HomeMy WebLinkAboutE2.0.pdfTAG DESCRIPTION LOAD VOLTAGE PHASE WIRE SIZE (CU) CONNECTION CIRCUIT BREAKER REMARKS
CU-1 CONDENSING UNIT #1 26 MCA 208 1 (3 #10, 1 #10G) 3/4"C 30/2 30A2P
THERMAL
EF-1 EXHAUST FAN #1 12 W 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P
SWITCH
THERMAL
EF-2 EXHAUST FAN #1 20 W 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P
SWITCH
EH-1 ELECTRIC DUCT HEATER #1 14.8 KW 208 3 (4 #6, 1 #10G) 1"C 60/3 60A3P
FC-1 FAN COIL #1 3.5 MCA 208 1 (3 #12, 1 #12G) 3/4"C CONNECT THRU CU-1 CONNECT THRU CU-1
FC-2 FAN COIL #2 33 MCA 208 3 (4 #8, 1 #10G) 1"C 40/3 40A3P
THERMAL
HRV-1 HEAT RECOVERY UNIT #1 9.5 MCA 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P
SWITCH
THERMAL
PP-1 PLUMBING PUMP 25W 120 1 (2 #12, 1 #12G) 1/2"C OVERLOAD 20A1P
SWITCH
WH-1 ELEC. WATER HEATER #1 2 KW 208 1 (3 #10, 1 #12G) 3/4"C 30/2 30A2P
MECHANICAL SCHEDULE
NOTE: VERIFY ALL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
KW
BB-2 BERKO BKOC25026W SEE PLANS SEE PLANS 2.5' 1700.0 0.50
BB-3 BERKO BKOC2503W SEE PLANS SEE PLANS 3' 2600.0 0.75
BB-4 BERKO BKOC2504W SEE PLANS SEE PLANS 4' 3400.0 1.00
BB-6 BERKO BKOC2506W SEE PLANS SEE PLANS 6' 5100.0 1.50
SERVICE REMARKS
208/1/60
208/1/60
ELECTRICAL DATA
208/1/60 SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS
208/1/60 SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS
ELECTRIC BASEBOARD SCHEDULE OR EQUIVALENT
SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS
SEE PLANS FOR T-STAT LOCATIONS, PROVIDE INTEGRAL T-STAT IF LOCATION IS NOT SHOWN ON PLANS
CAPACITY
(BTUH)
UNIT
TAG
MANUFACTURER &
MODEL NO.
LOCATION LENGTH
(IN) V / PH / Hz
04/27/15