HomeMy WebLinkAboutP1.0.pdfUNIT
TAG
MANUFACTURER & MODEL NO DESCRIPTION WASTE VENT
COLD
WATER
HOT
WATER
REMARKS
LV LAVATORY 1-1/2" 1-1/2" 1/2" 1/2"
KS KITCHEN SINK 2" 1-1/2" 3/4" 3/4"
DW DISHWASHER 1-1/2" - - 1/2"
SS SERVICE SINK 2" 1-1/2" 3/4" 3/4"
DF
DRINKING FOUNTAIN 1-1/2" 1-1/2" 1/2" -
UR URINAL (FLUSH VALVE) 2" 1-1/2" 3/4" -
WC WATER CLOSET 3" 2" 1/2" -
RD-1 ROOF DRAIN 3" - - - COORDINATE INSTALLATION DETAILS WITH ARCHITECT AND GC
RD-2 PLANTED ROOF DRAIN 3" - - - COORDINATE INSTALLATION DETAILS WITH ARCHITECT AND GC
FD ZURN Z415B 2" FLOOR DRAIN 2" 1-1/2" - - PROVIDE PROSET TRAP GUARD
FPHB WOODFORD MODEL 17 FREEZEPROOF HOSE BIBB - - 3/4" -
BWV WATTS BV-200 BACKWATER VALVE 4" - - - TO BE INSTALLED ON COMMON WASTE LINE PRIOR TO EXITING BUILDING. COORDINATE ACCESS IN FIELD.
CO ZURN ZN1400 CLEAN OUT VARIES - - -
WCO ZURN Z1441 WALL CLEAN OUT VARIES - - -
COTG ZURN Z1400 CLEAN OUT TO GRADE VARIES - - - LOCATE WITHIN 5' OF THE BUILDING
PLUMBING FIXTURE CONNECTION SCHEDULE
PLUMBING FIXTURE SPECIFICATIONS & HARDWARE
SELECTION TO BE BY THE ARCHITECT OR INTERIOR
DESIGNER. FIXTURE ALLOWANCE NOT TO EXCEED THE
ESTABLISHED BUDGET.
IN OUT
AMPS H(IN) D(IN)
WH-1
RHEEM
PROE30 1 RH93 POU
HOT WATER MECH ROOM 30 2 - 40 140
17 30 21.75 340
INPUT
(KW)
UNIT
TAG
MANUFACTURER &
MODEL NO.
WATER TEMP. (°F) ELECTRICAL DATA
V / PH / Hz
120 / 1 / 60
ELECTRIC WATER HEATER SCHEDULE
OR EQUIVALENT
SERVICE LOCATION
STORAGE
CAPACITY
(GAL.)
GPH @
90°F ∆T
(8000')
OPER. WT.
(LBS)
REMARKS
OR EQUIVALENT
V / PH / Hz HP\W
PP-1
GRUNDFOS
UP 10-16 BU/ATLC
HOT WATER
RECIRCULATION
WATER HEATER INLINE 2.4 1.0 - 115/1/60 25 W
BRONZE PUMP, AQUASTAT, PROVIDE SWITCH TO SHUT OFF POWER TO PUMP DURING
EXTENDED UNOCCUPIED PERIODS.
MANUFACTURER &
MODEL NO.
REMARKS
PUMP SCHEDULE
SERVICE LOCATION TYPE GPM
TOTAL
HEAD
(FT)
RPM
ELECTRICAL DATA
UNIT
TAG
03/12/15