HomeMy WebLinkAboutWVFS #3 Heat Trace Rev Letter Stamped.pdf BEAuDIN GANZE September 23, 2014 consulting engineers, inc. Town of Vail Building Department 75 S. Frontage Road West Vail, CO 81657 RE: West Vail Fire Station #3—Heat Trace Power Revisions Project#8776.00 The purpose of this letter is to describe an electrical scope of work and affirm code compliance to make necessary revisions and corrections to the originally installed roof heat trace system power feed at the West Vail Fire Station#3, in Vail, Colorado. The following is a description of the scope of work: • Replace the existing 20 amp, 3-pole circuit breaker in existing panel `P2' with a 40 amp, 3-pole circuit breaker to serve an existing heat trace control panel rated at 34.4 amps. • Replace existing#10 AWG conductor feeders to existing heat trace control panel with 3- #8 AWG+#10 ground. Sincerely, ,i',9:40 LICE ••el •• P S • OS O I t/ 422 5 ,', Marc Sacconi, PE o�FON SSI • •A\-` .,, Senior Project Engineer """""''' Attachments: See attached modified plans, the blue text and markups reflect the scope of work. 222 Chapel Place,Unit AC-201 P 0 Box 9650 Avon.CO 81620•p 970.949 6108 VAIL ALBUQUERQUE DENVER FORT COLLINS VAIL ( t sem cnc-mas Dcsirot,%km'1 ad I n c I Ica;1 m.r l'o,cr kc,LIN