HomeMy WebLinkAboutE2.0.pdfTAG DESCRIPTION LOAD VOLTAGE PHASE WIRE SIZE (CU) CONNECTION CIRCUIT BREAKER REMARKS CU-1 CONDENSING UNIT #1 26 MCA 208 1 (3 #10, 1 #10G) 3/4"C 30/2 30A2P THERMAL EF-1 EXHAUST FAN #1 12 W 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P SWITCH THERMAL EF-2 EXHAUST FAN #1 20 W 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P SWITCH EH-1 ELECTRIC DUCT HEATER #1 14.8 KW 208 3 (4 #6, 1 #10G) 1"C 60/3 60A3P FC-1 FAN COIL #1 3.5 MCA 208 1 (3 #12, 1 #12G) 3/4"C CONNECT THRU CU-1 CONNECT THRU CU-1 FC-2 FAN COIL #2 33 MCA 208 3 (4 #8, 1 #10G) 1"C 40/3 40A3P THERMAL HRV-1 HEAT RECOVERY UNIT #1 9.5 MCA 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P SWITCH THERMAL PP-1 PLUMBING PUMP 25W 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P SWITCH WH-1 ELEC. WATER HEATER #1 2 KW 208 1 (3 #10, 1 #12G) 3/4"C 30/2 30A2P MECHANICAL SCHEDULE NOTE: VERIFY ALL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN. KW BB-2 BERKO BKOC25026W SEE PLANS SEE PLANS 2.5' 1700.0 0.50 BB-3 BERKO BKOC2503W SEE PLANS SEE PLANS 3' 2600.0 0.75 BB-4 BERKO BKOC2504W SEE PLANS SEE PLANS 4' 3400.0 1.00 BB-6 BERKO BKOC2506W SEE PLANS SEE PLANS 6' 5100.0 1.50 SERVICE REMARKS 208/1/60 208/1/60 ELECTRICAL DATA 208/1/60 SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS 208/1/60 SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS ELECTRIC BASEBOARD SCHEDULE OR EQUIVALENT SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS CAPACITY (BTUH) UNIT TAG MANUFACTURER & MODEL NO. LOCATION LENGTH (IN) V / PH / Hz 04/27/15