPLY SETPOINT
(5°F EVERY 5 MINUTES) IN THE EVENT THAT ANY INDOOR SPACE
TEMPERATURE FALLS MORE THAN 5°F BELOW SETBACK
TEMPERATURE SETPOINT. RETURN TO RESET SCHEDULE
WHEN ALL SPACES ARE WITHIN 2 °F OF SETPOINT.
HWS SETPOINT SHALL BE MAINTAINED BY MODULATING AND
STAGING ON BOILERS BASED ON INTEGRAL FACTORY MOUNTED
CONTROLS, SEQUENCES, AND SAFETIES TO MAINTAIN BOILER
HWS TEMPERATURE AT SETPOINT DICTATED BY THE BAS.
BOILER HWS TEMPERATURE SETPOINT DICTATED BY THE BAS
SHALL BE EQUAL TO HWS RESET SCHEDULE INDICATED ABOVE.
START ASSOCIATED BOILER CIRC PUMP UPON ENABLING
BOILER. STOP ASSOCIATED BOILER CIRC PUMP UPON
DISABLING BOILER.
BUILDING HEATING WATER DISTRIBUTION PUMPING - SHALL BE
ENABELED WHEN OUTSIDE AIR TEMPERATURE IS LOWER THAN
60°F.
FEATURES -
1. PUMPS ROTATIONAL SEQUENCING - TALLY PUMPS' RUN
TIMES AND INDICATE TOTAL RUN HOURS IN GRAPHICS
SCREEN. ROTATE LEAD/LAG DESIGNATIONS AS
FOLLOWS ON A WEEKLY BASIS:
A. LEAD - PUMP WITH LEAST RUN HOURS.
B. LAG - PUMP WITH THE MOST RUN HOURS.
E. INDICATE THE ABOVE DESIGNATIONS IN
GRAPHICS SCREEN ADJACENT EACH BOILER'S
RUN HOUR INDICATOR.
3. EQUIPMENT FAILURES -
A. GENERATE ALARM SHOULD ANY BOILER STATUS
NOT MATCH COMMAND. ENABLE NEXT BOILER.
B. GENERATE ALARM SHOULD ANY PUMP STATUS
NOT MATCH COMMAND. ENABLE NEXT PUMP.
4. HOURLY TREND ITEMS INDICATED IN THE POINTS LIST
TO BE TRENDED. STORE DATA FOR 1 YEAR PRIOR TO
PURGING.
5. GENERATE ALARM AS INDICATED IN THE POINTS LIST
AND IN THE SEQUENCE OF CONTROL ABOVE.
TYPICAL HANGER DIAGRAM
NO SCALE
ANCHOR,
REFER TO
STRUCTURAL.
THREADED
ROD.
HANGER.
PIPE.
CONCRETE
STRUCTURE.
ALL PIPING WITH
INSULATION TO HAVE
INSULATION RUN FULL
SIZE THROUGH
HANGER WITH SHIELD
AND INSERT.
FOR WATER DIAGRAM
TYPICAL PIPE SIZE CHANGE
TOP OF PIPE
NO SCALE
PIPE
PIPE
INVERTED ECCENTRIC
REDUCER.
HORIZONTAL INLINE
PUMP DIAGRAM
NO SCALE
PIPE HANGERS. PROVIDE DOUBLE
DEFLECTION NEOPRENE TYPE FOR
FIRST TWO ON EACH SIDE OF PUMP.
MOUNT MOTOR
SHAFT IN
ORIENTATION
PER MFG'S
RECOMMENDATION.
NOTE:
SUPPORT PUMP FROM PIPING ONLY. DO
NOT SUPPORT PUMP FROM MOTOR,
UNLESS HANGER IS BUILT IN. MOUNT PUMP
PER MANUF. RECOMMENDATIONS.
DIRECTION OF
WATER FLOW.
FLOOR
DIAGRAM
GLYCOL FEEDER
NO SCALE
PS
CONNECTION AT EXPANSION
TANK ASSEMBLY,.
PRESSURE
SWITCH.
PRESSURE
GAUGE.
FULL SIZE
DISCHARGE PIPE
FROM SYSTEM
RELIEF VALVE.
STORAGE DRUM
WITH LID.
LOW WATER
CUT-OFF SWITCH.
3
4"
PUMP
AIR GAP.
4" CONC. PAD
DRAIN VALVE W/
HOSE
CONNECTION.
3/4"
PRESSURE
GAUGE DIAGRAM
NO SCALE
POINT OF
CONNECTION.
GAUGE.
PIGTAIL.
