HomeMy WebLinkAboutTest & Balance Report.pdf TEST, ADJUST AND BALANCE REPORT
PROJECT
BETTY FORD ALPINE GARDENS
#1165
PREPARED FOR
SKYLINE MECHANICAL
REPORT ISSUE DATE
7/9/2015
PREPARED BY
HVAC TAB llc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB llc
DATE: 7/8/2015
INSTRUMENT
CALIBRATION REPORT
PROJECT : BETTY FORD ALPINE GARDEN PROJECT ALTITUDE: “HG
INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE
SHORTRIDGE ADM-870C / #M00483 AIR FLOW READINGS 7/8/2015 06/08/2015 06/08/2016
ANEMOMETER #T57251515001 AIR FLOW READINGS 7/8/2015 04/6/2015 04/6/2016
SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * *
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2015 06/03/2016
PITOT TUBE 18” PRES. READINGS 7/8/2015 N/A N/A
PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 48” PRES. READINGS NOT USED NA NA
SHIMPO TACHOMETER / #C105B0010 RPM READINGS NOT USED 06/03/2015 06/03/2016
FLUKE 375 / #21290229 VOLT / AMP 7/8/2015 06/03/2015 06/03/2016
SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS NOT USED 06/08/2015 06/08/2016
ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * *
FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/11/2015 06/11/2016
REFRACTOMETER RHA-100 / #RHA-
100
GLYCOL % READINGS NOT USED N/A N/A
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE:
NOTES: HI SPEED
HVAC TAB llc
DATE: 7/8/2015
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER MITSUBISHI
MODEL PEAD-A42AA5.MX
SERIAL 4YR000078
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1485CFM@0.4"ESP
MIN OSA CFM 0 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. - -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208/230 2.8
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE DD
MOTOR BORE DD
FAN DRIVE DD
FAN BORE DD
NO. BELTS & SIZE DD
ROTATION CORRECT
CENTERLINE MOTOR ADJ PULLEY SPEED
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. DD DD
VOLTAGE 212 212
AMPERAGE 0.9 0.9
PAGE:
AIRFLOW DATA
SUPPLY CFM 1139
OSA CFM 0
RETURN CFM 1139
PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: FC-1
DX COIL
F I
L T
E R
-0.06" 0.20" -0.07"
ELECTRIC
COIIL
NOTES: HI SPEED
HVAC TAB llc
DATE: 7/8/2015
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER MARKEL PRODUCTS
MODEL F3E7210-2
SERIAL 248642-1
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 950 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 1/4 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 120 5.3
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE DD
MOTOR BORE DD
FAN DRIVE DD
FAN BORE DD
NO. BELTS & SIZE DD
ROTATION CORRECT
CENTERLINE MOTOR ADJ PULLEY SPEED
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. DD DD
VOLTAGE 57 121
AMPERAGE 3.0 5.3
PAGE:
AIRFLOW DATA
SUPPLY CFM 997
RETURN CFM 997
PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: FC-2
ELECTRIC COIL
F I
L T
E R
-0.09" 0.23"
HVAC TAB llc
DATE: 7/8/2015
FAN NUMBER HRV-1 NOT USED
UNIT DATA UNIT DATA UNIT DATA
MANUFACTURER ALDES
MODEL H650A-RI
SERIAL H650-RI1502001
SCHEDULE RATING/OUTLET TOTAL 400CFM@0.25"ESP
MOTOR DATA MOTOR DATA MOTOR DATA
MANUFACTURER - -
MOTOR HP RPM - -
PHASE FRAME - -
S.F. TYPE - -
VOLTS AMPS 120 5.5
DRIVE DATA DRIVE DATA DRIVE DATA
MOTOR DRIVE BORE DD DD
FAN DRIVE BORE DD DD
NO. BELTS SIZE DD DD
DRIVE CHANGE ROTATION DD CORRECT
STARTER DATA STARTER DATA STARTER DATA
MFG. MODEL NONE NONE
RANGE SET AT (AMPS) NONE NONE
SET AT HERTZ REQ. THERM NONE NONE
THERMAL PROTECTION NONE NONE
TEST DATA TEST DATA TEST DATA
CFM VOLTS 540 121
FAN RPM AMPS DD 5.2
ERV FAN TEST REPORT
PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: HRV-1
PAGE:
NOTES: LOW SPEED
OUTSIDE AIR -0. OUTSIDE AIR -0.05"
RETURN -0. RETURN -0.35" EXHAUST 0.17" EXHAUST 0.
SUPPLY 0. SUPPLY 0.05"
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
FC-1 1 SR 5/3 30 58 23
2 SR 5/3 30 25 25
3 SR 5/3 30 19 22
4 SR 28/3 465 409 348
5 SR 28/3 465 298 357
6 SR 28/3 465 405 364
1485 1214 1139 TOTAL
FC-2 1 SR 9/3 190 84 195
2 SR 9/3 190 97 206
3 SR 9/3 190 111 199
4 SR 9/3 190 107 196
5 SR 9/3 190 101 201
950 500 997 TOTAL
HRV-1 SUPPLY 1 - PITOT 290 470 434
2 SR 5/3 90 50 84
3 SR 5/3 20 20 22
400 540 540 TOTAL
HRV-1 EXHAUST 1 ER 8/5 150 87 150
2 ER 8/5 150 240 147
3 ER 5/5 100 114 105
400 441 402 TOTAL
NOTES:
HVAC TAB llc
DATE: 7/8/2015
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: BETTY FORD ALPINE GARDENS SYSTEM: FC-1 / FC-2 / HRV-1