Loading...
HomeMy WebLinkAboutTest & Balance Report.pdf TEST, ADJUST AND BALANCE REPORT PROJECT BETTY FORD ALPINE GARDENS #1165 PREPARED FOR SKYLINE MECHANICAL REPORT ISSUE DATE 7/9/2015 PREPARED BY HVAC TAB llc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB llc DATE: 7/8/2015 INSTRUMENT CALIBRATION REPORT PROJECT : BETTY FORD ALPINE GARDEN PROJECT ALTITUDE: “HG INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE SHORTRIDGE ADM-870C / #M00483 AIR FLOW READINGS 7/8/2015 06/08/2015 06/08/2016 ANEMOMETER #T57251515001 AIR FLOW READINGS 7/8/2015 04/6/2015 04/6/2016 SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * * TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2015 06/03/2016 PITOT TUBE 18” PRES. READINGS 7/8/2015 N/A N/A PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A PITOT TUBE 48” PRES. READINGS NOT USED NA NA SHIMPO TACHOMETER / #C105B0010 RPM READINGS NOT USED 06/03/2015 06/03/2016 FLUKE 375 / #21290229 VOLT / AMP 7/8/2015 06/03/2015 06/03/2016 SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS NOT USED 06/08/2015 06/08/2016 ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * * FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/11/2015 06/11/2016 REFRACTOMETER RHA-100 / #RHA- 100 GLYCOL % READINGS NOT USED N/A N/A * CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: NOTES: HI SPEED HVAC TAB llc DATE: 7/8/2015 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER MITSUBISHI MODEL PEAD-A42AA5.MX SERIAL 4YR000078 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1485CFM@0.4"ESP MIN OSA CFM 0 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. - - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208/230 2.8 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE DD MOTOR BORE DD FAN DRIVE DD FAN BORE DD NO. BELTS & SIZE DD ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY SPEED STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (AMPS) NONE SET AT (AMPS) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. DD DD VOLTAGE 212 212 AMPERAGE 0.9 0.9 PAGE: AIRFLOW DATA SUPPLY CFM 1139 OSA CFM 0 RETURN CFM 1139 PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: FC-1 DX COIL F I L T E R -0.06" 0.20" -0.07" ELECTRIC COIIL NOTES: HI SPEED HVAC TAB llc DATE: 7/8/2015 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER MARKEL PRODUCTS MODEL F3E7210-2 SERIAL 248642-1 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 950 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 1/4 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 120 5.3 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE DD MOTOR BORE DD FAN DRIVE DD FAN BORE DD NO. BELTS & SIZE DD ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY SPEED STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (AMPS) NONE SET AT (AMPS) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. DD DD VOLTAGE 57 121 AMPERAGE 3.0 5.3 PAGE: AIRFLOW DATA SUPPLY CFM 997 RETURN CFM 997 PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: FC-2 ELECTRIC COIL F I L T E R -0.09" 0.23" HVAC TAB llc DATE: 7/8/2015 FAN NUMBER HRV-1 NOT USED UNIT DATA UNIT DATA UNIT DATA MANUFACTURER ALDES MODEL H650A-RI SERIAL H650-RI1502001 SCHEDULE RATING/OUTLET TOTAL 400CFM@0.25"ESP MOTOR DATA MOTOR DATA MOTOR DATA MANUFACTURER - - MOTOR HP RPM - - PHASE FRAME - - S.F. TYPE - - VOLTS AMPS 120 5.5 DRIVE DATA DRIVE DATA DRIVE DATA MOTOR DRIVE BORE DD DD FAN DRIVE BORE DD DD NO. BELTS SIZE DD DD DRIVE CHANGE ROTATION DD CORRECT STARTER DATA STARTER DATA STARTER DATA MFG. MODEL NONE NONE RANGE SET AT (AMPS) NONE NONE SET AT HERTZ REQ. THERM NONE NONE THERMAL PROTECTION NONE NONE TEST DATA TEST DATA TEST DATA CFM VOLTS 540 121 FAN RPM AMPS DD 5.2 ERV FAN TEST REPORT PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: HRV-1 PAGE: NOTES: LOW SPEED OUTSIDE AIR -0. OUTSIDE AIR -0.05" RETURN -0. RETURN -0.35" EXHAUST 0.17" EXHAUST 0. SUPPLY 0. SUPPLY 0.05" SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-1 1 SR 5/3 30 58 23 2 SR 5/3 30 25 25 3 SR 5/3 30 19 22 4 SR 28/3 465 409 348 5 SR 28/3 465 298 357 6 SR 28/3 465 405 364 1485 1214 1139 TOTAL FC-2 1 SR 9/3 190 84 195 2 SR 9/3 190 97 206 3 SR 9/3 190 111 199 4 SR 9/3 190 107 196 5 SR 9/3 190 101 201 950 500 997 TOTAL HRV-1 SUPPLY 1 - PITOT 290 470 434 2 SR 5/3 90 50 84 3 SR 5/3 20 20 22 400 540 540 TOTAL HRV-1 EXHAUST 1 ER 8/5 150 87 150 2 ER 8/5 150 240 147 3 ER 5/5 100 114 105 400 441 402 TOTAL NOTES: HVAC TAB llc DATE: 7/8/2015 AIR TERMINAL TEST REPORT PAGE: PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: FC-1 / FC-2 / HRV-1