HomeMy WebLinkAboutE1.0.pdfH/P HEAT/PHOTOELECTRIC SMOKE DETECTOR
ELECTRICAL LEGEND
(NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT)
RECESSED OR SURFACE DOWNLIGHT
WALL MOUNTED LIGHT FIXTURE
RECESSED FLUOR. LIGHT FIXTURE
SURFACE FLUOR. LIGHT FIXTURE
Aa
Aa
FIXTURE DESIGNATIONS:
UPPER CASE - FIXTURE TYPE
LOWER CASE - SWITCH DESIGNATION
SHADING ON FIXTURE INDICATES EMERG. BATTERY BACKUP
FLUORESCENT STRIP FIXTURE
TRACK LIGHT AS NOTED OR SCHEDULED
WALL WASHER
POLE-MOUNTED FIXTURE
POST (BOLLARD) FIXTURE
CEILING OR WALL MOUNTED EXIT LIGHT
EMERGENCY BATTERY LIGHTS
DUPLEX RECEPTACLE @ 18" UNLESS NOTED
DOUBLE DUPLEX RECEPTACLE @ 18" UNLESS NOTED
SPECIAL OUTLET AS NOTED
FLUSH FLOOR DUPLEX RECEPTACLE
DUPLEX RECEPTACLE HALF-SWITCHED @ 18" UNLESS NOTED
TELE-POWER POLE
JUNCTION BOX IN FLOOR, CEILING OR IN WALL
MULTI-OUTLET PLUG STRIP
COMPUTER/TELEPHONE OUTLET IN FLOOR OR WALL
CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING
TELEPHONE BACKBOARD
CIRCUIT HOMERUN
CONDUIT RUN BELOW FLOOR OR GRADE
CONDUIT STUB-UP - CAP & MARK
LIGHT SWITCH AT 46" UNLESS NOTED
SUBSCRIPTS:
2 = 2-POLE SWITCH
3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
K = KEY-OPERATED SWITCH
TO = THERMAL OVERLOAD SWITCH
P = SWITCH WITH PILOT LIGHT
DIMMER SWITCH W/ WATTAGE
MAGNETIC MOTOR STARTER
DISCONNECT SWITCH
TRANSFORMER
GROUND
PUSHBUTTON CONTROL STATION
PHOTOELECTRIC CELL
TIME SWITCH
THERMOSTAT AT 60" UNLESS NOTED
DIVISION 15 EQUIPMENT
CIRCUIT BREAKER
MOTOR OUTLET
AUTOMATIC TRANSFER SWITCH
FOOD SERVICE EQUIPMENT
PC
TS
T
ABBREVIATIONS
- ABOVE COUNTER
AC
AFF - ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
AFG
- ALUMINUM
AL
- EMERGENCY
EM
- GROUND
GND
- GROUND FAULT INTERRUPTER
GFI
NIC - NOT IN CONTRACT
NL - NIGHT LIGHT
NTS - NOT TO SCALE
UG - UNDERGROUND
WP - WEATHER PROOF
XFMR - TRANSFORMER
+18" - MOUNTING HEIGHT TO CENTERLINE
OF DEVICE AFF OR AFG
FIRE ALARM SYSTEM
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM PULL STATION
ALARM HORN OR SPEAKER
COMBINATION HORN/STROBE OR SPEAKER/STROBE
THERMAL HEAT DETECTOR
H
SMOKE/IONIZATION DETECTOR
I
PHOTOELECTRIC SMOKE DETECTOR
P
DUCT DETECTOR
SPRINKLER SYSTEM FLOW SWITCH
SPRINKLER SYSTEM TAMPER SWITCH
STROBE
SMOKE/FIRE DAMPER CONNECTION
REMOTE INDICATOR LIGHT
COMMUNICATION SYSTEM
SPEAKER IN CEILING OR WALL
VOLUME CONTROL AT 60" UNLESS NOTED
MICROPHONE OUTLET IN FLOOR BOX OR WALL
CALL-IN SWITCH
PROGRAM BELL
INTERCOM
CLOCK
AMPLIFIER
TELEVISION OUTLET
CONTACT DOOR SWITCH IN JAMB OR HINGE
SECURITY SYSTEM
KEY-OPERATED ACCESS SWITCH
SURVEILLANCE CAMERA
DISTRIBUTION EQUIPMENT SYMBOLS
DISCONNECT SWITCH
FUSES
CIRCUIT BREAKER
CURRENT TRANSFORMER
TRANSFORMER
METER
CU - COPPER
STEP LIGHT
FACP
M = MOTION-OPERATED SWITCH
POP-UP RECEPTACLE
- ELECTRICAL CONTRACTOR
EC
- AUTHORITY HAVING JURISDICTION
AHJ
- MECHANICAL CONTRACTOR
