HomeMy WebLinkAboutE1.1.pdfNO SCALE
NOTE: PROVIDE #3/0 CU CONDUCTORS TO ALL GROUNDING ELECTRODES.
N
G
INCOMING WATER SERVICE
PIPE
(3) 3/4"x10' DRIVEN
GROUND RODS IF
REQUIRED BY
LOCAL AHJ
BONDING JUMPER
(#3/0 CU G)3/4"C
#6 TO TELEPHONE/TV
CONCRETE- ENCASED
ELECTRODE
WATER METER
BUILDING STEEL
INCOMING GAS SERVICE PIPE
NO SCALE
NOTE: PROVIDE SHORT CIRCUIT BRACING TO MEET REQUIREMENTS NOTED
AT ONE-LINE, NOTED AS "AIC AVAILABLE". SERIES RATED COMBINATION
ACCEPTABLE, SUBMIT MANUFACTURER'S SERIES RATINGS WITH SHOP
DRAWING REVIEW.
T
BFAG1
PANEL
BFAG2
PANEL
400/3
2[(4 #350 CU, 1 #1 CUG) 3"C]
OR 2[(4 #350 MCM AL, 1 #2/0 ALG) 4"C]
UTILITY
TRANSFORMER
PAD MOUNTED
MAIN DICONNECT & METER
400A, 120/208V, 3P, 4W
42kAlC
2[(4#500 MCM AL)4"C]
HOLY CROSS UTILITY
JUNCTION BOX
(COORD. LOCATION
WITH UTILITY)
PROVIDE 400A DIRECT METER ,
CONTINUOUS DEMAND AMPS IS
LESS THAN 320A(SEE SHEET E1.1).
&RS\ULJKWE\=HKUHQߙ$VVRFLDWHV,QF
03/12/15