HomeMy WebLinkAboutB14-0408 REV1 load calcs.pdfDanici Electric, Inc.
PO Box 7246 ~ Breckenridge, CO 80424
Phone (970) 390-1173 ~ Fax (970) 547-9221
sparky63@danicielectric.com
November 18, 2014
Revision #3
Attn: Dave Dantas & Mikael Pukas
D.W. Dantas Construction, LLC
PO Box 2322
Avon, CO 81652
The following are Load Calculations for 1772 Alpine Drive, Vail, CO 81657:
General Lighting 14,940VA
Small Appliance 3,000VA
Laundry 1,500VA
TOTAL 19,440VA
3,000VA at 100% 3,000VA
19,440VA – 3,000VA 16,440VA
16,440VA at 35% 5,754VA
NET LOAD 8,754VA
Range 8,000VA
Oven 4,000VA
Dryer 5,000VA
Steamer 8,000VA
Elevator 4,500VA
Add’l Small Appliance 1,500VA
Two Exterior Receptacles 360VA
Add’l Exterior Lighting 320VA
NET CALCULATED LOAD 40,434VA
40,434VA /240V = 169A
169A TOTAL LOAD CALC
200A Service is Required
Respectfully,
David Novak
Danici Electric, Inc.