MC
- PLUMBING CONTRACTOR
PC
UTP - UNSHIELDED TWISTED PAIR
- GENERAL CONTRACTOR
GC
- REFERENCE
REF
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY
SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL
U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND
SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED
ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102
MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES
AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM) WIDE BY 1-3/8 IN. (35 MM) DEEP
CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE
OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER
TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE CONDUIT INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR
TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51
MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM
(OR SMALLER) STEEL ELECTRICAL METALLIC TUBING
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN.
(16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES,
RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM)
DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING
OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE
PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED,
AS TABULATED TO THE LEFT.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
PENETRATION THROUGH A FIRE-RATED WALL
T
18"(1'6")
46"(3'10")
48"(4'-0")
80"(6'8")
TYPICAL DEVICE
MOUNTING HEIGHTS
MAIN CIRCUIT BREAKER &
BRANCH CIRCUIT BREAKERS
MAXIMUM MOUNTING HEIGHT
IS 79", MINIMUM IS 18".
THE ELECTRICAL CONTRACTOR WILL PROVIDE A WALK THROUGH WITH THE
OWNER/ARCHITECT PRIOR TO FINAL ROUGHIN AS FOLLOWS:
x CONFIRM ALL LOCATIONS FOR LIGHT SWITCHES; ADD THREE WAYS IF
FOUND NECESSARY.
x REVIEW RECEPTACLE LOCATIONS; MOVE AS REQUIRED. PROVIDE
UNIT PRICING IF ADDITIONAL RECEPTACLES ARE REQUIRED.
x REVIEW RECEPTACLE LOCATIONS AT COUNTERS AND CONFIRM IF
THOSE RECEPTACLES SHOULD BE ABOVE COUNTER OR BELOW. MOVE
AS REQUIRED.
IN GENERAL CONFIRM POWER AND LIGHTING REQUIREMENTS. THE
ELECTRICIAN SHOULD BE PREPARED TO REWORK SOME DEVICE LOCATIONS.
SIGNIFICANT REWORK SHOULD BE FLAGGED AND UNIT PRICING PROVIDED
AND WRITTEN AUTHORIZATION FOR ADDITIONAL COSTS APPROVED PRIOR
TO PROCEEDING.
+80"AFF
P
+80:AFF
TELEPHONE ONE-
LINE DIAGRAM
TELEPHONE/
COMPUTER ROUGHIN
UNO - UNLESS NOTED OTHERWISE
2"C PVC WITH PULLWIRE
BURIED 20" BELOW GRADE
CATV
PEDESTAL
COAX RECEPTACLE IN SINGLE
GANG BOX @ 18" A.F.F. UNO
QUANTITIES PER FLOOR PLANS
(RG6 QUAD SHIELDED CABLE) 3/4"C
CONDUIT STUBBED TO ACCESSIBLE
CEILING, PLENUM RATED WIRE, WHEN
REQUIRED, RAN TO BACK BOARD
STRUCTURED CABLE
DISTRIBUTION PANEL
#6 CU G
METALLIC COLDWATER PIPE
ROUTE WIRE AT CEILING PARALLEL OR
PERPENDICULAR TO STRUCTURE. SECURE
TO STRUCTURE AT 4' INTERVALS OR LESS.