SCREWED TEE.
NIPPLE.
CAP.
TE
AI
HWS TEMPERATURE
TE
AI HWR TEMPERATURE
BO PUMP ENABLE/DISABLE
BI PUMP STATUS
BO BOILER ENABLE/DISABLE
BI BOILER STATUS
AO HEATING WATER SETPOINT
CP
EXISTING CONTROL POINTS
FOR BOILER PUMPS TO
REMAIN. REFER TO
SEQUENCE OF CONTROLS.
2" HWS
CONTROL POINTS TO
CONNECT TO EXISTING BMS.
PROVIDE 1 GALLON
CPVC DILUTION TRAP
IN CONDENSATE
DRAIN AND FILL WITH
NON FLAMMABLE
MINERAL OIL FOR
HIGH TEMPERATURE
BOILER OPERATIONS
THAT MAY DRY OUT
WATER IN TRAPS.
OIL
WATER
CONDENSATE
NEUTRALIZATION
KIT.
VAIL, COLORADO 81657
09.24.14
SHEET TITLE:
NO. Job no.:
REVISION Drawn by:
Date:
Designed by:
DATE
BY 846 FOREST ROAD
EAUDIN
ANZE
COPYRIGHT 2014
B
G
S:\BGProjects\9538.00 ERWSD - Vail Administration Building Boiler Replacement\Drawings\BGCE\953800M02.dwg Printed By: cadd-drp September 24, 2014 - 1:26pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
9538.00
M0.2
MECHANICAL
SCHEDULES / DETAILS
10/20/14
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSION IN FIELD
PRIOR TO COMMENCEMENT OF WORK. REFER TO
ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS.
2. SUBCONTRACTOR SHALL BE RESPONSIBLE TO NOTIFY
G.C./ARCHITECT/ENGINEER OF DISCREPANCIES PRIOR TO
STARTING ANY WORK.
3. PIPING ON EXTERIOR WALLS OR PRE‐CAST CONCRETE
WALLS TO BE ROUTED IN FRAMED WALL ON INTERIOR
SIDE OF INSULATION.
4. ALL VALVES SHALL BE INSTALLED ABOVE DROP‐IN
CEILING IN ACCESSIBLE LOCATIONS OR WITH ACCESS
PANELS IN HARD‐LID CEILINGS.
5. PIPING ON EXTERIOR WALLS OR PRE‐CAST CONCRETE
WALLS TO BE ROUTED IN FRAMED WALL ON INTERIOR
SIDE OF INSULATION.
6. PROVIDE FLEXIBLE PIPE CONNECTIONS TO ALL
MOTORIZED EQUIPMENT.
7. SEAL ALL PIPE PENETRATIONS THROUGH FIRE RATED
WALLS AND CEILING WITH APPROVED FIRE PROOF
MATERIALS AS SPECIFIED.
NOTES:
CONNECT NEW PRIMARY BOILER PIPING TO
EXISTING PIPING PER BOILER PIPING DIAGRAM ON
SHEET M 0.2.
EXISTING SECONDARY PUMPING SYSTEM TO
REMAIN.
CONNECT NEW 4" DIA BOILER INTAKE TO EXISTING
UPPER LOUVER. CONFIRM LOVER HAS
MANUFACTURE MINIMUM 20 SQUARE INCHES FREE
AREA. IF UPPER LOUVER DOES NOT HAVE 20
SQUARE INCHES FREE AREA CONNECT INTAKE TO
BOTTOM LOUVER AS WELL.
EXTEND NEW 4" DIA BOILER FLUE UP TO ROOF
THROUGH EXISTING B VENT. TERMINATE ON ROOF
PER MFR'S INSTRUCTIONS.
CONNECT AND EXTEND GAS PIPING TO NEW BOILER.
EXISTING GLYCOL FEEDER AND PUMP TO REMAIN.
1
FLAG NOTES:
4
3
2
1
4
3
2
5
5
6
6
SCALE:
MECHANICAL PLAN
1/8" = 1'-0"
VAIL, COLORADO 81657
09.24.14
SHEET TITLE:
NO. Job no.:
REVISION Drawn by:
Date:
Designed by:
DATE
BY 846 FOREST ROAD
EAUDIN
ANZE
COPYRIGHT 2014
B
G
C:\Users\cadd-drp\local settings\temp\AcPublish_9340\953800M03.dwg Printed By: cadd-drp September 24, 2014 - 1:27pm LC-XXX
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
9538.00
M0.3
MECHANICAL PARTIAL
FLOOR PLAN
ZRW
ZRW
10/20/14