STUB UP TO ABOVE
ACCESSIBLE CEILNG
STRUCTURED CABLE
DISTRIBUTION PANEL
(2#CAT 6) 3/4"C
PLENUM RATED WIRE
WHEN REQUIRED
(1) RJ-11 & (1) RJ-45
IN SINGLE GANG
BOX AT 18" AFF UNO
COLD WATER PIPE
NOT TO SCALE
NOTES:
1. HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX
UNLESS NOTED OTHERWISE.
2. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP
OF DOOR TRIM AND CEILING LINE.
3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS
AND NOTED ON ELECTRICAL FLOOR PLANS SHALL GOVERN
OVER THOSE SHOWN ABOVE.
4. FOR CEILING HEIGHTS HIGHER THAN 7'2", INSTALL FIRE ALARM
NOTIFICATION AUDIO AND VISUAL APPLIANCES AT 80"AFF
OTHERWISE INSTALL AT 6" BELOW CEILING.
5. MOUNTING HEIGHTS PER IBC 2009 AND ADA CODES
MAIN TELE/DATA
ROOM
(PULLWIRE)4"C
NOT TO SCALE
NO SCALE
NO SCALE
FINISHED FLOOR
TYPICAL 8'0" CEILING
electrical apparatus as shown on single line diagram and
Complete provision, installation and connection of lighting fixtures,
exit signs and lamps as specified and as shown on drawings.
Complete branch circuit wiring required for the connection of
emergency lighting and exit signs to existing emergency stand
Complete feeder(s) installation as required for new and/or
devices, new control devices, etc. for a complete lighting and
including new panelboards, new conduits, new wires, new wiring
Complete wiring system for new lighting and power as shown,
contract. Electrical work shall include, but not limited to, these major
as indicated on drawing and as specified, as necessary to complete the
SCOPE: Furnish all materials and labor required to execute this work
2.
A.
ELECTRICAL SPECIFICATIONS
1.
drawings.
by power system.
and power system.
b.
a.
items:
N. All cabling shall be bundled and properly secured and terminated.
warranty period shall begin at the point of system acceptance or beneficial
system during this warranty period at no additional cost to the owner. The
free of defects of workmanship or products and will inspect and repair the
from the date of project completion. The contractor warrants the system to be
O. The warranty set forth for this system shall consist of a full three (3) years
use, whichever comes later.
Coordinate numbering scheme with owner.
enclosed within cable trays, raceways or conduit, as specified.
engineer. Cabling shall be in the wall, above the ceiling or where exposed,
M. No exposed wiring will be accepted unless approved in writing by the
Care must be taken to ensure cables are not kinked, bent beyond limit,
including NEC, EIA/TIA 568,569 and 606, and federal, state and local codes.
familiar and install in accordance with all applicable codes and standards,
L. All cable hangers shall be no more than 48" apart. Contractor shall be
Cables are to be kept a minimum of 6" from power lines, electric motors,
K. Cable bends shall be no less than eight times the cable diameter or 1.00".
termination. No more than .5 inches of exposed untwisted pairs shall be
the extent in which each twisted pair is unraveled at the point of its physical
J. All connections of twisted wiring shall be made in such a way as to minimize
length of the run. Splices and bridge taps with cabling are strictly prohibited.
Cabling shall be free from tension at both ends, as well as through out the
I. All wiring shall be protected from moving mechanical or physical contacts.
cable runs exceeding 90 meters and provide solution to meet the 90 meter
H. Route cables so as not to exceed 90 meters in length. Bidder will identify any
the case of "hard" drywall ceilings, adequate support shall be accomplished
independent hangers. Cable "draped" across ceiling tiles is unacceptable. In
G. All cable above the ceiling must be tied and properly supported with
F. Provide plenum rated cable when required by article NEC 300-22.
overloaded, over-cinched, crushed, improperly untwisted, etc.
fluorescent fixtures or heat generating devices.
present at these locations.
Wiring is to be run in cable tray and conduit where specified.
requirement.
where reasonably possible.
patch panel location, and each wall/floor faceplate that has wiring installed.
E. All cables will be labeled with self-laminating labels at each cable end, at each
jacks, match faceplates to power, color coded for voice and data, match to
modular RJ-45, 8 pin, 8 conductor, Hubbell, Leviton, or lucent or equivalent
C. The terminations at the station locations must be Category 6, T568B (AT&T)
B. Data cable will be colored blue. Voice cable will be colored white.
manufacturers include: Berk-Tek, Belden, Lucent or equivalent.
500 Mhz or better category 6, 4 pair UTP as applicable. Acceptable
A. The cabling for voice and data must be continuous, home run, non-spliced,
D. Wall mounted patch panels will be provided.
cable. Outlets will be securely held in place.
B. Cat 6 Wiring Requirements
A. General Requirements
14.
decora style. Finish per owner or architect. All dwelling unit
Convenience receptacles will be 20 amp, commercial grade
Light switches will be 20 amp, commercial grade,
B.
ELECTRICAL DEVICES
A.
decora style. Finish per owner or architect.
Provide decora style, finish per owner or architect.
Dimming switches will be a minimum of 600W or as noted.
C.
15.
Support all electrical equipment independent of accessible ceilings as
required by NEC.
SUPPORT
A.
All mounting heights will conform to ADA guidelines. Typical receptacle
D.
heights will be +18"AFF and switch heights will be +46"AFF
unless noted otherwise.
16.
At fire rated wall, space electrical boxes at opposite sides of the wall
no less than 24" horizontal distance.
ELECTRICAL BOXES
A.
When phone, TV & power receptacles are shown on plan next to each other.
Locate respective receptacles next to each other on site with no more
B.
than 1" separating cover plates.
Provide GFI type receptacles at kitchens, bathrooms,
garages, exterior etc. as required by code.
E.
equipment, etc. furnish by mechanical - refer to both electrical and
and mechanical drawing for scope and work and additinal infor-
Complete connection of HVAC/Plumbing motor(s), water heater(s),
Fire alarm system will be by electrical contractor.
3.
4.
6.
5. Provide grounding and bonding Facilities.
Complete all electrical demolition as required.
mation.
A. Contractor shall submit shop drawings for engineer review and approval.
Lighting fixtures.
Shop drawing submittal shall include:
Panelboard(s).
CONDUIT AND WIRE:
B.
13.
A.
B.
2.
1.
and contractor shall have written approvals from building owner prior
Core drilling and patching of existing building structure required for
Operating, Maintenance and identification instructions manuals, if
electrical work. Core drilling shall follow Building Standard procedures
Applicable codes: National Electric Code (2014)
PERMITS AND FEES: Obtain and pay for all necessary permits, inspec-
tions, examinations and fees or charges necessary for execution and
and to the requirements of Federal, State or other City agencies
Town of Vail Electrical Code, pertinent NFPA publications
Conform to the prevailing edition and amendments thereto of the
SHOP DRAWINGS AND SUBMITTAL:
to start of any work.
Test of entire system and work.
REGULATIONS AND CODES:
having jurisdiction.
completion of electrical work.
12.
11.
A.
7.
9.
8.
10.
any.
receptacles to be tamper-resistant per NEC 406.11.
MC cable permitted per local codes. Run hard pipe from panel to local
junction box, and run MC cable from junction box to device.
CONDUCTOR SIZES AND TYPES: For sizes #1/0 AWG and larger, use
coppper THW or aluminum XHHW. For sizes #1 AWG and smaller, use only
copper wire with 600V insulation, types TW, THHN, or THW - stranded in
sizes #8 and larger, solid in sizes #10 and smaller. Control wiring shall be #14,
stranded. Use type THHN for wires entering or passing through fluorescent
lighting fixtures. All motors shall be wired with copper conductors only.
17. METERING
A. EC shall coordinate whether or not meters require lever bypass with local
utility and provide all meters with a lever bypass when required.
CONDUIT OR CIRCUIT CONTINUES
&RS\ULJKWE\=HKUHQߙ$VVRFLDWHV,QF